ahlsell ENERGY FLEX SKP 20 User manual

SKP 20
LCD TERMINALS
User manual for ENERGY FLEX
ENGLISH

SKP 20

3
SKP 20
INDEX
USER INTERFACE
1.1 Keys 4
1.1.1 Description of keys 4
1.1.2 Description led utilities 4
1.1.3 ICONS: States and Operating Modes 5
1.1.4 Icons and Double Display 5
1.1.5 Double Display 5
1.2 Hot keys 5
1.2.1 Local On/O 5
1.2.2. Controler ”On” ”OFF” 5
1.2.3 Controler “OFF”“On” 5
1.2.4 Manual alarm acknowledgment and reset 6
1.3 First power on 6
1.3.1 Access to folders - menu structure 6
1.3.2 Main display Menu 6
1.3.3 “Operating Mode”Menu 7
1.3.4 Setting the clock (CL) 7
1.3.5 Alarm Display (AL) 8
1.3.6 Example of how to set the setpoint (SP) 8
1.3.7 Reset compressor/pump time 9
1.3.8 Parameters (folder PAr) 9
1.3.9 Setting a password (Par/PASS folder) 10
1.3.10 Alarm events (Par/EU folder) 10
DIAGNOSTICS
2.1 Alarms 12
2.1.1 Automatic reset 12
2.1.2 Manual reset 12
2.1.3 Alarm mute 12
2.2 Digital alarms 12
2.3 Analogue alarms 13
2.4 Alarms table 13
2.4.1 Alarm table key 13
2.4.2 Alarms table 14

4
SKP 20
1.
User interface
1.1 Keys
1.2 Functions description
Preliminary precautions
• Thecontrolpanelallowsyoutomakeallthenecessaryadjustmentstothechilleroperationandtoviewthevaluesofthe
mainparametersandalarms.Thecontrolpanelislocatedonthefrontpaneloftheelectricalboard.
1.1 Keys
Theinterface,comprisingthefrontcoverofthecontroller,allowsyoutoperformalloperations
needed to use the device.
Theterminalsarethesameandareinterchangeable–seetable.
• SKW22(L)Thereare4keysonthefrontcoverofthecontroller.
• SKWP22(L)Thereare5+3keysonthefrontcoverofthecontroller.
Each key has (see the two tables below)
• Adirectaction(shownonthekeyitself).
• An“associated”function(forSKW22(L):markedwithanicononthefrontpanelofthetermi-
nalbesidethekey).Inthemanual,thisisshowninsquarebrackets(e.g.[UP])
• A combined action using 2 keys. In the manual, this is shown in square brackets
(e.g.[UP+DOWN])
1.1.1 Description of keys
1.1.2 Description led utilities
Icons associated with utilities are all congurable. From the factory device is set to the table:
Key Press once
(press and release)
Long press
(press and hold for about 3 seconds)
1
Increase a value.
Go to next label.
See also F1
[Activatemanualdefrost]
See the Functions menu (folder FnC).
2
Decrease a value.
Go to previous label.
See also F3
[Machineactive→OFF]
[OFF→machineactive]
See Local On/OFF section.
See also Functions menu.
(FnC folder)
3
Conrm value / exit and save new settings.
Move to next level
(openfolder,subfolder,parameter,value).
Open State Menu.
Open Edit Mode
(Main display)
See Main Display section.
4
Exit menu page / go back to previous menu.
Move cursor to left in Edit Mode.
(press and hold)
Exit Edit Mode without saving.
See also F2
(Mode Change)
See section on Changing operating mode.
5 Open Programming menu /
Tasto Pressione singola
(premi e rilascia)
Pressione prolungata
[premi per 3 secondi circa]
Note
[F1+F3]
/
[Riarmomanualedegliallarmi]
F1
/
[Attivasbrinamentomanuale] VediTastoUP
pressione prolungata
F2
/
[Cambiomodo] VediTastoesc
pressione prolungata
F3
/
[MacchinaattivaOFF]
[OFFmacchinaattiva]
VediTastoDOWN
pressione prolungata
<IMGINFO>
1 Compressor 1
2 Compressor 2
3
Sanitary water
4 Boiler
5
Exchanger electric heater
6 Fan-coil
7Waterpump
1234567

