AIREDALE R410A User manual

6PDUW&RRO'RZQÀRZ16 to 60kW
R410A
Technical Manual

Warranty
All AIAC products or parts (non consumable) supplied for installation within the UK mainland and commissioned by
an AIAC engineer, carry a full parts & labour warranty for a period of 12 months from the date of commissioning or 18
months from the date of despatch, whichever is the sooner.
Parts or equipment supplied by AIAC for installation within the UK or for Export that are properly commissioned in
DFFRUGDQFHZLWK$,$&VWDQGDUGVDQGVSHFL¿FDWLRQQRWFRPPLVVLRQHGE\DQ$,$&HQJLQHHUFDUU\DPRQWKZDUUDQW\on non consumable parts only from the date of commissioning or 18 months from the date of despatch, whichever is the
sooner.
3DUWVRUHTXLSPHQWLQVWDOOHGRUFRPPLVVLRQHGQRWWRDFFHSWDEOH$,$&VWDQGDUGVRUVSHFL¿FDWLRQLQYDOLGDWHDOOZDUUDQW\Warranty is only valid in the event that
In the period between delivery and commissioning the equipment: is properly protected & serviced as per the AIAC
installation & maintenance manual provided where applicable the glycol content is maintained to the correct level.
,QWKHHYHQWRIDSUREOHPEHLQJUHSRUWHGDQGRQFHZDUUDQW\LVFRQ¿UPHGDVYDOLGXQGHUWKHJLYHQLQVWDOODWLRQDQGoperating conditions, the company will provide the appropriate warranty coverage (as detailed above) attributable to the
UHFWL¿FDWLRQRIDQ\DIIHFWHG$LUHGDOHHTXLSPHQWVXSSOLHGH[FOXGLQJFRVWVIRUDQ\VSHFLDOLVWDFFHVVRUOLIWLQJHTXLSPHQWthat must be ordered by the customer).
Any spare part supplied by Airedale under warranty shall be warranted for the unexpired period of the warranty or 3
months from delivery, whichever period is the longer.
To be read in conjunction with the Airedale conditions of sale - Warranty and warranty procedure, available upon
request.
CAUTION
Warranty cover is not a substitute for maintenance. Warranty cover is conditional to maintenance being carried out
in accordance with the recommendations provided during the warranty period. Failure to have the maintenance
procedures carried out will invalidate the warranty and any liabilities by Airedale International Air Conditioning Ltd.
Spares
A spares list for 1, 3 and 5 years will be supplied with every unit and is also available from our spares department on
request.
Training
As well as our comprehensive range of products, Airedale offers a modular range of Refrigeration and Air Conditioning
Training courses, for further information please contact Airedale.
Customer Services
For information, visit us at our Web Site: www.airedale.com
Legal Notices
AIAC Ltd endeavours to ensure that the information in this document is correct and fairly stated, but none of the statements are to be relied upon as a
statement or representation of fact. AIAC Ltd does not accept liability for any error or omission, or for any reliance placed on the information contained in
this document.
The development of Airedale products and services is continuous and the information in this document may not be up to date. It is important to check the
current position with AIAC Ltd at the address stated. This document is not part of a contract or licence unless expressly agreed.
No part of this document may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying, recording, or
information storage and retrieval systems, for any purpose other than the purchaser’s personal use, without the express written permission of AIAC Ltd.
Cover image for illustration only.
©2012 Airedale International Air Conditioning Limited. All rights reserved. Printed in the UK.
SmartCool™ 16 - 60 Precision Air Conditioning
2
Introduction
SmartCool Technical Manual 7525371 V1.2.0_03_2013

Warranty 2
Health and Safety 4
Nomenclature 5
Introduction 6
6\VWHP&RQÀJXUDWLRQVPrecision Air Conditioning System 8
Construction 8
8QLW2YHUYLHZRefrigeration Components 9
Chilled Water Components 13
$LUÀRZ&RPSRQHQWVElectrical Components 17
+XPLGL¿FDWLRQControls 21
General Features 27
,QVWDOODWLRQ'DWDDimensions 30
Positioning 31
Minimum Unit Clearance 31
Weights 32
Refrigerant Pipe Sizing Guide 33
Refrigerant Charging Guide 35
Oil Charging Guide 38
Pipework Schematics 39
Incoming Services 42
Electrical Incoming Services 43
Glycol 45
'RZQÁRZ'LUHFW([SDQVLRQPerformance Data 46
Sound Data 48
SC09D016 - SC09D019 50
SC09D023 - SC09D026 52
SC12D020 - SC12D029 54
SC12D033 - SC12D036 56
SC15D027 - SC15D035 58
SC15D040 - SC15D044 60
SC18D037 - SC18D044 62
SC18D048 - SC18D055 64
Interconnecting Wiring 66
'RZQÁRZ&KLOOHG:DWHUPerformance Data 72
Sound Data 73
SC09D015 - SC09D030 74
SC12D025 - SC12D045 76
SC15D035 - SC15D060 78
SC18D045 - SC18D080 80
Waterside Pressure Drop Data 82
Interconnecting Wiring 83
$IWHU6DOHVWarranty 84
Contents
Precision Air Conditioning SmartCool™ 16 - 60
3
SmartCool Technical Manual 7525371 V1.2.0_03_2013
Introduction

