AgroLogic Temptron 616 User manual

TEMPTRON 616
OPERATION MANUAL
The
Temptr
on 616
is a stand alone climate controller that can control one heater, 7
groups of fans, minimum ventilation system,1 cooling system, 1 lighting system, 1
inlet motor, 1 curtain motor and 1 relay to be used for an alarm output.
The
Temptron 616
has a built in automatic temperature reduction table and
automatic weight increase table for ventilation
The first fan group is working as minimum ventilation.
It is optional to connect the
Temptron 616
to a PC for central management with the
help of the WinChick
software package.
INSTALLATION
____________________________________________
3
OPERATION
_______________________________________________
3
READING SET POINT
________________________________________
4
CHANGE OF SET POINT
______________________________________
4
Lock Code
_________________________________________________
5
SET POINTS
_______________________________________________
5
Heating system
______________________________________________
5
Fan Set points
_________________________________________________
6
Inlet/curtain Position
____________________________________________
7
Minimum ventilation Setup
_____________________________________
7
Cooling System
______________________________________________10
Alarm
____________________________________________________10
Light and feed index
__________________________________________11
24-
hour data
________________________________________________13
Temperature Reduction Table
____________________________________14
Weight increase table
__________________________________________15
Hidden functions.
____________________________________________17
Flap Calibration
_____________________________________________19
TROUBLE
-
SHOOTING
_______________________________________20
Diagram
___________________________________________________21

INSTALLATION
Open the front panel
Sensors
1
. Connect the Temperature Sensors to the
analog i
nput
inputs
1 and 2.
The sensors can be placed up to 100 meter from the main unit with an ordinary two
-
wire cable. The sensor has no polarity.
2.
Feed back flap 1 (Inlet);
Connect a dry contact from flap 1 to the digital 1 input.
3.
Feed back flap 1 (Curt
ain);
Connect a dry contact from flap 2 to the digital 2
input.
4.
Feed output;
Connect a dry contact from the feed contactor to the digital 7
input.
5.
Water counter;
Connect a dry contact from the water clock to the digital 8
input.
6.
Humidit
y sensor; Use a three wire cable. Connect the brown wire to the +V
input, Blue wire to GND and the yellow wire to analog input 7.
7
. Static pressure sensor; Use a three wire cable. Connect the brown wire to the
+V input, Blue wire to GND and the yellow wir
e to analog input 8.
Relays
Connect the relay outputs to the various systems. All outputs are dry contacts,
maximum 2 Amp/220V NO/NC.
Relay 1 = Alarm
(bottom left side of
relay box)
Relay 9 = Fan group 1
(bottom right
side of relay box)
Relay 2 = Heat
ing system
Relay 10 = Fan group 2
Relay 3 = Cooling system
Relay 11 = Fan group 3
Relay 4 = Lighting system
Relay 12 = Fan group 4
Relay 5 = Open inlet
Relay 13 = Fan group 5
Relay 6 = Close inlet
Relay 14 = Fan group 6
Relay 7 = Open cool curtain
Rel
ay 15 = Fan group 7
Relay 8 = Close cool curtain
Relay 16 = Fed line
Connect a 220V cable to the unit.
Close the panel with the two screws.
OPERATION
The
Temptron 616
will display the average temperature of the connected temperature
Sensors. It is poss
ible to display each sensor separately.
Turn on power.
1. Each time power is connected to the unit Agro Lo will appear on the
display.
The
Temptron 616
is calibrating its connected sensors.
2. After 20 Seconds the average temperature will appear on the
left display.

Temperature, humidity and pressure sensors
To view each sensor reading separately, press once on:
Number 1
-
5 = Displays the chosen temperature sensor reading.
Number 7 = Displays the humidity sensor reading.
Number 8 = Static pressure sens
or reading.
To display sensor 1, press on button 1 .
The temperature of Sensor 1 will be
displayed.
To display Sensor 2, press on button 2 .
The temperature of sensor 2 will be
displayed.
READING SET POINT
It is possible to read all the information on th
e
Temptron 616
display.
The right display indicates the function number. The left display shows the set point
for each function.
Each set point has a code number (see menu on the front panel). It is possible to go
into the code in two ways:
1. By pressing
on the DATA button the code number display on the right side of
the panel will increase. The preset information will appear on the data display on the
left side of the panel.
2. By pressing on the 0 button, two lines will appear on the code display and
FUNC on the data display.
Example:
If you would like to see code no.8;
a) Push on the 0 button.
b) Push on 0 and than on 8 button.
On the code display will appear 08 and on the data display the information.
If a code number is higher than 10, pu
sh on 0 and than enter the code number.
It is possible to continue from code 12 by pushing on the DATA button to the
next code.
CHANGE OF SET POINT
It is possible to change each set point.
1. Go into the desired code as explained above.
2. Push on PROG button. The code display will start to flash.
3. Use the keyboard to enter the desired data. The new data will appear on the data
display.
4. Check the display to see if the information is correct. If yes, push on the Enter
button. The code displa
y will stop flashing to indicate that the new information has
been stored into the unit s memory.