5
SKP 20
ICONS
States and operating
modes
Icons
Description
Permanently on Flashing
Alarm Active alarm
Alarm acknowledged
Economy
Congurable
----
Ui /dS folder
Parameters
UI07 /dS00
Congurable
----
Ui /dS folder
Parameters
UI07 /dS00
Display B shows the value/
resource set
for the“main display”.
If there is an alarm:
Display A shows the alarm
code Exx.
(when more than one alarm
occurs at
thesametime,theonewith
the lowest
number will be shown rst).
Display B shows“- - -”if the
alarm is a
probe alarm referring to the
value set
for the main display.
Not used
Clock(RTC) Shows current time
(24hr format).
Set time
Stand by Local standby mode
(from keyboard) Remote standby
Heating Heating mode
Antifreeze with heat
pump active
Remote heating mode
Cooling Cooling mode Remote
cooling mode
Not used / /
AUTO
Not used / /
ICONS
States and operating
modes
ICON
symbols
on display
ICONS Default
Default icon
on front
panel
ICON 1
(rst from top
on the left)
Menu navigation
(ABC)
ICON 2 Manual defrost
Icons are associated with menu navigation and manual defrost.
Thefactorysettingsofthecontrollerarelistedinthetable:
1.1.5 Double LCD
Whichwewillrefertoasfollows:
Thedouble display has 26 icons:
• Statesandoperatingmodes-9icons
oBrowsemenu/manualdefrost–2icons
• Valuesandunitsofmeasure-4icons
• Utilities-7icons
• Fans-4icons
Read-outs can have up to
• Display A: 4 digits or
• Display B:2andahalfdigitsand+/-sign
Note:
• Icons are all grey in colour.
• Some icons are NOT used – are shown on a grey background.
Display Display A Display B
4-gure
read-out
Read-out
with 2
and a half
digits and
+/-sign
1.2 Hot keys
1.2.1 Local On/OFF
1.2.2 Controller “On”“OFF”
Pressthe[DOWN]keyforabout3secondsfromthe
main display.
ThewordOFFwillappearonthedisplay.
All other icons will remain o.
1.2.3 Controller “OFF”“On”
ThewordOFFappearsonthedisplay.
Pressandholdthe[DOWN]keyforabout3seconds.
Energy Flex will return to the normal display.
1.1.3 ICONS: States and Operating Modes
1.1.4 Icons and Double Display
he13iconsonthefrontpanelindicateassociated/combinedfunctions(6icons)+defaultutilities
(7 icons).

6
SKP 20
1.3.1 Access to folders - menu structure
Folders are organized into menus.
Access to said folders is dened by the keys on the front cover (see relative paragraphs).
Intheparagraphsthatfollow(orchaptersindicated),wewillexplainhowtoentereachindividualmenu.
Thereare4menus:
•MainDisplayMenusee the“Main Display Menu”chapter.
•OperatingModeMenusee the“Operating Mode Menu”chapter.
•StatesMenusee the“States Menu”chapter.
•ProgrammingMenusee the“Programming Menu”chapter.
Thereare4folders/sub-menusintheProgrammingMenu:
•ParametersMenu(folderPar)see Energy FLEX manual Parameters Chapter.
•FunctionsMenu(folderFnc)see Functions chapter.
•PasswordPASS
•EUalarmcodes
All menus and labels are listed in the table below:
1.3.2 Main display Menu
“MainDisplay”meanswhatthecontrolleronthedefaultdisplayscreen,i.e.whennokeyshavebeen
pressed.
Modifying the main display
InEnergyFLEX,themaindisplaycanbecustomizedtosuitpersonalrequirements.Thevariouscon-
tentscanbeselectedfromthe“disp”menuwhichisopenedbypressingandholdingthe[set]keyfor
morethan3seconds.Themaindisplay canbeselectedfrom:
1.3 First power on
MENU
Main Display
(Display B)
Note:
Display A always
shows
the clock.
Ai AIL1 AIL1 AIL1 AIL1 AIL1 Air1 Air2
di diL1 diL2 diL3 diL4 diL5 diL6
...
...
Sr
Hr
Operating mode
HEAt
COOL
StdBY
States
Ai
di
...
CL HOu dAt YEA
...Hr CP01 CP02 CP03 CP04 PU01 PU02 PU03
PROGRAMMING
MENU label
Parameters
PAr
CL CL00...
CF CF01...
... ...
AL ALOO...
Functions
FnC
dEF
tA
St OFF/ON
CC UL dL Fr
EUr
Password PASS
EU EU
WhenEnergySKW22(L)ispoweredonfortherst
time,alamptestiscarriedouttocheckitsstateand
operation.
----------
TheLampTestlastsforjustafewseconds.During
thisshorttime,alliconsanddigitsashatthesame
time.
Afterthelamptest,thefollowingare
displayed (depending on the default
settings):
Display A
•Thetime(always**)
Display B
•Realsetpoint
•Parametersetpoint
•Thevalueoftheanalogueinputselected
(AIL1…AIL5,Air1,Air2).
----------
Intheexample,themaindisplayis:
DisplayA:currenttime(RTC**)
DisplayB:parametersetpoint(+12°C)
Intheexample,thecurrenttimeisthemaindisplay
(RTC).
Note that in this case Display is o (display A shows
the time).
**N.B.Thetimewillbeshownonmodels/C,i.e.
thosewiththeRealTimeClock(RTC)installed.
1.2.4 Manual alarm acknowledgment and reset
Alarmsignalsaredisplayedasashing.Belowisanexplanationofhowtoacknowledgeanalarm.
ThevariouserrormessageswillbeshowninfolderAL(seeStatesMenu).
ALARM/ERRORACKNOWLEDGMENT
An error can be acknowledged by pressing any
key once.
Afterpressinganykey,thealarmiconwillstart
to blink.
MANUALRESET
Tomanuallyresetanalarm,pressthe“up”and
“down”keystogether[UP+DOWN]
- - - - - - - - -
N.B.: resetting an active alarm will save the alarm
in the alarm log.
Thedevicewillreturntothemaindisplay.
1
Anerrormessagewillbeshown,
alternating with the error alert (2)
and the main display (1).
TheALARMiconwillbepermanentlyon.
2

