CFM DVK100B-T Maintenance and service guide

DDVVKK110000BB--TTKKIITTIINNCCLLUUDDEESS::
•DDVVKK110000BBFan with Mounting Brackets
•CCTT--110000- 0-1 Hour Spring Wound Interval Timer
DDVVKKDDRRYYEERRBBOOOOSSTTEERRKKIITTWWIITTHHSSPPRRIINNGGWWOOUUNNDDIINNTTEERRVVAALLTTIIMMEERR
RREEAADDAANNDDSSAAVVEETTHHEESSEEIINNSSTTRRUUCCTTIIOONNSSFFOORRFFUUTTUURREERREEFFEERREENNCCEE
RREEAADDAANNDDSSAAVVEETTHHEESSEEIINNSSTTRRUUCCTTIIOONNSSFFOORRFFUUTTUURREERREEFFEERREENNCCEE
IINNSSTTAALLLLAATTIIOONN,,MMAAIINNTTEENNAANNCCEE
&&WWAARRRRAANNTTYYIINNSSTTRRUUCCTTIIOONNSS
FFAANNIINNSSTTAALLLLAATTIIOONN
SSTTEEPP11..FFAANNLLOOCCAATTIIOONN
In order to perform recommended maintenance, sufficient
access to the fan should be allowed at its location. Fan should
be mounted a minimum of 15' away from the dryer outlet, up to
a maximum of 90'. To calculate the length of the duct, measure
the length from the dryer outlet to the termination point; add 5'
of duct for each bend or elbow.
Note: An auxiliary lint trap (LT100) may be used to minimize lint
build up in the system.
SSTTEEPP22..MMOOUUNNTTFFAANN
Attach mounting brackets to the fan
housing as shown in Figure 1a or Figure
1b. Attach the fan to a support beam at
selected location. Vertical mounting is
recommended to reduce condensation
build-up in the fan, however, the fan may
be mounted in any position. The terminal
box (wiring box) should be positioned for
easy access. The airflow direction arrow
located on the junction box cover shows
the direction of the airflow, which cannot
be reversed.
SSTTEEPP33..CCOONNNNEECCTTDDUUCCTT
Connect the duct to the inlet and outlet
ends of the fan housing (by means of
mounting clamps or duct tape). The duct
connection should be properly sealed to
prevent air leakage and loss of fan per-
formance. Rigid duct is recommended
and should be installed as straight as
possible. If using flex duct, it should be
stretched as smooth as possible.
Figure 1a
Figure 1b
BBEEFFOORREEIINNSSTTAALLLLAATTIIOONN
IIMMPPOORRTTAANNTTNNOOTTIICCEE!!
DDVVKK110000BBfans are not explosion proof and should not be used
when a potentially explosive situation exists. Do not use where
temperatures will exceed 140oF/60oC.
1. Ensure that the electrical service to the fan is locked in the
“OFF” position. Do not re-establish power supply until fan
and activation device are completely installed.
2. DDVVKK110000BBfans are not suitable for outdoor use.
3. This unit has rotating parts! Safety precautions must be
exercised during installation, operation and maintenance.
Turn centrifugal impeller by hand to make sure it rotates
freely.
4.
CCAAUUTTIIOONN::
For general ventilation use only. Do not use to
exhaust hazardous or explosive materials and vapors.
5.
WWAARRNNIINNGG::
To reduce the risk of fire, electric shock, or
injury to persons – observe the following:
a) Use this unit only in the manner intended by the manu-
facturer. If you have questions, contact the factory.
b) A qualified person(s) must perform installation work and
electrical wiring in accordance with all applicable codes
and standards, including fire-rated construction.
c) The combustion airflow needed for safe operation of fuel
burning equipment may be affected by this unit’s opera-
tion. Follow the heating equipment manufacturer’s
guidelines and safety standards as published by the
National Fire Protection Association (NFPA), the
American Society of Heating, Refrigeration, and Air
Conditioning Engineers (ASHRAE), and local code
authorities.
d) When cutting or drilling into walls or ceilings, take care
not to damage electrical wires or other hidden utilities.
e) Ducted fans must always be vented to the outdoors when
used to exhaust moist/humid air.
6.
WWAARRNNIINNGG::
Check voltage at the fan to see that it corresponds
to the motor nameplate.
Note:
The DVK100B-T kit cannot be used in systems where the duct length is 25' or less. The DVK100B-T is suitable to overcome an equivalent of 90' of 4" rigid duct.

