7 Technical data
DOL 139 0-10V
Specification Parameter Unit
Output Voltage range 0 - 10 VDC
Limited output power per port 20 mA
Output impedance <1 Ω
Recommended load impedance >100 kΩ
Max. Cable length @ 0.75 mm2100 m
Max. cable length @ 1.50 mm2200 m
Load impedance 0.5 – 10000 kΩ
Relative humidity Measurement range 0-100 %RH
Output resolution 0.1 V/%RH
Accuracy +10 oC - +40 oC (40-80%
RH)
+/-3 %RH
Accuracy 10%RH – 95%RH +/-3 + 0.02 x mv %RH
Time constant: T63 4 min. at 0.5 m/s air speed
Temperature Measurement range -40 - +60 oC
Output resolution 0.1 V/oC
Accuracy +10 oC - +40 oC +/-0.75 oC
Accuracy 0 oC - +60 oC +/-1.5 oC
Time constant T63 7 min. at 0.5 m/s air speed
CO2Measurement range 0-10000 ppm
Output resolution 0.001 V/ppm
Accuracy 400 - 10000 50 ppm + 5% of measured
value
ppm
Time constant T63 2 min. at 0.5 m/s air speed s
Supply voltage 13.5 - 30 VDC
Supply current No load 9 mA
Max. load 105 mA
Temperature, operation 0 - +60 oC
Temperature, storage -40 - +60 oC
IP classification IP67 (DIN 40050-9)
NEMA 1, 3, 4, 6
Cable length 2 m
Cable conductor size 5 x 0.34 (5 x AWG22) mm2
Dimensions (diameter/
width)
33.3 mm
Dimensions (length) 128.3 mm
Weight (sensor and ca-
ble)
243 g
Approvals CE