7
SKP 20
•AnalogueinputsAiL1,AiL2,AiL3,AiL4,AiL5,(whenconguredasdigitalinputs,thedisplaywillbe
dened on the basis of the state and logical parameter - digital input associations).
•Set-point
o SP= set from parameter.
o Sr= real with any decalibration.
A step by step account of how to proceed is provided below.
1.3.3 “Operating Mode” Menu
Changing the operating mode
Therearethreedierentoperatingmodes:
• Stand-by(StbY)mode
• HEATmode
• Coolingonlymode(COOL)
1.3.4 Setting the clock (CL)
EnergyFLEXhasaclock(RTC)torunthealarmlog,justlikeaprogrammabletimerthermostat.
Wewillnowshowyouhowtosetthetime:
you will also use the same procedure to set the date and year.
Toopenthe[disp]menutomodifythemain
displaysetup,pressandholdthesetkeyforat
least 3 seconds.
[set]
Opens the blinking menu for the previous display
(SEtP,i.e.SetPointfromparameter,inthiscase).
Tomodifythedisplay,usethe“up”and“down”
keys to browse the menu.
On selection of your preferred display (AiL1 in
thiscase),pressthesetkeytoconrm.
You will be automatically returned to the
precongured main display.
InthiscaseAiL1,withavalueof7.5°C
Forexample,let’ssayyouwanttochange
from StbY to COOL mode.
Tochangeoperatingmode,pressandholdthe
[esc]keyforatleast2seconds.
A blinking menu will open containing the values
StbY(standby),HEAt(heat)andCOOL(cool)
thatyoucanscrollusingtheDOWNkey.
---
Selectyourrequiredoperatingmode(COOLin
this case) and press the set key.
You will be automatically returned to the main
display and you will see that the Stby icon that
was previously on has gone o and the COOL
icon has come on.
Tochangethetimeonyour
machine,startingfromthemain
display,pressthesetkey.
Press the key once to view the
various folders.
Usethe“UP”and“DOWN”keys
to nd the CL folder.
Press the set key to open the CL menu.
1
Onceyouareinthismenu,you
will see the HOUr label on
Display B.
Usethe“UP”and“DOWN”keys
(1-2-3) to select the
- - -
Pressthe[set]key**toopenthe
menu you want to modify.
TheHOurlabelwillreappearon
Display B.
Display A will blink.
Press and hold for
2
Entra in menu modica