Lock Code
It is possible to enter a 4
-
digit code, which will lock the
Temptron 616
to prevent
unauthorized personnel form making changes in the unit.
It is
possible to see all the information in the unit, but not possible to make any
changes.
The unit is factory set in an unlocked manner, without a code. If a code is needed
see the
hidden function
section for an explanation of h
ow to program the code.
Once a code has been programmed, in order to unlock the unit to change values,
enter the programmed 4 digit code while the display is showing the average
temperature. There is no need to press PROG for this.
Once the code has bee
n entered, after a ten minute period from the last value
change, the unit will relock.
If no code is desired enter 0000 for the lock code.
SET POINTS
Functions
01. Time
(not shown on front panel menu)
This is a reading of the current time setting. It is
possible here to adjust the time
reading.
02. Required Temperature
The required temperature is the requested temperature in the house. All set points
(except the cool temperature set point) are set as a differential from the requested
room temperature.
The required temperature will be reduced daily according to the
temperature reduction table. See function 55
-64.
Heating system
03 Heat
Heat set point is the temperature differential
below
the Required temperature that the
heating system will turn on.
Exam
ple:
Heat
set point = 1.0
If the room temperature should drop 1.0° below the Required temperature (code 02)
setting then the heating system will start to run.

Fan Set points
04. Fan 1
Fan group 1 is used as the minimum ventilation fan group.
Fan
1 set point is the temperature differential
above
the required temperature at which
time fan 1 will run nonstop. Fan group 1 is working as minimum ventilation as long
as the measured temperature is less than the required temperature plus fan 1 set point.
F
an 1 group will work in the minimum ventilation mode as set up in functions 18
-26.
and according to the weight increase graph as setup in functions 65
-74.
Each time fan group 1 comes into operation, during minimum ventilation cycle, the
inlet will open to
the set opening (in percentage) as setup in function 11. The fan
group will start to run after 10 seconds. This waiting time is needed to prevent a build
up of high negative pressure in the house.
05.
Fan 2
Fan 2 set point is the temperature differential
above
the requested room
temperature that fan 2 will turn on. When fan group 2 comes into operation the
inlet/curtain will open to its preset opening as set in function 12.
06.
Fan 3
Fan 3 set point is the temperature differential
above
the requested room temperature
that fan group 3 will turn on. When fan group 3 comes into operation the inlet/curtain
will open to its preset opening as set in function 13.
07. Fan 4
Fan 4 set point is the temperature differential
above
the requested room tem
perature
that fan group 4 will turn on. When fan group 4 comes into operation the inlet/curtain
will open to its preset opening as set in function 14.
08. Fan 5
Fan 5 set point is the temperature differential
above
the requested room temperature
that fan group 4 will turn on. When fan group 5 comes into operation the inlet/curtain
will open to its preset opening as set in function 15.
09. Fan 6
Fan 6 set point is the temperature differential
above
the requested room temperature
that fan group 6 will turn on. When fan group 6 comes into operation the inlet/curtain
will open to its preset opening as set in function 16.
10. Fan 7
Fan 7 set point is the temperature differential
above
the requested room temperature
that fan group 7 will turn on. When fan group 7 comes into operation the inlet/curtain
will open to its preset opening as set in function 17.