Health and Safety
IMPORTANT
The information contained in this manual is critical to the correct operation and maintenance of the unit and should be
read by all persons responsible for the installation, commissioning and maintenance of the Airedale unit.
Safety
The equipment has been designed and manufactured to meet international safety standards but, like any mechanical/
electrical equipment, care must be taken if you are to obtain the best results.
CAUTION
1. Installation, service and maintenance of Airedale equipment should only be carried out by technically trained
competent personnel.
2. When working with any air conditioning units, ensure that the electrical isolator is switched off prior to servicing or
repair work and that there is no power to any part of the equipment.
3. $OVRHQVXUHWKDWWKHUHDUHQRRWKHUSRZHUIHHGVWRWKHXQLWVXFKDV¿UHDODUPFLUFXLWV%06FLUFXLWVHWF4. Electrical installation commissioning and maintenance work on this equipment should be undertaken by competent
and trained personnel in accordance with local relevant standards and codes of practice.
5. 7KHUHIULJHUDQWXVHGLQWKLVUDQJHRISURGXFWVLVFODVVL¿HGXQGHUWKH&26++UHJXODWLRQVDVDQLUULWDQWZLWKVHW:RUNSODFH([SRVXUH/HYHOV:(/IRUFRQVLGHUDWLRQLIWKLVSODQWLVLQVWDOOHGLQFRQ¿QHGRUSRRUO\YHQWLODWHGDUHDV6. A full hazard data sheet in accordance with COSHH regulations is available should this be required.
Personal protective equipment
Airedale recommends that personal protective equipment is used whilst installing, maintaining and commissioning
equipment.
Refrigerant Warning
The Airedale SmartCool uses R410A refrigerant which is a high pressure refrigerant. It requires careful attention to
proper storage and handling procedures.
Use only manifold gauge sets designed for use with R410A refrigerant. Use only refrigerant recovery units and cylinders
designed for high pressure refrigerants.
R410A must only be charged in the liquid state.
The refrigerant must be stored in a clean, dry area away from sunlight and never be stored above 50°C.
Manual Handling
Some operations when servicing or maintaining the unit may require additional assistance with regard to manual
handling. This requirement is down to the discretion of the engineer. Remember, do not perform a lift that exceeds your
ability.
Environmental Policy
It is our policy to:
Take a proactive approach to resolve environmental issues and ensure compliance with regulatory requirements.
Train personnel in sound environmental practices.
Pursue opportunities to conserve resources, prevent pollution and eliminate waste.
Manufacture products in a responsible manner with minimum impact on the environment.
Reduce our use of chemicals and minimise their release to the environment.
Measure, control and verify environmental performance through internal and external audits.
Continually improve our environmental performance.
SmartCool™ 16 - 60 Precision Air Conditioning
4
Introduction
SmartCool Technical Manual 7525371 V1.2.0_03_2013

SC
SC 12 D 025 C 0 0 0 0
0
12
D
V
Downflow
Upflow
400V / 3PH / N / 50Hz
0
SmartCool
Case Width (dm) 9 - 18
SC 15 D 030 X 2 0
0
0
0
Nominal Cooling Capacity (kW)
027
Air Cooled Direct Expansion
Chilled Water
X
C
Air Cooled Direct Expansion
Chilled Water
X
C
Number of Compressors (per circuit)
0
1
2
Number of Compressors (per circuit)
0
1
2
SmartCool Single Circuit Chilled Water
SmartCool Single Circuit Tandem Compressor
–
–
0
0
SC
SC
18
09
D
D
040
023
X
X
1
1
X 1
SmartCool Dual Circuit Single Compressor
SmartCool Single Circuit Single Compressor
–
–
Examples
Circuit 1
Circuit 2
Nomenclature
Precision Air Conditioning SmartCool™ 16 - 60
5
SmartCool Technical Manual 7525371 V1.2.0_03_2013
Introduction

Introduction
Designed to provide environmental precision air conditioning for applications such as telecommunication facilities, data
centers, computer rooms, clean rooms and laboratories.
Description Capacity kW (1)
X1X1 Dual circuit direct expansion air cooled 54 - 60
X200 Single circuit, tandem compressors direct expansion 21 - 47
X100 Single circuit single compressor direct expansion 16 - 26
C000 Single circuit chilled water 25 - 68
(1) %DVHGRQQRPLQDOXQLWFDSDFLWLHV)XOOIXQFWLRQXQLWVSURYLGHIXOOFRQWURORIWHPSHUDWXUHKXPLGLW\DQG¿OWUDWLRQThe modular design of the SmartCool allows grouping of differing model types and capacities to be installed side by
VLGH7KHÀH[LELOLW\RIWKLVW\SHRILQVWDOODWLRQSURYLGHVIRUPXOWLFLUFXLWIXQFWLRQDOLW\A full range of air cooled condensers is available with the direct expansion indoor units to provide a matched system
with optional performance upgrade, refer to Outdoor Unit.
Also available is a full range of Airedale water chillers to complement the chilled water indoor units.
The range has been designed and optimised for operation with ozone benign refrigerant R410A.
CE Directive
Airedale certify that the equipment detailed in this manual conforms with the following EC Directives:
Electromagnetic Compatibility Directive (EMC) 2004/108/EC
Low Voltage Directive (LVD) 2006/95/EC
Machinery Directive (MD) 89/392/EEC in the version 2006/427/EC
Pressure Equipment Directive (PED) 97/23/EC
To comply with these directives appropriate national & harmonised standards have been applied.
These are listed on the Declaration of Conformity, supplied with each product.
SmartCool™ 16 - 60 Precision Air Conditioning
6
Introduction
SmartCool Technical Manual 7525371 V1.2.0_03_2013