8
SKP 20
1.3.5 Alarm Display (AL)
1.3.6 Example of how to set the setpoint (SP)
Forexample,wewillmodifythesetpointinCOOLmodefrom12.0degreescentigradeto12.5de-
grees centigrade.
Setpoint edit function enable from main screen
Parameter Ui25 allows you to enable Set Point modication on the main display with the UP and
DOWNkeys.Forexample,wewillmodifythesetpointinCOOLmodefrom12.0degreescentigrade
to 12.5 degrees centigrade.
Parameter UI25=1 (folder Par/Ui/UI25) must be set.
See Parameters section (folder PAr)
Press the set key from the main display.
Label Ai appears on the display.
UsetheUPandDOWNkeysto
browse the other labels until you nd
the AL label.
Press the set key to view the label of
the rst active alarm (if it exists).
Inthiscase,therstalarmisEr01.
Scroll using the“up”and“down”keys
to nd other active alarms.
-------------------------------------
N.B.: the menu is not cyclical.
Forexample,iftheactivealarmsare
ER01,Er02andEr03,thedisplaywillshow:
Er01 ->Er02->Er03 <-Er02<-Er01
NOTE:->UP,<-DOWN
Press the esc key to go back to the
main display.
Tochangethesetpointonyour
machine,startingfromthemain
display,pressthesetkey.
Let’ssaywewanttochangetheCOOLmode
setpoint.
ThedevicemustbeinCOOLmode
(or in StdBy mode from COOL).
TochangethesetpointoftheHEATmode,
proceed in the same way by rst changing the
device”smodefromCOOLtoHEAT
See Operating Mode Menu chapter.
Tochangethesetpointonyourmachine,press
theUPorDOWNkeyinthemaindisplay
Label Ai appears on the display.
UsetheUPandDOWNkeysto
scroll the other labels until you
nd the SP label
Press the set key to open the SP
menu.
TherstdisplaywillbeCOOL
mode,andthenscrollingwiththe
UPandDOWNkeys,theHEAT
mode (the various displays are
shown at the side).
Let’ssaywewanttochangethe
COOL mode setpoint.
Press the set key beside the COOL
label.
Thedevicewillshowthecurrent
setpointofthemachine,whichis
12.0 degrees centigrade in this case).
- - -
Toincreaseordecreasethis,press
the“up”and“down”keys. For
example,ifyouwanttochange
thesetpointto12.5degrees,press
the“up arrow”key until you reach
therequiredvalue.
- - -
Torepeattheprocedurein
reverse until you get back to the
maindisplay,presstheesckeyor
wait for the 15-second timeout to elapse.
Change time/date/day menu
Note: Display A blinks.
Usethe“UP”and“DOWN”keys
toselectthetime,dateoryear.
Once you have decided what you
want to set (for example the
time),pressthesetkeyagainto
open the modication menu for
the variable selected.
- - -
Tosetthetime(thesame
procedure applies to the date
andyear),usethe“UP”and
“DOWN”keystoenterthe
requiredvalueandpressthe
- - -
Toexitthesettimemenu,press
the esc key until you are returned
to the main display.
Change time

9
SKP 20
Thedevicewillshowthecurrentsetpointofthe
machine,whichis12.0degreescentigradeinthis
case).
Toincreaseordecreasethis,pressthe“up”and
“down”keys again.
Forexample,ifyouwanttochangethesetpoint
to12.5degrees,pressthe“uparrow”keyuntil
youreachtherequiredvalue.
Onreachingtherequiredvalue,pressthesetkey.
Thedevicewillsavethevalue12.5.
Press the esc and set keys together to open the
parametersmenu.ThiswillopenthePArmenu.
ThePArparametersmenucontainsallcontroller
parameters. Press the set key to view folders.
TherstfolderthecontrollershowsistheCF
conguration folder.
Simply press the set key again to modify individual CF
parameters.
ThecontrollerwillshowparameterCL00(factory
default settings).
Press the“up”key to scroll through the various
parameters or move to the next parameter (CL01 in
this case) or the“down”key to go back to the previous
parameter (CL97 in this case)
CL00->CL01->CL02->…->CL97->CL00
CL97<-CL00<-CL01->…<-CL96<-CL97
NOTE:->UP,<-DOWN
Press the set key to change the value of the parameter
(CL01 in this case).
Press the“up”and“down”keys to change the value of
the parameter (CL01 in this case).
Onselectingavalue,pressthesetkey.**
Toexitthisdisplayandreturntothepreviouslevel,
press the esc key.
**N.B.pressingthesetkeyconrmsthemodied
value; pressing the esc key returns you to the previous
level without saving the new value entered.
Example display and reset hours
for Pump 1.
Press the set key from the main
display.
Label Ai appears on the display.
UsetheUPandDOWNkeysto
scroll the other labels until you
nd the Hr label.
Press the set key to view the rst
label - which in this case is the
running time for compressor 1
(CP1)
ScrollwiththeUPandDOWNkeys
to view (if the relative resources
are present) the running time for
compressor 1 (CP1) the the pump
running time (PU1)
Therunningtimeis5hours.
ToclearpumpPU1runningtime,
pressandholdthe[set]key.
-------------------------------------
Press the esc key to go back to the
main display.
1.3.7 Reset compressor/pump time
1.3.8 Parameters (folder PAr)
Modifying a parameter
Instructionsareprovidedbelowonhowtochangeamachineparameter.Bywayofexample,let’s
lookattheCFcongurationparametersfolder,parameterCF00(folderPAr/CF/CF00).