Inlet/curtain Position
11. Flap Position 1 %
Enter here the in percentage that the inlet / curtain will open each time the
corresponding fan group comes int
o operation.
Fan group 1 = Position 1
12. Flap Position 2 %
Enter here the in percentage that the inlet / curtain will open each time the
corresponding fan group comes into operation.
Fan group 2 = Position 2
13. Flap Position 3 %
Enter here the in percentage that the inlet / curtain will open each time the
corresponding fan group comes into operation.
Fan group 3 = Position 3
14. Flap Position 4 %
Enter here the in percentage that the inlet / curtain will open each time the
corresponding fan group co
mes into operation.
Fan group 4 = Position 4
15. Flap Position 5 %
Enter here the in percentage that the inlet / curtain will open each time the
corresponding fan group comes into operation.
Fan group 5 = Position 5
16. Flap Position 6 %
Enter here the in percentage that the inlet / curtain will open each time the
corresponding fan group comes into operation.
Fan group 6 = Position 6
17. Flap Position 7 %
Enter here the in percentage that the inlet / curtain will open each time the
corresponding fan group comes into operation.
Fan group 7 = Position 7
Minimum ventilation Setup
18. Fan Minimum Duty
A value set in percent. This is the minimum amount of time the fan1 group will run
out of the Fan cycle time (see next function) during minimum ventilation.
19. Fan Cycle Time
This is a time period set in minutes and seconds. This is the time frame that the
minimum ventilation cycle will use.

20. Maximum Air Per Hour.
Enter here the total amount of cubic air per hour that minimum ventilation fan group 1
can supply. Take the total amount and divide it by 1000. Example: If fan group 1 can
supply 20,000 cubic meters of air per minute then enter the value 20.
21. Minimum Air Per Kg
Enter here the minimum amount of cubic air per kg wanted in the house.
22. Nu
mber Of Birds
Enter here the total number of birds in the house.
Example: 20,000 birds will appear as 20.00
23. Current Weight.
This is the current weight of one bird as calculated in the automatic weight increase
table (function 65
-
74).
This weight can
be changed if needed.
24. Fan Duty Cycle
This is the calculated duty cycle (percent) of the Fan Cycle Time according to the
minimum ventilation mode as explained later. If this number is larger than the
minimum duty cycle time then the fan 1 group will run this amount out of the fan
cycle time. If the minimum duty cycle time is larger then the calculated duty cycle
time the fans will run according to the minimum.
25. Cycle Timer
This is a display in seconds of the minimum ventilation timer.
The timer sho
ws the time left of the Fan Cycle Time (function 19).
26
. Tunnel On Group.
Enter here a fan group number that when reached will cause the unit to close the inlet
and open the tunnel curtain.
Example of minimum ventilation
02. Required temperature = 25.0
04. Fan 1 = 1.5
11. Flap Position 1 % = 10
05. Fan 2 = 2.5
12. Flap Position 2 % = 25
06. Fan 3 = 3.5
13. Flap Position 3 % = 45
07. Fan 4 = 4.5
14. Flap Position 4 % = 65
08. Fan 5 = 5.5
15. Flap Position 5 % = 75
09. Fan 6 = 6.5
16. Flap Positi
on 6 % = 85
10. Fan 7 = 7.5
17. Flap Position 7 % = 100
18. Fan Minimum Duty = 10
19. Fan Cycle Time = 10:00
20. Maximum Air Per Kg = 20
21. Minimum Air Per Kg = 1.0
22. Number Of Birds = 10000
23. Current Weight = 1.500
24. Fan Duty Cycle = 75
26.Tun
nel Group = 3