6\VWHP&RQ¿JXUDWLRQV
C000
Where a chilled water single circuit system is
preferred, warm room air is drawn across the
HI¿FLHQWFRROLQJFRLORIWKH6PDUW&RRO&DQGWKHheat transferred to a chilled water system such as
$LUHGDOH¶VKLJKHI¿FLHQF\FKLOOHU%\FRQWUROOLQJWKHRUZD\ZDWHUUHJXODWLQJvalve, the intelligent Airetronix microprocessor
can achieve precise control of temperature and
humidity.
X200
The SmartCool X200 is an air cooled, direct
expansion (DX), single circuit system linked to a
remotely mounted air cooled condenser.
2SWLPLVHGIRUKHDWWUDQVIHUXVLQJHQHUJ\HI¿FLHQWrefrigerant R410A, the X200 system is located
within the conditioned space, absorbing room heat
and transferring it outside to the condenser.
%\XVLQJWZRVDPHVL]HGVFUROOFRPSUHVVRUVDFURVVWKH;VLQJOHFLUFXLWSDUWORDGHI¿FLHQF\can be maximised and capacity more precisely
matched to application.
X1X1
The SmartCool X1X1 is an air cooled, direct
expansion (DX), double circuit system linked
to two separate, remotely mounted air cooled
condensers.
2SWLPLVHGIRUKHDWWUDQVIHUXVLQJHQHUJ\HI¿FLHQWrefrigerant R410A in each circuit, the X1X1
system is located within the conditioned space,
absorbing room heat and transferring it outside
to the condensers.
%\XVLQJRQHVFUROOFRPSUHVVRUVDFURVVWKH;;GRXEOHFLUFXLWSDUWORDGHI¿FLHQF\FDQEHmaximised and capacity more precisely matched
to application.
X100
The SmartCool X100 is an air cooled, direct
expansion (DX), single circuit system linked to a
remotely mounted air cooled condenser.
The X100 is simular to the X200 except it has one
compressor
Precision Air Conditioning SmartCool™ 16 - 60
7
SmartCool Technical Manual 7525371 V1.2.0_03_2013
Introduction

Precision Air Conditioning System
Each unit shall be capable of providing ___ kW total cooling and ___ kW sensible cooling @ ____m³/sec of conditioned
DLU7KHURRPFRQGLWLRQVKDOOEHBBB&G%BBB5+#DVXPPHUGHVLJQDPELHQWWHPSHUDWXUHRIBBB&G%7KHFKLOOHGZDWHUWHPSHUDWXUHVVKDOOEHBBB&ÀRZZLWKBBB&UHWXUQ7KHFRPSXWHUURRPDLUFRQGLWLRQLQJHTXLSPHQWVKDOOEHGHVLJQHGVSHFL¿FDOO\IRUSUHFLVLRQWHPSHUDWXUHDQGKXPLGLW\FRQWURODSSOLFDWLRQV,WVKDOODXWRPDWLFDOO\PRQLWRUDQGFRQWUROFRROLQJKHDWLQJKXPLGL¿FDWLRQGHKXPLGL¿FDWLRQDQG¿OWHULQJIXQFWLRQVIRUWKHFRQGLWLRQHGVSDFH7KHV\VWHPVKDOOEHEXLOWWRWKHKLJKHVWTXDOLW\HQJLQHHULQJDQGmanufacturing standards, and shall be subject to a functional test prior to leaving the factory.
Construction
The cabinet shall be manufactured using an external aluminium extrusion frame with aluminium corners. Panels shall be
completely removable to gain unequalled access during installation as required. The galvanised sheet steel panels and
DOXPLQLXPIUDPHDQGFRUQHUVVKDOOEHFRDWHGZLWKDQHSR[\EDNHGSRZGHUSDLQWWRSURYLGHDGXUDEOH¿QLVK6WDQGDUGXQLWFRORXUVKDOOEH%ODFN*UH\WR5$/&DELQHWVVKDOOEHOLQHGLQWHUQDOO\ZLWKPP¿UHUHVLVWDQWIRDP%6IRUWKHUPDODQGDFRXVWLFLQVXODWLRQ7KHinsulation density shall not be less than 75 kg/m³.
7KHFDELQHWGRRUVVKDOOEHIXOOKHLJKWKLQJHGDQGNH\ORFNVHFXUHG7KHKLQJHDUUDQJHPHQWVKDOODOORZÀH[LEOHGRRUopening/removal for improved access.
A propriety rubberised door seal shall reduce sound breakout and eradicate air leakage. In-seal type foam based door
seals shall not be acceptable.
7KHFRQWUROSDQHOLVPRXQWHGRQKLQJHVWRDOORZHDV\UHPRYDORI¿OWHUVDQGDFFHVVWRVHYHUDOHOHFWULFDOFRPSRQHQWV7KHXQLWGHVLJQVKDOOLQFRUSRUDWHDVHULHVRI0¿[LQJVWRWKHWRSDQGERWWRPIDFHWRHDVHFXVWRPHUGXFWZRUNconnection and reduce installation time.
SmartCool™ 16 - 60 Precision Air Conditioning
8
Introduction
SmartCool Technical Manual 7525371 V1.2.0_03_2013