10
SKP 20
ToviewfolderPASinthemaindisplay,presstheEsc
andSetkeysatthesametime.[esc+set]
Pressing the two keys will open the menu containing
the list of folders. Use the“up”and“down”keys to
scroll the list until you nd the PAS folder.
Press the set key to open the PAS folder.
Enterthepassword(installerormanufacturer),
(password=1intheexample)fromhere,pressthe
set key and exit.
Now open and view parameters to change a value
(see parameters section in the Energy FLEX manual)
Alarm code Er
Therstlabelwillbeshown
(alarmcode,inthiscaseEr01)
UsetheUPandDOWNkeystoscroll:
Alarm start time Hi
(20:08 in this example)
Alarm start date
(20 May in this example)
Alarm stop time HO
(alarm still active in this case)
Alarm stop date dO
(alarm still active in this case)
TypeofalarmtY
(automatic AUtO)
or alternatively
(manual ManU)
ToviewthePASSfolderinthemaindisplay,
press the Esc and Set keys at the same time.
[esc+set]
Pressing the two keys will open the menu
containing the list of folders. Use the“up”and
“down”keys to nd the EU folder.
Press the set key to open the PAS folder.
Press the set key again to view details of the
selected event (EU00 in this specic case).
1.3.9 Setting a password (Par/PASS folder)
Toviewparametersvisibleforthegivenpassword,openfolderPASS(pressescandsettogether
[esc+set]fromthemaindisplayandsearchthefolderusingtheup/downkeys)andsetthePASS
value.
1.3.10 Alarm events (Par/EU folder)

