Adicos GSME-X22 User manual

EN
GSME-X22
Supplementary Instructions Manual
Fire Gas Detector GSME®

2ADICOS X22-Melder405-2010-003 EN21
Supplementary Instructions for GSME-X22
Article number: 400-2410-002
Index: EN21
Release date: 28.01.20
– Translation –
Manufacturer:
GTE Industrieelektronik GmbH
Helmholtzstr. 21, 38-40
41747 Viersen
GERMANY
Support hotline: +49 2162 3703-0
E-Mail: [email protected]
© 2020 GTE Industrieelektronik GmbH – This document and all figures contained may not be copied,
changed, or distributed without explicit approval by the manufacturer!
Subject to technical changes!
ADICOS®and GSME®are registered trademarks of GTE Industrieelektronik GmbH.

I
ADICOS X22-Melder 405-2010-003 EN21
Abstract
The Advanced Discovery System (in short: ADICOS) is used for early detection of fire scenarios
in the industrial environment. It comprises different, independent detector units that enable inter-
ference-resistant fulfillment of the detection objective defined during planning via suitable layout
and parameterization.
The detector units are connected using the ADICOS M-bus to a central unit, which enables
voltage supply and parameterization of every individual detector, and which stores all sensor
data for statistical analyses.
ADICOS X22-Detectors are designed for for operation within explosive atmospheres of ATEX
zone 22.

II ADICOS X22-Melder405-2010-003 EN21
CONTENTS
Contents
1 About this manual .......................................... 1
1.1 Objective ........................................... 1
1.2 Explanation of symbols .................................. 1
1.3 Storing the manual ..................................... 1
2 Safety instructions........................................... 2
2.1 Intended use ......................................... 2
2.2 Standards and regulations ................................ 2
2.3 Personnel qualification ................................... 3
2.4 Handling electrical voltage ................................ 3
2.5 Modification ......................................... 3
3 Structure ................................................. 4
3.1 Overview ........................................... 4
3.3 Type plate information ................................... 6
4 Installation ............................................... 7
4.1 Mounting ........................................... 7
4.2 Wiring ............................................. 8
5 Commissioning ............................................ 8
6 Operation ............................................... 8
3.2 Cable assignment ...................................... 5
7 Maintenance: Detector replacement .............................. 9
8 Technical Data ............................................10
9 Appendix: ADICOS mounting plate...............................11

1
ADICOS X22-Melder 405-2010-003 EN21
ABOUT THIS MANUAL
1 About this manual
1.1 Objective
This manual describes the special requirements on installation, wiring, commissioning, and
operation of ADICOS detectors for explosive atmospheres of ATEX zone 22. They are
exclusively addressed to knowledgeable specialist personnel (–› Chap. 2, Safety instructions).
1.2 Explanation of symbols
This manual features a continuous structure for best possible comprehension. The following
labels are used.
Warning signs
This manual uses the following information types.
NOTE!
This information type provides information directly important for further
system operation.
WARNING!
This information type signals a danger that can lead to fatal or severe
injuries.
DANGER!
This information type signals a danger that directly leads to fatal or severe
injuries.
1.3 Storing the manual
Store this manual easily reachable and in direct vicinity of the detector system to enable use
as needed.

SAFETY INSTRUCTIONS
2ADICOS X22-Melder405-2010-003 EN21
2 Safety instructions
ADICOS detectors for explosive atmospheres of ATEX zone 22 (short: ADICOS X22-Detectors)
ensure operational safety assuming proper installation, commissioning, operation, and
maintenance. For this purpose, it is absolutely required to completely read, understand, and
follow this manual and the safety information contained.
WARNING!
Installation and operating errors can lead to fatal and severe injuries and
damage to the industrial plant.
−Read and follow this manual carefully!
2.1 Intended use
ADICOS X22-Detectors are designated for the detection of fire scenarios in explosive
atmospheres of ATEX zone 22. In this context, the operating parameters described in
Chap. 8, »Technical data« must be met. Any deviating use requires prior consultation with the
manufacturer.
Compliance with this manual as well as all applicable country-specific provisions is also part
of the intended use.
2.2 Standards and regulations
The safety and accident prevention regulations applicable for the specific application must be
observed during detector installation, commissioning, maintenance, and test.
The following standards and directives are of particular importance when handling potentially
explosive atmospheres:
Regulation Description
DIN EN 60079-0:2012 + A11:2013
IEC 60079-0:2011
Explosive atmospheres
Equipment - General requirements
DIN EN 60079-31:2014 Explosive atmospheres
Equipment protection by intrinsic safety “t”
DIN EN 60529:2014-09 Degrees of protection provided by enclosures
Guideline Description
2014/34/EU ATEX Product Directive
1999/92/EG ATEX Operational Directive

3
ADICOS X22-Melder 405-2010-003 EN21
SAFETY INSTRUCTIONS
2.3 Personnel qualication
Any work on ADICOS systems may only be performed by qualified personnel. Persons, who
can perform work on electrical systems and recognize possible dangers based on their pro-
fessional education, knowledge, and experience as well as knowledge of the applicable
provisions, are considered qualified personnel.
WARNING!
Installation, commissioning, parameterization, and maintenance may only be
performed by authorized and respectively trained personnel
2.4 Handling electrical voltage
DANGER!
The electronics of ADICOS X22-Detectors works with an electrical voltage that
can trigger an explosion in potentially explosive atmospheres.
−Do not open enclosure!
−De-energize the entire detector system and secure against
unintentionally reactivation for all wiring work!
2.5 Modication
Any form of unauthorized modifications or extensions are expressively prohibited! In case of
doubt, contact the manufacturer.