Airflow Components
Refrigeration Components
Incoming Mechanical
Services Incoming Electrical
Services
Filtration
Control Panel
Cooling Coil
Humidification
Unit Overview
Refrigeration Components 6\VWHP&RQ¿JXUDWLRQFeature X200 X100 X1X1
Refrigeration
Fixed Speed Scroll Compressor ƔƔƔElectronic Expansion Valves (EEV) ƔƔƔLiquid Line Sight Glass ƔƔƔLiquid Line Solenoid Valves ƔƔƔDischarge Line Non Return Valves ƔƔ–
Suction Throttle Valve żżżDirect Refrigerant Leak Detection żżżRefrigerant Pump Down żżżHydrophilic Epoxy Coated RTPF Cooling Coil ƔƔƔƔStandard Features żOptional Features –Feature Not Available
Precision Air Conditioning SmartCool™ 16 - 60
9
SmartCool Technical Manual 7525371 V1.2.0_03_2013
Introduction

Refrigeration
Evaporator
(X200, X100 and X1X1 Models)
$ODUJHVXUIDFHDUHDFRLOVVKDOOEHLGHDOO\SRVLWLRQHGWRRSWLPLVHDLUÀRZDQGKHDWWUDQVIHULWVKDOOEHPDQXIDFWXUHGIURPUHIULJHUDWLRQTXDOLW\FRSSHUWXEHZLWKPHFKDQLFDOO\ERQGHGDOXPLQLXP¿QV7KHFRSSHUWXEHVKDOOEHLQWHUQDOO\ULÀHGIRULPSURYHGKHDWWUDQVIHU)LQVVKDOOEHFRDWHGZLWKDQRQVWLFNDFU\OLFK\GURSKLOLF¿OPWRSURYLGHDGGLWLRQDOFRUURVLRQSURWHFWLRQDQGHI¿FLHQWsurface water removal for improved performance. Plain aluminium shall not be acceptable.
The cooling coil shall be mounted over a full width stainless steel condensate tray.
7KHIDFWRU\SUHVVXUHWHVWVKDOOEHQRWOHVVWKDQ%DUJSweated copper pipe for brazed connection shall be standard.
Compressor
Compressor(s) shall be mounted on the unit base via the use of vibration
isolators. Each compressor shall be designed for use with R410A refrigerant.
&RPSUHVVRU&RQ¿JXUDWLRQVX200 X100 X1X1
Circuit 1 CP
Thermal Protection ƔƔƔSingle Compressor –ƔƔTandem Compressors Ɣ– –
Circuit 2 CP
Thermal Protection – – ƔSingle Compressor – – ƔTandem Compressors –––
Tandem Compressors
Comprising of 2 scroll type compressors linked together by refrigerant pipework to
one common circuit.
Tandem compressors provide variable control of the system performance by
activating individual compressors as required. Multiple steps of unloading allow
external load demands to be met with greater precision, eliminating unnecessary
WHPSHUDWXUHDQGKXPLGLW\YDULDWLRQV&RQVHTXHQWO\V\VWHPHI¿FLHQF\DQGreliability are much improved by extending major component working hours.
Liquid Line Solenoid Valve
$OLTXLGOLQHVROHQRLGYDOYHLV¿WWHGWRHQDEOHSDUWLDOIXOOUHIULJHUDQWSXPSGRZQCompressor Discharge Line Non Return Valve
1RQUHWXUQYDOYHVDUH¿WWHGWRHQVXUHOLTXLGUHIULJHUDQWFDQQRWHQWHUWKHcompressors through the discharge line in the compressor off state.
(X1X1 unit the NRV is integral with the compressor.
;DQG;XQLWVWKH159LV¿WWHGWRWKHGLVFKDUJHSLSHZRUN
SmartCool™ 16 - 60 Precision Air Conditioning
10
Introduction
SmartCool Technical Manual 7525371 V1.2.0_03_2013