11
SKP 20

12
SKP 20
2.
Diagnostics
2.1 Alarms
2.2 Digital alarm
2.3 Analog alarms
2.4 Alarm table
Preliminary precautions
• Thecontrolpanelallowsyoutomakeallthenecessaryadjustmentstothechilleroperationandtoviewthevaluesofthe
mainparametersandalarms.Thecontrolpanelislocatedonthefrontpaneloftheelectricalboard.
The“EnergySBA600”performsfullinstallationdiagnosticsandreportsavarietyofalarms.
Parameters for alarm activation and resetting can be viewed and congured in folder
AL (parameters AL00…AL82) (see User Interface and Parameters section).
2.1.1 Automatic reset
Forautomaticresetalarms,normaloperationisrestoredassoonasthecauseofthealarmhasbeen
removed.
2.1.2 Manual reset
Alarmscanbemanuallyresetbypressingandreleasingthe[UP+DOWN]keys
Normal operation can only be reset
• bypressingakeyontheinstrumentkeyboardand
• onlyifthecauseofthealarmhasbeenremoved.
2.1.3 Alarm mute
Alarms can be acknowledged by pressing any key.
acknowledging an alarm has no eect on the alarm generated other than on the alarm
LED,whichgoesfromxedtoashing.
An alarm has two eects:
• Itblockstheservicesconcerned
• Messageonthekeyboarddisplayalternateswithamessageonthemaindisplay.
Thenexttwosectionssummarizealarmsgroupedbytype(digitaloranalogue).
Alarm code and alarm parameters are in bold (folder PAr/AL)
2.1 Alarms
Alarm code
Name of alarm
Bypass activation
event
Bypass time
Automatic alarm
activation time
Manual alarm
activation
time
Exit alarm
deactivation time
Number of interventions
per sample time
E001
Circuit 1
high pressure
alarm
None Not
present
Not
present
Not
present
Not
present AL10
E002
Circuit 2
high pressure
alarm
None Not
present
Not
present
Not
present
Not
present AL10
E005
(NOTA 4)
Circuit 1
low pressure
alarm
Circuit
compressor
activated
or reversal
of 4-way valve
(NOTE1)
(NOTE4)
AL11
(NOTA4)
Not
present
Not
present
Not
present AL12
Alarm code
Name of alarm
Bypass activation
event
Bypass time
Automatic alarm
activation time
Manual alarm
activation
time
Exit alarm
deactivation time
Number of interventions
per sample time
E006
(NOTA 4)
Circuit 2
low pressure
alarm
Circuit
compressor
activated
or reversal
of 4-way valve
(NOTE1)
(NOTE4)
AL11
(NOTA4)
Not
present
Not
present
Not
present AL12
E020
(NOTA 2)
Primary circuit
flow switch
alarm
Internal circuit
pump activation
(One of the two
pumps)
AL14 AL15 AL16 AL15 Not
present
E025
(NOTA 3)
Primary circuit
pump thermal
switch alarm
External circuit
pump activation AL17 AL18 AL19 AL18 Not
present
E010
Compressor 1
thermal switch
Compressor 1
switched on AL20 Not
present
Not
present
Not
present AL21
E011
Compressor 2
thermal switch
Compressor 2
switched on AL20 Not
present
Not
present
Not
present AL21
E012
Compressor 3
thermal switch
Compressor 3
switched on AL20 Not
present
Not
present
Not
present AL21
E013
Compressor 4
thermal switch
Compressor 4
switched on AL20 Not
present
Not
present
Not
present AL21
E015
(NOTE 2)
Compressor 1 oil
pressure switch
Compressor 1
switched on AL22 Not
present
Not
present
Not
present AL23
E016
(NOTE 2)
Compressor 2 oil
pressure switch
Compressor 2
switched on AL22 Not
present
Not
present
Not
present AL23
E017
(NOTE 2)
Compressor 3 oil
pressure switch
Compressor 3
switched on AL22 Not
present
Not
present
Not
present AL23
E018
(NOTE 2)
Compressor 4 oil
pressure switch
Compressor 4
switched on AL22 Not
present
Not
present
Not
present AL23
Er40
Primary exchanger
fan thermal switch
None Not
present
Not
present
Not
present
Not
present AL24
Er41
External exchanger
fan thermal switch
Circuit 1
None Not
present
Not
present
Not
present
Not
present AL25
Er42
External exchanger
fan thermal switch
Circuit 2
None Not
present
Not
present
Not
present
Not
present AL25
E021
Primary circuit
pump 1 thermal
switch
None Not
present
Not
present
Not
present
Not
present AL26
2.2 Digital alarms