STRUCTURE
4ADICOS X22-Melder405-2010-003 EN21
3 Structure
3.1 Overview
100
100
28
1
2
3
4
5
No. Description
①Enclosure
②Display elements
③ GSME spray protection
④Sinter metal filter
⑤Cable gland

5
ADICOS X22-Melder 405-2010-003 EN21
STRUCTURE
3.2 Cable assignment
Wire Color Signal Limit value contact
1 black Operating voltage
24 ... 40 V DC non-polarised
1 white
2 black Relay output X6 e Alarm NO1
2 white Relay output X6 a Alarm NO1
3 black Relay output X7 a Fault NC
3 white Relay output X7 e Fault NC
4 black M-Bus
max. 40 V non-polarised
4 white
1 with series resistor, standard 680 Ω
Analog signal option
Wire Color Signal Analog signal
5 black Analog signal - protected
against polarity reversal
4 ... 20 mA
6 black Analog signal - protected
against polarity reversal
0 ... 5 V
0 ... 10 V
5 white Analog signal 4 ... 20 mA
6 white Analog signal 0 V
Option Fire panel interface
Wire Color Interface module Siemens
FDnet
Bosch
LSNi
5 black Interface module A - in FDnet (+) LSN a in
5 white Interface module B - in FDnet-A (-) LSN b1 in
6 black Interface module A - out FDnet (+) LSN a out
6 white Interface module B - out FDnet-B (-) LSN b2 out
Option Auxiliary relay
Wire Color Auxiliary relay
5 black -
5 white Normally open
6 black Normally closed
6 white Common

STRUCTURE
6ADICOS X22-Melder405-2010-003 EN21
3.3 Type plate information
The type plate of the ADICOS X22-Detectors
contains the following information:
NOTE!
Until 12-2014, some ADICOS X22-Detectors have been labeled as
ADICOS Ex detectors.
GTE Industrieelektronik GmbH
Typ K.N.
IP
6X
T100°C Dc
-20 ≤ t
amb
≤ 50
Art.
Bj.
I
k
21,6-40V
DC
/14VA
-X22 GS.xx.IR. xxx 20xx
400-2410-0xx
°C
II 3D Ex tc IIIC
S/N
V/VA

7
ADICOS X22-Melder 405-2010-003 EN21
INSTALLATION
4 Installation
4.1 Mounting
WARNING!
ADICOS X22-Detectors must be mounted with closed enclosure.
−Do not open enclosure!
−Use ADICOS mounting plate!

COMMISSIONING
8ADICOS X22-Melder405-2010-003 EN21
4.2 Wiring
DANGER!
The electronics of the ADICOS X22-Detectors works with an electrical voltage
that can trigger an explosion in potentially explosive atmospheres.
−Do not open enclosure!
−De-energize the entire detector system and secure against
unintentionally reactivation for all wiring work!
−In the case of wiring within potentially explosive atmospheres,
only use Ex-protected connection boxes with respective approval!
−Do not bend connection cable! Observe minimum bending radius!
(–› Chap. 8, Technical data)
5 Commissioning
DANGER!
The electronics of the ADICOS X22-Detectors works with an electrical voltage
that can trigger an explosion in potentially explosive atmospheres.
−Prior to switching on, check that all detectors are properly
mounted and wired!
6 Operation
DANGER!
The electronics of the ADICOS X22-Detectors works with an electrical voltage
that can trigger an explosion in potentially explosive atmospheres.
−Never open the enclosure or loosen the cable gland
during operation!

9
ADICOS X22-Melder 405-2010-003 EN21
MAINTENANCE: DETECTOR REPLACEMENT
7 Maintenance: Detector replacement
DANGER!
The electronics of the ADICOS X22-Detectors works with an electrical voltage
that can trigger an explosion in potentially explosive atmospheres.
−Do not open enclosure!
−De-energize the entire detector system and secure against
unintentionally reactivation for all wiring work!
−Replace the closed detector including connection cable only!

TECHNICAL DATA
10 ADICOS X22-Melder405-2010-003 EN21
8 Technical Data
General
Model: GSME-X22
Item No.: 408-2001-251
Enclosure dimensions: mm 128 x 100 x 100 (l x w x h)
Weight:
(icl. 7 meter cable):
kg 2
Weight (excl. cable): kg 1,7 kg (incl. 7m cable)
Enclosure: Aluminum die casting, powder-coated
Electrical properties
Rated Voltages: V DC 24
Voltage range: V DC 21,6 … 40
Max. Power consumption:
(excl. heating):
VA 3,5
Max. Power consumption:
(incl. heating):
VA 14
M-Bus-Voltage (Signal): V/mA max. 40 V non-polarised / max. 30 mA
Thermal data
TEMP: -20 °C ≤Ta ≤+ 50 °C
IP: IP 64
Optional communication modules (input parameters)
BMZ-ModulSinteso FDnet: V DC 33 V; max. 10 mA
ADICOS
Coupling module 4-20 mA:
V DC 35 V; max. 20 mA
BMZ-Modul Bosch LSN: V DC 36 V; max. 20 mA
Pre-alarm relay module: V DC 40 V; max. 10 mA
V DC 24 V; max. 20 mA
Information regarding explosion protection
Explosion protection class: II 3D tc IIIC T 80 °C Dc
Max.
Surface temperature:
T 80 °C
Device group: II, category 3D

11
ADICOS X22-Melder 405-2010-003 EN21
APPENDIX: ADICOS MOUNTING PLATE
A
A
150
150
130
130
6,4
A-A
NOTE!
ADICOS X22-Detectors are rated Protection by enclosure “tc”.
−An Ex barrier is not mandatory!
9 Appendix: ADICOS mounting plate