Electronic Expansion Valves (EEV)
Electronic expansion valves differ to the normal thermostatic expansion valves in their
ability to maintain control of the suction superheat at reduced head pressures. This
FDQOHDGWRVLJQL¿FDQWHQHUJ\VDYLQJVSDUWLFXODUO\DWUHGXFHGORDGLQJDQGORZDPELHQWtemperatures.
EEV step position, superheat setpoint, head pressure set point and other features can be
viewed and adjusted via the microprocessor display.
Whilst offering versatile control at the full design duty of the unit, Thermostatic Expansion
Valve’s (TEV) do not automatically optimise themselves to all operating conditions.
7KHUHIRUHLIWKHUHIULJHUDWLRQV\VWHPLVRSHUDWLQJDWRURIIXOOORDGHVSHFLDOO\at a lower ambient temperature than that for which the valve was sized, the conventional
TEV must have the design head pressure available to ensure good refrigerant control.
0DLQWDLQLQJDQDUWL¿FLDOO\KLJKFRQGHQVLQJSUHVVXUHLVQRUPDOLQFRQYHQWLRQDOV\VWHPVUsing an EEV allows for good refrigeration control whilst operating at part load and lower
DPELHQWFRQGLWLRQVZLWKDUHGXFHGFRQGHQVLQJSUHVVXUH%\¿WWLQJDQ((9DQGDGMXVWLQJWKHKHDGSUHVVXUHFRQWUROVHWWLQJDQLQFUHDVHLQWKHV\VWHP((5(QHUJ\(I¿FLHQF\5DWLRRIXSWRFDQW\SLFDOO\EHVHHQ7KH0ROOLHUGLDJUDPVKRZQEHORZKHOSVWRLOOXVWUDWHKRZWKLVLQFUHDVHLQHI¿FLHQF\LVDFKLHYHGEEV’s differ to normal thermostatic expansion valves in their ability to maintain control
RIUHIULJHUDQWÀRZDQGWKHVXFWLRQVXSHUKHDWDWUHGXFHGKHDGSUHVVXUHV7KHWXUQGRZQrate of a typical EEV is superior to that of it’s thermostatic equivalent, such that a reduced
optimum condensing pressure can be maintained at low compressor load. However low
WKHORDGLVRQWKHFRPSUHVVRUIURP]HURWRWKHUHZLOOQRWEHDSUREOHPZLWKWXUQGRZQHYHQGRZQWRRIWKHYDOYH¶VUDWHGFDSDFLW\Key:
&RROLQJ&\FOH#&DPELHQWZLWKDFRQYHQWLRQDO7(9¿WWHG(2) Cooling cycle @ 22°C ambient, demonstrating a typical EEV condensing temperature taking full advantage of lower
ambient air temperatures (below 35°C).
Heat of Rejection
Reduction in
Compressor Input
Power
Enthalpy kJ/kgIncrease in
Cooling Duty
Evaporating
Pressure
Reduced
Condensing
Pressure
Presssure
Bara
Thermostatic Expansion Valve (1)
Electronic Expansion Valve (2)
1
2
3
4
Precision Air Conditioning SmartCool™ 16 - 60
11
SmartCool Technical Manual 7525371 V1.2.0_03_2013
Introduction

Suction Throttle Valve
(X200, X100, X1X1 Models)
$QHOHFWULFDOO\RSHUDWHGVXFWLRQWKURWWOHYDOYHVKDOOEH¿WWHGWRSURYLGHDFFXUDWHFDSDFLW\FRQWUROIURPWRGHSHQGLQJRQWKHURRPORDG3UHFLVHWHPSHUDWXUHFRQWUROLVREWDLQHGDVDUHVXOWRIPRGXODWLQJWKHUHIULJHUDQWÀRZLQWKHevaporator by throttling a valve on the suction line.
&DSDFLW\#&5+UHWXUQDLUFRQGLWLRQV((5#&5+UHWXUQDLUFRQGLWLRQV100
90
80
70
60
50
40
30
20
10
Capacity (%)
0
1
2
EER
Fully Closed Fully Open
Minimum
Maximum
SmartCool™ 16 - 60 Precision Air Conditioning
12
Introduction
SmartCool Technical Manual 7525371 V1.2.0_03_2013

Airflow Components
Chilled Water Components
Incoming Services
Filtration
Control Panel
Cooling Coil
Humidification
Chilled Water Components 6\VWHP&RQ¿JXUDWLRQFeature C000
Chilled Water
Hydrophilic Epoxy Coated RTPF Chilled Water Coil Ɣ0-10 Volts Chilled Water Regulating Valve (3 Way) Ɣ0-10 Volts Chilled Water Regulating Valve (2 Way) żThreaded Connections żƔStandard Features żOptional Features –Feature Not Available
Precision Air Conditioning SmartCool™ 16 - 60
13
SmartCool Technical Manual 7525371 V1.2.0_03_2013
Introduction

Chilled Water Coil
/DUJHVXUIDFHDUHDFRLOVKDOOEHLGHDOO\SRVLWLRQHGWRRSWLPLVHDLUÀRZDQGKHDWWUDQVIHUWKH\VKDOOEHPDQXIDFWXUHGIURPSODLQFRSSHUWXEHVZLWKPHFKDQLFDOO\ERQGHGDOXPLQLXP¿QV)LQVVKDOOEHFRDWHGZLWKDQRQVWLFNDFU\OLF¿OPK\GURSKLOLFWRSURYLGHDGGLWLRQDOFRUURVLRQSURWHFWLRQDQGHI¿FLHQWVXUIDFHZDWHUUHPRYDOIRULPSURYHGSHUIRUPDQFHPlain aluminium shall not be acceptable.
The cooling coil shall be mounted over a full width stainless steel condensate tray.
)RUFRQWURORIZDWHUÀRZDSRUWPRGXODWLQJPL[LQJFRQWUROYDOYHVKDOOEH¿WWHGDVVWDQGDUG7KHIDFWRU\WHVWSUHVVXUHVKDOOQRWEHOHVVWKDQ%DUJDQGWKHPD[LPXPRSHUDWLQJSUHVVXUHVKDOOQRWEHOHVVWKDQbarg.
Sweat copper pipe for brazed connection shall be standard. Optional threaded connections shall be available.
0-10 Volts DC 3 Port Chilled Water Regulating Valve
)RUFRQWURORIZDWHUÀRZDSRUWPRGXODWLQJPL[LQJFRQWUROYDOYHVKDOOEH¿WWHGDVVWDQGDUG0-10 Volts DC 2 Port Chilled Water Regulating Valve
)RUV\VWHPVZLWKYDULDEOHVSHHGSXPSVDQGZDWHUÀRZDSRUWFRQWUROYDOYHFDQEH¿WWHGLQSODFHRIWKHVWDQGDUGSRUWYDOYH7KHWZRSRUWYDOYHKDVDVKXWRIISUHVVXUHRI%DUJThreaded Water Pipe Connection
&0RGHOV$VDQDOWHUQDWLYHWREUD]HGZDWHUSLSHFRQQHFWLRQV%63EUDVVPDOHWDSHUWKUHDGHGFRQQHFWLRQVVKDOOEHIDFWRU\¿WWHGSmartCool™ 16 - 60 Precision Air Conditioning
14
Introduction
SmartCool Technical Manual 7525371 V1.2.0_03_2013