13
SKP 20
(NOTE1) Thebypassisactivatedbythereversalofthe4-wayvalveonlyifatleastonecompressor
is on
(NOTE2) Thealarmisenabledonlyiftheassociatedresource(e.g.agivencompressororpump)
is active
(NOTE3) Thealarmisenabledonlyiftheassociatedresource(e.g.speciccompressororspecic
pump) is active only in heating mode.
(NOTE4) Thealarmisenabledonlyiftheassociatedresource(e.g.speciccompressororspecic
pump) is active only in heating mode. Low pressure digital alarm related to dedicated
circuitisnotactiveifPump-downvalveoftherelavantcircuitisactive(valveclosed,
Pump-downongoing,andafterCP33timeafterdesactivation)
(NOTE1) IfNo.trips=1,thealarmisalwaysmanualresettype.
(NOTE2) Alarmbypassisactiveinheatingmodeonly.
(NOTE3) Anosetof6°C(valuecannotbechanged)isaddedtotheactivationsetpointAL51
during the defrost stage.
Alarm code
Name of alarm
Bypass activation
event
Bypass time
Automatic alarm
activation time
Manual alarm
activation
time
Exit alarm
deactivation time
Number of interventions
per sample time
E022
Primary circuit
pump 2 thermal
switch
None Not
present
Not
present
Not
present
Not
present AL26
E026
Disposable circuit
pump thermal
switch
None Not
present
Not
present
Not
present
Not
present AL27
E050
Primary exchanger
electric heater 1
thermal switch
None Not
present
Not
present
Not
present
Not
present
Not
present
E051 Primary exchanger
electric heater 2 None Not
present
Not
present
Not
present
Not
present
Not
present
E056 Auxiliary output
alarm None Not
present
Not
present
Not
present
Not
present
Not
present
2.4 Alarms Table
Alarm code
Name of alarm
Bypass activation event
Bypass time
SETactivation
Hysteresis
Automatic alarm time
(NOTE1)
No. of trips
Control Probe
E003
Circuit 1
analogue
high pressure
alarm
None None AL40 AL41 Not present AL42
Circuit 1
high pressure
probe
E004
Circuit 1
analogue
high pressure
alarm
None None AL40 AL41 Not present AL42
Circuit 1
high pressure
probe
E007
Circuit 1
analogue
low pressure
alarm
A circuit 1
compressor
is switched on
or reversal of
the 4-way
valve
AL43 AL44 AL45 Not present A46
Circuit 1
low pressure
probe
E008
Circuit 2
analogue
low pressure
alarm
A circuit 2
compressor
is switched on
or reversal of
the 4-way
valve
AL43 AL44 AL45 Not present A46
Circuit 2
low pressure
probe
E030 Primary circuit
antifreeze
On/O (local or
remote),input
in heat mode
(NOTE2)
AL50 AL51
(NOTA3) AL52 Not present A53
Internal
exchanger
water/air outlet
temperature
E031 External circuit
antifreeze
On/O (local or
remote),input
in heat mode
(NOTE2)
AL54 AL55 AL56 Not present A57
External
exchanger
outlet water
temperature
E032 “Vacuum”
circuit 1 None None AL59 AL60 AL58 manual reset Low pressure
input circuit 1
Alarm code
Name of alarm
Bypass activation event
Bypass time
SETactivation
Hysteresis
Automatic alarm time
(NOTE1)
No. of trips
Control Probe
E033 “Vacuum”
circuit 2 None None AL59 AL60 AL58 manual reset Low pressure
input circuit 2
E035 High
temperature None None AL47 AL48 AL49 Automatic
reset
Internal
exchanger
water/air outlet
temperature
• Thealarmsignalconsistsofacode,theformatbeing“E0nn”(nnisa2-gurenumberiden-
tifyingthetypeofalarm,e.g.E000,E025,E039...).
• Inthecaseofmultiplesimultaneousalarmsonlytheonewiththelowestcodewillbedispla-
yed(e.g.simultaneousalarmsE000andE001).ThedisplaywillshowonlyE000alternated
with the main display page
• Ifthemeasurementonthemaindisplayisincorrect,intheeventofanalarm,thealternate
alarm code will alternate with“----”.
All possible alarms are listed in the table below with their respective codes and the relative utilities
blocked:
2.4.1 Alarms table key
column
Alarm code
NOTA:
the codes are shown in ascending order (E000, E001) but there may be
some gaps (there is no E006)
Name of alarm
Notes CMP 1/2 Compressor 1/power step 2
PUMP 1/2 Pump1/2
Alarm DDigital
AInput
Reset AUTO Automatic
UTILITY
OFF COMP1 OFF compressor 1
OFF COMP2 OFF compressor 2
OFF COMP3 OFF compressor 3
OFF COMP4 OFF compressor 4
OFF (1) Whenusedfortemperaturecontrol
OFF (2) Whenusedfortemperaturecontroland/orantifreeze
OFF RES1 OFF heater 1
OFF RES2 OFF heater 2
2.3 Analogue alarms

14
SKP 20
Alarm Code
Name of Alarm
Notes
Digital/Analogue
Alarm type
Sanitary water valve
Sanitary water heater
Compressors
External exchanger fan
Recirculation fan
Internal circuit pump
External circuit pump
Internal exchanger heaters
External exchanger heaters
Output
Auxiliary
Boiler
E000 General alarm DAUTO OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF
E001 Circuit 1 digital high pressure DEvents OFF (1)
E002 Circuit 2 digital high pressure DEvents OFF (1)
E003 Circuit 1 analogue high pressure AEvents OFF (1)
E004 Circuit 2 analogue high pressure AEvents OFF (1)
E005 Circuit 1 digital low pressure DEvents OFF (1) OFF (2) OFF
E007 Circuit 1 analogue low pressure AEvents OFF (1) OFF (2) OFF
E008 Circuit 2 analogue low pressure AEvents OFF (1) OFF (2) OFF
E009 Machine low charge AEvents OFF OFF (2) OFF
E010 Compressor 1 thermal switch CMP 1 DEvents OFF COMP1
E011 Compressor 2 thermal switch CMP 2 DEvents OFF COMP2
E012 Compressor 3 thermal switch CMP 3 DEvents OFF COMP3
E013 Compressor 4 thermal switch CMP 4 DEvents OFF COMP4
E015 Compressor 1 oil pressure switch CMP 1 DEvents OFF COMP1
E016 Compressor 2 oil pressure switch CMP 2 DEvents OFF COMP2
E017 Compressor 3 oil pressure switch CMP 3 DEvents OFF COMP3
E018 Compressor 4 oil pressure switch CMP 4 DEvents OFF COMP4
E020 Primarycircuitowswitch DTime OFF for manual
reset alarm OFF OFF
OFF for
manual
reset
alarm
OFF OFF
E021
Primary circuit pump 1 thermal switch DEvents OFF (3) OFF (3) OFF
Pump 1 OFF 3) OFF 3)
E022
Primary circuit pump 2 thermal switch DEvents OFF 3) OFF 3) OFF
Pump 2 OFF 3) OFF 3)
E025
Externalcircuitowswitch DTime OFF
OFF if
alarm with
manual reset
OFF for
manual
reset
alarm
OFF
E026
Disposable circuit pump thermal switch DEvents OFF OFF OFF
E030
Primary circuit antifreeze AAUTO OFF OFF
E031
External circuit antifreeze AAUTO OFF OFF
E032
Vacuum circuit 1 AManual OFF (1) OFF (2) OFF
E033
Vacuum circuit 2 AManual OFF (1) OFF (2) OFF
E035
High temperature AAUTO OFF
E040
Primary exchanger fan thermal switch DEvents OFF OFF OFF
E041
Circuit 1 external heat exchanger fan thermal switch DEvents OFF (2) OFF (1) OFF (2)
E042
Circuit 2 external heat exchanger fan thermal switch DEvents OFF (2) OFF (1) OFF (2)
E045
Faulty clock AUTO
E046
Timelost AUTO
2.4.2 Alarms table

