1 Wiring Configuration
The diagram below shows a ‘typical’ application for the 4A sounder booster. Note that a 10KΩ EOL resistor
must be fitted to the end of the boosted sounder output circuit to maintain correct fault monitoring.
Mxp-026 Wiring Configuration.
Note. PSU ‘Failsafe’ Operation
The EN54 PSU shall be fitted with a ‘Fault’ relay that is energised during normal operation and de-energised for
any fault condition. The ‘FAULT I/P’ connections on the sounder booster card should be connected to the ‘COM’
and ‘N/O’ connections of the PSU as shown above. The table below indicates the state of the relay for all
conditions.
PSU ‘ON’ without Fault
(Energised)
PSU ‘ON’ with Fault
(De-energised)
sounder output
must be fitted to the
end of the boosted
output circuit for
correct fault
(-BXP)