$LUÀRZ&RPSRQHQWV6\VWHP&RQ¿JXUDWLRQ
$LUÀRZ
Features X200 X100 X1X1 C000
(&%DFNZDUG&XUYHG&HQWULIXJDO)DQVƔƔƔƔG4 Air Filtration ƔƔƔƔ+LJKHI¿FLHQF\)LOWUDWLRQZLWKSUH¿OWHU*)żżżż$LUÀRZ0RQLWRULQJƔƔƔƔ$LUÀRZ6ZLWFKƔƔƔƔConstant Air Volume żżżżConstant Pressure Control – – – żƔStandard Features żOptional Features –Feature Not Available
Fan & Motor Assembly
%DFNZDUGFXUYHGLPSHOOHUVGLUHFWGULYHFHQWULIXJDOIDQDVVHPEOLHVVKDOOEHXVHGZLWKLQWHJUDO(&PRWRUV7KH\VKDOOEHdynamically balanced for quiet operation.
)DQVSHHGDLUÀRZDQGH[WHUQDOVWDWLFSUHVVXUHVKDOOEHFRQWUROOHGE\WKHXVHRIDYROWDJHFRQWUROOHUZKLFKVKDOOmaintain optimised performance and reduce energy consumption.
Designed for high corrosion resistance, the impellers shall be composite plastic with a galvanised rotor.
Precision Air Conditioning SmartCool™ 16 - 60
15
SmartCool Technical Manual 7525371 V1.2.0_03_2013
Introduction

Electronically Commutated (EC) Fan Motor
EC motors incorporate integrated electronics to convert AC power to
'&IRUHI¿FLHQWDQGDFFXUDWHVSHHGFRQWURODQGDUHDGMXVWDEOHYLDWKHmicroprocessor display keypad.
7KHIDQVRIIHUPD[LPXPDLUÀRZSHUIRUPDQFHZKLOHNHHSLQJVRXQGlevels to a minimum.
,WJLYHVWKHÀH[LELOLW\RIFRQQHFWLQJWR$&PDLQVZLWKWKHHI¿FLHQF\DQGVLPSOHVSHHGFRQWURORID'&PRWRU7KH(&IDQRIIHUVVLJQL¿FDQWpower reduction in comparison with equivalent AC fan at both full and
modulated fan speeds. The inbuilt EC fan control module allows for fan
VSHHGPRGXODWLRQIURP$VWDQGDUG$&IDQVPRGXODWLQJUDQJHLVW\SLFDOO\RIIXOOIDQVSHHGStandard voltage regulated (VR) fan speed controllers offer a linear
response. The following illustration shows a comparison of the typical
power input required by each method.
G4 Filtration
3OHDWHGGLVSRVDEOHSDQHO¿OWHUVLQDULJLGIUDPH&RQIRUPWR%6(1*Access and removal from unit front.
As standard the microprocessor provides an alarm following a pre set run time limit being exceeded.
+LJK(I¿FLHQF\3UH)LOWHUVPPSOHDWHGGLVSRVDEOHSDQHO¿OWHUVFRQIRUPLQJWR%6(1)VKDOOEHSURYLGHG$PPGLVSRVDEOHV\QWKHWLFW\SHSUH¿OWHUVFRQIRUPLQJWR%6(1*VKDOOSURWHFWWKHPDLQ¿OWHU7RPDLQWDLQGHVLJQH[WHUQDOVWDWLFSUHVVXUH(63IDQVHOHFWLRQPD\DOWHUZLWKKLJKHI¿FLHQF\¿OWHUVAccess and removal from unit front.
As standard the microprocessor provides an alarm following a pre set run time limit being exceeded.
Air Flow Switch
An adjustable differential pressure switch shall activate a visual alarm at the status panel and break the power supply in
the event of a fan or motor failure.
Input Power
Airflow
EC (Electronically Commutated) Fan Speed Control
Regulated (VR) Fan Speed Control
Key
SmartCool™ 16 - 60 Precision Air Conditioning
16
Introduction
SmartCool Technical Manual 7525371 V1.2.0_03_2013