15
SKP 20
Alarm Code
Name of Alarm
Notes
Digital/Analogue
Alarm type
Sanitary water valve
Sanitary water heater
Compressors
External exchanger fan
Recirculation fan
Internal circuit pump
External circuit pump
Internal exchanger heaters
External exchanger heaters
Output
Auxiliary
Boiler
E047
LAN communication absent AUTO
E048
Anti-legionnaires alarm AUTO
E050
Primary exchanger electric heater 1 thermal switch DAUTO OFF
RES.1
E051
Primary exchanger electric heater 2 thermal switch DAUTO OFF
RES.2
E056
Auxiliary output thermal switch DAUTO OFF
E060
Primary exchanger water or air input temperature
probe faulty AUTO SeeProbeErrorsTable
E061
Primary exchanger water or air output temperature
probefaulty,and/orCircuit1primaryexchanger
wateroutlettemperatureprobefaulty,
and/or Circuit 2 primary exchanger
water outlet temperature probe faulty
AUTO SeeProbeErrorsTable
E062
Circuit 1 external exchanger temperature
probefaulty,and/orCircuit2external
exchanger temperature probe faulty
AUTO SeeProbeErrorsTable
E063
Faulty disposable exchanger water or air input
temperature probe AUTO SeeProbeErrorsTable
E064
Faulty disposable exchanger water or air output
temperature probe AUTO SeeProbeErrorsTable
E065
Faulty ambient temperature probe AUTO SeeProbeErrorsTable
E066
Sanitary water temperature probe faulty AUTO SeeProbeErrorsTable
E067
Faulty display probe
(temperature / pressure) AUTO SeeProbeErrorsTable
E068
Faulty external temperature probe AUTO
E069
Faulty circuit 1 high pressure transducer or
Faulty circuit 2 high pressure transducer AUTO SeeProbeErrorsTable
E070
Faulty circuit 1 low pressure transducer
Faulty circuit 2 low pressure transducer AUTO
E071
Faulty compressor 1 discharge temperature probe AUTO
E073
Faulty dynamic setpoint input AUTO
E074
Faulty primary heat exchanger transducer
circuit1,and/orFaultyprimaryheat
exchanger transducer circuit 2
AUTO SeeProbeErrorsTable
E075
Faulty disposable exchanger transducer
circuit1,and/orFaultydisposable
exchanger transducer circuit 2
AUTO SeeProbeErrorsTable
E080
Conguration error AUTO OFF OFF
E081
Compressoroperatinghoursexceeded(*) CMP Manual
E085
Primarycircuitpumpoperatinghoursexceeded(*) PUMP Manual
E086
Externalcircuitpumpoperatinghoursexceeded(*) PUMP Manual
E090
Alarm log full warning Manual

Serie
SKP 20
Issue Supersedese
02.15 ---
Catalogue
M 204b
Thedataindicatedinthismanualispurelyindicative.
Themanufacturerreservestherighttomodifythedatawheneveritisconsiderednecessary.
Table of contents