Using the values
in the previous table,
the ventilation will run as follows.
Fan group1 will be used to supply the minimum ventilation.
As long as the house temperature is less then 26.5 degrees (function 02 plus function
04) the unit will run in the minimum ventilation mode. The fans will run 75 percent
(function 24) out of 10:00 minutes (function 19). In other words the fans will run in a
cycle of 7:30 minutes on, 2:30 minutes off.
How the calculation is made is explained as follows.
Th
e unit multiplies the total number of birds (function 22) by the current weight
(function 23) to get the total weight in Kg for the house = 15,000kg. This number is
then multiplied by the minimum amount of cubic air per kg (function 21) = 15,000
cube per hour. This gives us the total amount of cubic air per hour needed to supply a
minimum amount of air to the birds. Next we take into account the maximum amount
of air that fan group 1 can supply while per hour = 20,000 cube per hour.
We can now calculate the amount of time (function 24) that the fan 1 group needs to
run out of the fan cycle time (function 19) = 75 percent or 7 and a half minutes on 2
and a half minutes off.
As the weight increases (function 23) the fan duty cycle will increase. Once the du
ty
cycle reaches 100 percent fan 1 will run nonstop
If more than one group of fans is to be used there will be a 5 second delay between
the start of each fan group. The same delay time will be used when the fan groups go
off.
During the minimum ventilatio
n cycle the fan group 1 will be running in a cycle
mode. Before the fan group comes into operation the inlet will open to the set position
as programmed in function 11. Once the inlet has opened the fan group will come into
operation (after the 5 second de
lay). This cycle mode will continue to run as long as
the temperature is less then the required house temperature (function 02) plus the set
point for fan group 1 (function 04) = 26.5 degrees. Once the temperature in the house
rises to 26.5 degrees, the fan group 1 will run nonstop (if the duty cycle is less then
100%). If the temperature in the house reaches the set point of fan group 2 (function
05), then the inlet will open to the preset opening as set in function 12. Once the inlet
has opened fan group
2 will come into operation.
This mode will continue as explained, fans running and the inlet opening according to
preset positions.
Once the set point of the fan group that was programmed as the Tunnel group
(function 26) is reached the unit will open the cooling curtain to the set position
according to the programmed flap position. The inlet will be closed
According to the example this will happen when the set point for fan group 3 is
reached.
The fans will continue to operate during this transition. The
unit will continue to bring
into operation the fan groups according to the temperature increase.
Note: It is necessary to program the set points of the fan groups in a order
starting from fan group 1 through to fan group 7 .
Be sure that the programmed inlet/curtain opening for each group increases in
size in order to prevent a high (negative) static pressure in the house.

Cooling System
27. Cool Temp.ABS
Enter here the temperature that when reached in the house the cooling system will
start to run in
its cycle mode as setup in functions 28 and 29.
This temperature is set as an absolute temperature.
28.Cool On Time mm:ss
This is the on time for the cooling system, set in minutes and seconds, which the
cooling system will run.
29. Cool Off Time mm:s
s
This is the off time for the cooling system, set in minutes and seconds, which the
cooling system will be off.
30.Cool Humidity Set Point
Enter here the maximum humidity in percentage. If the humidity in the house reaches
this level then the cooling s
ystem will turn off.
Note: If no humidity sensor is connected to the V911 unit then the value 100 must be
used.
31. Cool Timer Display
This is a display in seconds of the time cycles for the cooling system.
Alarm
32. Alarm Low set
Enter the number of de
grees
below
the required house temperature that if reached the
unit will activate the alarm relay.
Example: Required temperature 25.0
Alarm Low: 5.0
If the house temperature drops to 20.0 then the alarm relay will be activated.
33. Alarm High set
Enter th
e number of degrees above
the required house temperature that if reached the
unit will activate the alarm relay.
Example: Required temperature 25.0
Alarm High: 5.0
If the house temperature rises to 30.0 then the alarm relay will be activated.

34. Alarm
Type
Shown here is the current alarm in digital form
The unit has 8 alarms
1.
Cold
2. Hot
3.
Memory
- represents a problem with the unit s memory.
4.
Sensors
-
all temperature malfunctioning.
5.
Sensor
-
one sensor is malfunctioning.
6.
Inlet
-
the unit has detected a proble
m with the inlet motor feedback.
7.
Curtain
-
the unit has detected a problem with the curtain motor feedback.
8. Light dimmer
35. Alarm Disable
It is possible to disable alarms 5
-8.
To disable an alarm enter the corresponding number.
Example: In order to d
isable alarm number 5 (bad sensor) enter the value 5.
Note:
If an alarm is disabled then the alarm relay will not be activated when there
is a problem.
Light and feed index
36. Light/Feed Index
It is possible to program up to 8 on off programs for the light and feed systems
over a 24
-
hour period.
If your Temptron 616 is equipped with a built in light dimmer it is possible to
create dust dawn programs up to 8 times over a 24 hour period. See hidden
function number 85 for built in dimmer setup.
Enter here the number of the program (from 1-8) that is to be programmed.
Always start with the number 1 program.
Enter 1 and then continue to program the on and off times in functions37
-40.
Be sure to clear all unused indexes by entering zero (0) as the values in the used
indexes.
37. Light On Time
Enter here the light on time for the chosen index program. Use a real time mode.
38. Light Off Time
Enter here the light off time for the chosen index program. Use a real time mode.
Example:
Index (function 36) = 1
Light O
n Time (function 37) = 0600
Light Off Time (function 38) = 2000
In this example the lights will go on at 06:00 and off at 20:00.
If more than one lighting program is needed, continue to program the indexes.
Index (function 36) = 1
Light On Time (function 3
7) = 0600
Light Off Time (function 38) = 2000
Index (function 36) = 2
Light On Time (function 37) = 2200