Electrical
The control panel contains the necessary compressor starter contactors, transformer, sub circuit protection, volt free
contacts for a common alarm and mains and inter-connecting terminals. The panel is situated within the cabinet and can
be opened to allow for essential maintenance of other components within the unit. The electrical control panels are wired
to the latest European standards and codes of practice.
Electrical Components 6\VWHP&RQ¿JXUDWLRQFeatures X200 X100 X1X1 C000
Electrical
Door Interlocked Mains Isolator ƔƔƔƔElectrical Switch Gear ƔƔƔƔHinged Electrical Panel ƔƔƔƔCustomer Connection Terminals ƔƔƔƔPower Monitoring żżżżPhase Monitoring Relay żżżżPhase Rotation Relay żżżż8OWUD&DSDFLWLYH0RGXOH&RQWUROOHU3RZHU%DFNXSżżżżDual Power Supply żżżżCompressor Soft Start żżż–
9DULDEOH+XPLGL¿FDWLRQżżżżElectric Heating żżżżModulating Electric Heating żżżżƔStandard Features żOptional Features –Feature Not Available
Precision Air Conditioning SmartCool™ 16 - 60
17
SmartCool Technical Manual 7525371 V1.2.0_03_2013
Introduction

Sub Fusing
The electrical mains supply for the system’s outdoor unit is supplied via the indoor unit.
0&%VDUH¿WWHGIRUFDEOHSURWHFWLRQ6XEIXVLQJLVQRWDYDOLDEOHZLWK6KRUW&DVH$[LDO)DQV6&$)Electric Heating
7KHVHVKDOOEHPXOWLVWDJH¿QQHGHOHFWULFKHDWLQJHOHPHQWVFRPSOHWHZLWKDXWRDQGPDQXDOUHVHWRYHUKHDWFXWRXWSURWHFWLRQHOHPHQWVKDOOEHSKDVHEDODQFHGIRULQFUHDVHGHI¿FLHQF\Electric Heating Thyristor Control
,QDGGLWLRQWRWKHHOHFWULFKHDWRSWLRQD±7K\ULVWRUVKDOOEHSURYLGHGWRGHOLYHUDFFXUDWHKHDWLQJFRQWURODual Power Supply
The SmartCool range shall be designed with dual power supply capability, so that in the event of a power failure the
supply can be switched from utility to an alternative power supply (such as second utility or generator).
A dual power supply changeover switch shall be provided to enable continuous power to the SmartCool in order to
reduce unit downtime and therefore loss of cooling to a minimum.
For the dual power supply feature to operate effectively the two incoming power supplies must have the same voltage
and frequency.
During changeover of power there is an interval of ~180ms with no power. For critical applications a power backup
module can be added to maintain power to the unit controls, allowing for immediate reinstatement of cooling following
changeover.
7KHRSWLRQDVVWDQGDUGRIIHUVVZLWFKSRVLWLRQVWDWXVDQGVXSSO\SULRULW\VHWERWKRIZKLFKDUHFRQ¿JXUDEOHYLDWKHXQLW¶Vdisplay.
6XSSO\SULRULW\VHWLVIXOO\FRQ¿JXUDEOHYLDWKHXQLW¶VGLVSOD\DQGLVXVHGWRVHWZKLFKRIWKHWZRSRZHUVXSSOLHVSRZHUZLOObe drawn from when both power supplies are active.
6ZLWFKSRVLWLRQVWDWXVLQGLFDWHVWRWKHHQGXVHUZKLFKSRVLWLRQWKHVZLWFKLVFXUUHQWO\LQLH$RU%DQGLVVKRZQYLDWKHunit’s display.
Ultracap UPS
The ultracap module is an external backup device for the controller. The module guarantees temporary power to the
controller in the event of power failures and allows for enough time to keep the controller running with time to change
power supplies. The module is made using Ultracap storage capacitors (EDLC = Electric Double Layer Capacitor),
which are recharged independently by the module.
These ensure reliability in terms of much longer component life than a module made with lead batteries: the life of the
Ultracap module is at least 10 years.
Energy Manager
Analysis of system energy consumption can be monitored via a dedicated LCD display. Unit parameters can be adjusted
via the unit microprocessor control to affect energy usage in line with the system need.
Phase Rotation Protection
A phase sequence relay shall be available for units containing 3 phase scroll compressors, to prevent possible damage
by running the compressor in the wrong direction.
SmartCool™ 16 - 60 Precision Air Conditioning
18
Introduction
SmartCool Technical Manual 7525371 V1.2.0_03_2013

