
97-2120001_7-8-19 Information subject to change 17
2110/2120 OPERATOR’S MANUAL – SECTION 4
Standby mode by pressing the Reset button on the
amplier displaying the Fault status. Refer to the
chart below to determine the fault condition being
Figure 4.7 – Fault Status Indicators for Multi-Amplier Systems
Indicator is lit Indicator is not lit Indicator may be lit
One or More Amps in System
Main Status
Indicators of
Other Amps
in System State of Operation
Action Needed to Clear
Fault Condition and Re-
turn to Run Mode
Main Status
Indicators
Fault Status
Reported on
LCD Display
Run
Ready
Standby
Stop
WARNING!
OUTPUT
DEVICE FAULT
Run
Ready
Standby
Stop
Output Device Fault sta-
tus: This indicates that an Out-
put Fault condition has occurred
in the amplier displaying the
Fault status, and the system has
been placed in Standby mode.
The Fault indicator will light
under two conditions: 1) High-
frequency oscillation is causing
high shoot-through current; or 2)
An output transistor has shorted,
causing the output fault condi-
tion.
This fault condition cannot be
cleared using the front-panel
Reset button. See the ”Trou-
bleshooting” section for more
information on diagnosing and
clearing this fault condition.
Run
Ready
Standby
Stop
WARNING!
OVERLOAD
Run
Ready
Standby
Stop
Overload status: This
indicates that the output of the
system could not follow the input
signal due to voltage or current
limits. Under normal operation
with the factory-default settings,
an Overload condition will not
place the system in Standby
mode. If the system has been
congured to be forced to Stand-
by on Overload, the system
will be placed in Standby mode
when the Fault indicator lights.
To remedy the Overload fault
during operation, turn down the
level of the input signal until
the Overload indicator turns
o. To clear an Overload fault
condition when the amplier is
forced to Standby, turn down
the level of the input signal,
then push the Reset button on
the amplier(s) displaying the
Overload status.
Run
Ready
Standby
Stop
WARNING!
OVERTEMP
Run
Ready
Standby
Stop
Overtemp status: Each am-
plier in the system monitors the
temperature inside the high-volt-
age transformers, low-voltage
transformer and in the output
stage heat sinks. The Overtemp
indicator will light and the system
will be placed in Standby mode
when the temperature sensors
detect a condition that would
damage the amplier system. If
the Overtemp pulse is extremely
short, as in the case of defective
wiring or switches, the Fault LED
may be lit too briey to observe.
To reset after an Overtemp
fault has occurred, make sure
the amplier fans in all ampli-
ers are running, and then
remove the input signal from
the system. Allow the fans to
run for about 5 minutes until the
system automatically returns to
Run mode. If the system has
been congured for Standby
mode on Overtemp, then the
system will not automatically re-
turn to Run mode. In that case,
push the Reset button on any
amplier displaying the Over-
temp status to return the system
to Run mode. Please see the
”Troubleshooting” section
for information on correcting
the cause of an Overtemp fault
condition.
indicated and the action required to clear the fault
condition and return the system to Run mode. See
Figure 4.7.