Light Off Time (function 38) = 0100
In this example the lights will go on at 06:00 and off at 20:00 (index 1)
At 22:00 the lights will come back on an
d then go off at 01:00.
In order to erase all indexed programs, enter in the Index (function 36) the value 0
(zero). After the value 0 is entered the index number will return automatically to
1.
39. Feed On Time
It is possible to program up to 8 on off p
rograms for the feeding system over a 24
-
hour period..
Use the Index function as explained above to program up to 8 different on off
programs for the feeding system
Enter here the feed on time for the chosen index program. Use a real time mode.
38. Feed O
ff Time
Enter here the feed off time for the chosen index program. Use a real time mode.
Example:
Index (function 36) = 1
Feed On Time (function 39) = 0700
Feed Off Time (function 40) = 2100
In this example the feeding system will go on at 07:00 and off at
21:00.
If more than one feeding program is needed, continue to program the indexes.
Index (function 36) = 1
Feed On Time (function 39) = 0700
Feed Off Time (function 40) = 2100
Index (function 36) = 2
Feed On Time (function 39) = 0200
Feed Off Time (funct
ion 40) = 0500
In this example the feeding system will go on at 07:00 and off at 21:00 (index 1)
At 02:00 the feeding system will come back on and then go off at 05:00.
Note:
In order to erase all indexed programs, enter in the Light Index (function
36) the value 0 (zero). After the value 0 is entered the index number will return
automatically to 1.
41.Max Light
If your Temptron is equipped with a built in light dimmer then you can program
the maximum light intensity and the time it takes to reach this in
tensity.
Enter in this function the maximum light intensity, in percentage from 0 to 100
that is desired for the house.
42.Light Delay
Enter here in minutes and seconds the amount of time it take the lights to go from
0 to the set maximum intensity and ba
ck down to 0 intensity.
Example:
Index (function 36) = 1
Light On Time (function 37) = 06.00

Light Off Time (function 38) = 20.00
Max Light (function 41) = 75
Light Delay (function 42) =00.50
In this example the lights will go on at 06:00. Over the next 50 seconds the lights
will increase in intensity. At the end of the 50 second time frame the lights will
have reached an intensity of 75 %.
At 20.00, over a 50 second period the lights will decrease in intensity. At the end
of the 50 second time frame the
lights will be off.
24-hour data
43. Min Temperature
A display of the minimum temperature recorded over the last 24 hours. This will
be updated according to the reset time (function 71).
44. Minimum Temperature Time
A display of the time that the minimu
m temperature occurred in the house.
45. Maximum Temperature
A display of the maximum temperature recorded over the last 24 hours. This will
be updated according to the reset time (function 71).
46. Maximum Temperature Time
A display of the time that
the maximum temperature occurred in the house.
47. Minimum Humidity
A display of the minimum humidity recorded over the last 24 hours. This will be
updated according to the reset time (function 71).
48. Minimum Humidity Time
A display of the time that t
he minimum humidity occurred in the house.
49. Maximum Humidity
A display of the maximum humidity recorded over the last 24 hours. This will be
updated according to the reset time (function 71).
50. Maximum Humidity Time
A display of the time that the
maximum humidity occurred in the house.
51.Water Clock
If a water measuring clock has been connected to the Temptron 616 then in this
function will be displayed the amount of water consumed over a 24 hour period.
This 24 hour time period is from Reset ti
me to Reset time (function 76).
52.Feed Clock
If a dry contact has been connected to the Temptron 616 from the feed auger
contactor. then in this function the amount of feed consumed over a 24 hour