TTRROOUUBBLLEESSHHOOOOTTIINNGG
WWAARRNNIINNGG::
If fan fails to start, please follow the procedure listed below:
1. Check the incoming supply for proper voltage.
2. Ensure that the electrical service to the fan is locked in the
“OFF” position.
3. Consult wiring diagram to ensure proper connection.
4. Use a meter to test the continutity across the fan motor leads.
5. If the motor leads show continuity, rewire the fan and timer.
6. Turn on the electrical supply and restart.
7. Check to be certain that fan starts.
8. If fan fails to start:
a) Ensure that the electrical service to the fan is locked in
the “OFF” position.
b) Remove the timer from the circuit.
c) Connect the incoming power supply directly to the fan motor.
d) Turn on power to fan.
9. If fan fails to start, please contact technical support @
1-800-779-4021.
RREECCOOMMMMEENNDDEEDDMMAAIINNTTEENNAANNCCEE
CCAAUUTTIIOONN::
1. Before servicing or cleaning, ensure that the electrical
service to the fan is locked in the “OFF” position.
2. Fan bearings are sealed. No additional lubrication is necessary.
3. Periodic inspection, based upon usage, should be performed
to ensure that the fan impeller is not obstructed. The fan
should be inspected a minimum of every six (6) months.
4. Excessive fan noise or vibration may indicate an obstructed
impeller.
5. To inspect and clean impeller:
a) Ensure that the electrical service to the fan is locked in
the “OFF” position.
b) Remove the duct from the fan inlet and remove any
obstruction from the impeller.
c) Reconnect the duct to the fan.
d) Turn power supply on.
DVK-T DRYER I&M-0805
USA www.continentalfan.com Canada www.aeroflo.com
CCoonnttiinneennttaallFFaannMMaannuuffaaccttuurriinnggIInncc..
203 Eggert Rd.
Buffalo, NY 14215
Tel: 716-842-0670 Toll: 800-779-4021 Fax: 716-842-0611
AAeerrooffllooIInncc..
12-205 Matheson Blvd. East
Mississauga, ON L4Z 3E3
Tel: 905-890-6192 Toll: 800-779-4021 Fax: 905-890-6193
SSPPRRIINNGGWWOOUUNNDDIINNTTEERRVVAALLTTIIMMEERR
The CCTT--1100000-1 hour spring wound interval timer is
easily installed in a standard electrical box. This
spring wound timer will automatically turn the fan off
after a preset period. For automatic operation, turn
timer clockwise to desired drying time. Timer will
turn “OFF” at the end of preset timed period.
TTIIMMEERRIINNSSTTAALLLLAATTIIOONN
Ensure that the electrical service to the fan is locked in the
“OFF” position. Wiring must be done in accordance with all
applicable codes and standards. The unit must be properly
grounded. Ensure the supply voltage corresponds to the volt-
age listed on the name plate.
AATTSSWWIITTCCHHLLOOCCAATTIIOONN
1. Remove wall plate and disconnect switch from electrical
box.
2. Strip wire ends ½ inch long using strip gauge on back of
timer.
3. Follow the enclosed wiring diagram. Insert the stripped wire
ends under the pressure plate of terminal screws on the side
of timer (terminal screws provide in plastic bag). Screw
down tightly. Insert wired timer into a standard electrical box
with“TOP”(indicated on front of timer) in proper position and
fasten timer to junction box using the screws provided.
4. Slip metal dial plate over threaded extension with “OFF”
position facing up.
5. Fasten metal dial plate securely to timer with stamped nut
provided..
WWIIRRIINNGGPPRROOCCEEDDUURREESS
Refer to wiring diagram.
WWAARRRRAANNTTYY
This warranty supersedes all prior warranties.
DDVVKK110000BBfans are warranted against defects in material and workmanship for a period of five years from date of purchase. All
other products are warranted for a period of one year from date of purchase.
WWAARRRRAANNTTYYDDOOEESSNNOOTTAAPPPPLLYYTTOO::
• Shipping damage, whether concealed or visible. Claims must be filed with the carrier.
• Damage caused by improper installation, wiring, or incorrect electrical voltage.
• Materials that have been modified, altered or disassembled.
• Damage caused by corrosion, abrasion or severe temperature.
• Materials that have had the identification labels removed or altered.
• Materials that have been subjected to improper maintenance, abuse, misuse, abnormal usage or accident.
No other warranties, expressed, implied or written shall apply to this product. Vendor will not be responsible for any consequen-
tial or incidental damages, loss of property, revenues or profit, cost of removal, installation, or reinstallation, personal damage or
loss of life, or for any breach of warranty, regardless of how caused.
All warranty claims must be processed through point of purchase..

TITLE
BY DATE
REV. DATE BY
Better Airflow By Design
CFM
DIMENSIONS SUBJECT TO CHANGE WITHOUT NOTICE.
DRAWING NOT TO BE USED FOR CONSTRUCTION.
NOTE:
JUMPER MUST BE USED WHEN MOTOR IS OPERATED WITH FAN TIMER
GREEN
WHITE
BLACK
CAPACITOR
TERMINAL
BLOCK
BLACK
WHITE
GREEN
BROWN
BLACK
BLUE
YELLOW
FAN
MOTOR
117 VOLT SUPPLY
FROM FUSE PANEL
WIRING DIAGRAM
J. E. EVANS AUG. 08 2002 A-103,284
WHITE JUMPER
FAN TIMER
OFF
FAN WITH TIMER
03 01 JUNE 2006 JEE
02 25 MAY 2005 JEE
01 11 FEB. 2005 JEE
DVK-T DRYER I&M-0805
Table of contents
Popular Extender manuals by other brands

Avocent
Avocent LongView IP Quick installation guide

Savant
Savant HCX-4KHDR100 Quick reference guide

Patton electronics
Patton electronics Industrial Ethernet Extender with LCD Interface... Cli reference guide

Marmitek
Marmitek POWERMID XL user manual

D-Link
D-Link AMPLIFI DAP-1525 user manual

Interface Devices
Interface Devices OB-30 Installation, operation & maintenance manual