period will be displayed. The 24 hour time period is from Reset time to Reset
time.
53.Feed Mult
Feed multiply is the total amount for feed in kilograms that is duped from the feed
auger over a one minute time period.
If a dry contact has been connected to the Temptron 616 from the feed auger
contactor and a Feed multiply is entered then the Temptron 616 will convert the
feed augers motor running time into kilogram and display this amount in function
52.
Example:
Over a one minute time period 25 kilogram comes out of the feed auger.
The Temptron 616 will calcu
late feed consumption using this value.
If the feed auger runs for 10 minutes then the Temptron will assume that 250
kilogram of feed was consumed. Since different types of feed will cause a change
in the amount of feed, this is only an approximant calcula
tion of consumed feed..
54. Average 24
-
Hour Temperature
A display of the average temperature over the last 24 hours. This is updated at
reset time.
Temperature Reduction Table
It is possible to enter a automatic temperature reduction table for the req
uired
house temperature.
55.Day 1 Temp
Day 1 temperature is the starting temperature for the first day grow day. It is the
temperature that will appear as required temperature (function 02) when 1 is
entered here. The room temp will be reduced according
to the following table.
Important:
When Day is equal to 1 it is not possible to change Required
Temperature (function 02).
56-
64 Temperature Graph 1
It is possible to set a temperature graph to reduce automatically the room
temperature each day during the raising period. It is possible to set up to 9
Groups. Length of each Group can be up to 9 days. Each Group can be reduced up
to 9.9
C.
Example:
Day 1 temperature 31
C (function 55).
Growth day 1 (function 7
5)
Room temperature will be 31
C.
Group 1 -
7 days reducing of 2.1
C.

Each day the room temperature will be reduced by 0.3
C. At day 7
-
the room
temperature will be 29
C.
Group 2-
3 days reducing of 1.5 C. Each day the room temperature will be reduced by
0.5
C. At day 10 the room temperature will be 27.5 C. and so on.
Example:
To Enter temperature reduction of 2
C in 7 days, press on 7 and than on 2 than on 0
and than on enter. On the display will appear : 7 2.0 G1
Press on data key, next group will appear.
To enter temperature reduction of 1.5
C in 3 days, press on 3 than on 1 than on 5 then
on enter. On the display will appear: 3 1.5 G2.
It is
important
to enter data in all 9 groups. If a group is not in use than put one day
and 0
C. as a reduc
tion temperature
65. Day 1 Weight
It is possible to enter an automatic weight increase table to be used by the
minimum ventilation system.
Enter here the weight of one bird at one day old.
Each time day one is entered at Grow day (function 75) the current weight
(function
23) will be updated to this weight
Important:
When Day is equal to 1 it is not possible to change current weight
(function 23).
Weight increase table
66-
74. Weight Graph
The weight increase graph (table) works as follows:
The table ha
s 9 groups. Each group contains two settings.
The first setting represents the number of days that the weight increase will take place
over. The maximum number of days is 9.
The second setting is the actual weight increase over the set number of days. The
maximum weight increase is 990 grams
25
26
27
28
29
30
31
32
G1 G2
T
e
m
p

Example 1
Enter the first table of the weight increase graph.
To enter a weight increase of 80 grams over 7 days, press on number 7, number 0 and
number 8. Next press on enter.
On the display will appear: 7 0
8 G1
Example
2
Press on the data button to go to the next table in the weight increase graph.
To enter a
weight increase of
2
00 grams over the next
9
days,
press on number 9,
number 2 and number 0. Next press on enter.
On the display will appear:
9 20
G2.
It is
important
to enter data in all 9 groups. If a group is not in use, than put one day
and 0 as weight increase.
75. Grow Day
This is the current grow day of the flock. At the beginning of the flock enter here
The room temperature (fun
ction 02) will automatically receive the value as
entered in Grow day1 temp
.
The Current weight function will automatically receive the value as entered in
Day 1 Weight.
76. Reset Time
The
Temptron 616
collects all its information on a 24 hours basis. I
t is possible to set
the reset time. The grow day also changes after this time is passed. All information,
temperature, humidity, water count and feed consumption will reset at this time.

77. Flap 1 Position%
A display of the current position of the inl
et in percent.
78. Flap 2 Position%
A display of the current position of the curtain in percent.
Hidden functions.
Hidden functions are functions that are normally set up once and are not used on a
daily basis.
There are 8 hidden functions.
In order to re
ach the hidden function (79
-
85) you must first unlock them.
To unlock the hidden functions follow these steps.
A
. Enter the time function (01).
B.
Push on PROG
C.
Enter 3331
and press enter.
The hidden functions are now unlocked
To relock the hidden fu
nctions manually enter function 01 and enter 3330 and
enter
.
If no information is enter for a period of 10 minutes the unit will automatically lock
the hidden functions.
Hidden functions:
79.
Flap 1 current state.
80.Flap 2 current state.
The flaps have 1
4 different states.
State 0= The flap is not moving.
State 1= The flap is opening.
State 2= The flap is closing.
State 3= The flap is at zero percent and there is no feedback.
State 4= The flap is a 100 percent and there is no feedback.
State 5
-
9= The flap
is in a state other than opening or closing.
State 10= The is in a error state. This state indicates that at some point during
operation the flap lost its calibration. In this state the Temptron will activate the alarm
relay and the alarm type will be ei
ther 6 (inlet) or 7 (curtain).
State 11=. No flap was detected during the calibration process (function 4441/4442).
State 12= the unit has closed the flap open relay but no flap is connected. The
relay will remain closed for 10 seconds. N
o alarm will be activated.
State 13= the unit has closed the flap open relay but no flap is connected. The
relay will remain closed for 10 seconds. No alarm will be activated.
81. Lock code.
Enter here the 4
-
digit code for locking/unloc
king the unit. If the value 0000 is entered
then the lock code is disabled.
82. NAVR
Number of sensors for average. Enter here up to 4 sensors that are to be used for
calculating the average temperature.

83.Net Name
It is possible to connect the
Temptron 616
to a PC computer with the help of the
"ChickPro" software package. It is possible to manage up 99 Temptron 607 units.
Each unit needs a net name.
84.Digital Input reading:
This is a display of the current digital input in use. This readout is a b
inary
number.
Digital input 1=1 (inlet input)
2=2 (curtain input)
7=64 (water counter input)
8=128 (feed input)
85.Op Mode:
Here we program the unit for the built in light dimmer.
If the unit
is not equipped with a built in dimmer, enter here 0.
If the unit is equipped with a built in dimmer, enter here 1.
Add
2
to Op Mode in order to keep fan 1 on after fan 2 and up are working.
For example: Op Mode = 3 (2 + 1), the internal dimmer is being
used and fan 1
will remain running together with fan 2.
This feature was added in program version 1602 and up.
86.
Minimum ventilation off
Enter here a fan group number. When this fan group comes into operation all fan
groups below this group will turn
off.
Example: Minimum ventilation off = 3
When fan group 3 comes into operation fan groups 1 and 2 will shut off.
87.
Version Number
This is the version number of the unit.

Flap Calibration
Flap 1 Calibration (inlet)
It will be necessary to calibrate th
e inlets / curtains before the start of each flock.
A.
Go to the time function (code 01)
B.
Push on PROG
C. Enter 4441 and press "Enter".
This will start the calibration process. The flap will first close to 0 percent and
then open to 100 perc
ent. The flap will then go to its required position.
Flap 2 Calibration (curtain)
It will be necessary to calibrate the inlets / curtains before the start of each flock.
A.
Go to the time function (code 01)
B.
Push on PROG
C. Enter 4442 and pr
ess "Enter".
This will start the calibration process. The flap will first close to 0 percent and
then open to 100 percent. The flap will then go to its required position.
If no flap feedback is detected during the calibration process, the unit will assume
that
no flap is attached. Each time the unit gives a command for a flap to open or close it
will close the corresponding relay and leave it closed for 10 seconds. This will be an
indication that the flap must be moved manually.
There will be no alarm in t
his case.

TROUBLE
-
SHOOTING
1. If a temperature sensor or its cable is disconnected, the sensor reading will
show
Open.
2. If a temperature sensor or its cable is shorted, the sensor reading will show
Short.
3. If all sensors are disconnected,
the unit will show open as average and activate
the alarm.
If one sensor is disconnected, the system will automatically work on the remaining
sensor.
Table of contents
Popular Temperature Controllers manuals by other brands

Siemens
Siemens SITRANS T Series Compact operating instructions

aci
aci BACnet Series Installation & operation instructions

Auber
Auber WS-1500EBPM operation instruction

Emerson
Emerson TS1-G Operating instruction

VOLTCRAFT
VOLTCRAFT ETC 902 operating instructions

Uponor
Uponor UponorControl System Installation and operation manual