+XPLGL¿FDWLRQControl Principles
,QDKXPLGL¿HUZLWKHOHFWURGHVVWHDPVKDOOEHSURGXFHGE\SDVVLQJDFXUUHQWEHWZHHQHOHFWURGHSODWHVWRJHQHUDWHKHDWThe higher the current being passed between the electrodes, the greater the quantity of steam that is produced.
To modulate the rate of steam production, this system shall vary the level of water within the cylinder, thereby increasing
the immersion level of the electrodes and the current being passed between them. The more conducting area that is
available to pass current between the electrodes, the larger the amount of steam that shall be produced.
Modulated by the controller, the water level is varied so that the level of steam being produced ensures that the room
humidity set-point is continually maintained within a tight tolerance.
Optimised Lifetime
7KHOLIHVSDQRIWKH$LUHGDOHKXPLGL¿FDWLRQV\VWHPVKDOOEHRSWLPLVHGE\WKHLQFOXVLRQRIDZDWHUFRQGXFWLYLW\VHQVRUinto the bottle feed. This sensor shall determine the conductivity level of the supply water and by using an algorithm
embedded in the software, determines the frequency that the bottle should be drained.
Example: (Optimised Lifetime with High Water Conductivity Supply)
As liquid water is boiled off into steam, mineral deposits are left in solution increasing the conductivity of the water.
To counter this, the intelligent software increases the frequency of drain meaning that the replenishing supply water
NHHSVWKHFRQFHQWUDWLRQRIPLQHUDOVGLOXWHG%\PDLQWDLQLQJDQDFFHSWDEOHPLQHUDOFRQFHQWUDWLRQWKHERWWOHOLIHVSDQLVmaximised.
'HKXPLGL¿FDWLRQ:LWK(OHFWULF+HDWLQJDQG+XPLGL¿FDWLRQRQO\&RQWUROOHGE\WKHPLFURSURFHVVRUWKHGHKXPLGL¿FDWLRQIHDWXUHUHGXFHVIDQVSHHGVE\DGMXVWDEOH7KHUHGXFWLRQRIIDQVSHHGLQFUHDVHVGHKXPLGL¿FDWLRQZKLFKPHDQVWKDWWKHWLPHWDNHQWRUHGXFHWKHURRPKXPLGLW\WRWKHUHTXLUHGlevel is drastically decreased, along with the energy required to do so.
7KHUHWXUQWHPSHUDWXUHLVPRQLWRUHGGXULQJGHKXPLGL¿FDWLRQWRHQVXUHWKDWWKHWHPSHUDWXUHGRHVQRWIDOOWRDFULWLFDOOHYHO,IWKHWHPSHUDWXUHUHDFKHVWKHORZOLPLWGHKXPLGL¿FDWLRQLVFDQFHOOHGXQWLOWKHUHWXUQDLUWHPSHUDWXUHLQFUHDVHV5DSLG'HKXPLGL¿FDWLRQControlled by the microprocessor, electronic expansion valves are unlike their conventional thermostatic counterparts in
that they can modulate independently of the suction line temperature. This unique feature allows the controller to raise
WKHVXSHUKHDWVHWSRLQWLQWXUQGURSSLQJWKHHYDSRUDWLQJWHPSHUDWXUHWRDSRLQWDWZKLFKFRQVLGHUDEOHGHKXPLGL¿FDWLRQtakes place.
2
3
4
5
6
7
8
0 5 10 15 2
0
(1)
(2)
1.00
0.98
0.96
0.94
0.92
0.90
0.88
0.86
0.84
0.82
Superheat Set Point (°C)
Mean Evaporating
Temperature (°C)
(1) Normal Operating Conditions
(2) Rapid De-hum Condition
Precision Air Conditioning SmartCool™ 16 - 60
19
SmartCool Technical Manual 7525371 V1.2.0_03_2013
Introduction

+XPLGL¿HU,QWHOOLJHQW0RGXODWLRQ+XPLGL¿FDWLRQVKDOOEHSURYLGHGE\DQHOHFWURGHERLOHU7KHVHDOHGKXPLGL¿HUGHVLJQVKDOOHQVXUHWKDWRQO\FOHDQVWHULOHsteam is supplied to the conditioned area and corrosive salts and minerals are held in the disposable bottle. The steam
VKDOOEHGLVWULEXWHGWKURXJKDVSDUJHSLSH¿WWHGWRWKHFRLODVVHPEO\Featuring modulating capacity output control as standard, the system shall provide continuous modulation of steam
RXWSXWLQUHVSRQVHWRDSURSRUWLRQDOFRQWUROVLJQDO7KHRXWSXWFRQWUROVKDOOUDQJHIURPRIWKHKXPLGL¿HUUDWHGYDOXHDQGEHGHVLJQHGWRJLYHDQDSSUR[LPDWHVWHDPRXWSXWRIDW&DWWKHVHQVRUWKXVHQVXULQJSUHFLVHcontrol of the conditioned space.
The cylinder operating life time shall be automatically optimised via the integrated water conductivity sensor, which
FRPELQHGZLWKWKHFRQWUROVVKDOOPRQLWRUDQGUHJXODWHWKHZDWHUUH¿OOF\FOHWRUHGXFHH[FHVVLYHVDOWGHSRVLWVDQGWKHprogressive wear of the cylinder.
$OOKXPLGL¿HUSDUDPHWHUVDQGDODUPVVKDOOEHDFFHVVLEOHDQGDGMXVWDEOHYLDWKHPLFURSURFHVVRUGLVSOD\NH\SDGXQLWmain features shall include not less than:
Supply water conductivity (S/cm)
Actual steam output (kg/h)
Required steam output (kg/h)
Actual current rating (A)
Required current rating (A)
Status mode (Start Up, Running, Filling, Draining)
Water Conductivity & Cylinder Type
Three different cylinders shall be available which correspond to the supply water conductivity.
The cylinder type shall be matched with the standard conductivity of the supply water to ensure optimum performance
and increases the life span of the cylinder.
1 Low Conductivity (Soft Water) 100 to 350 S/cm
2 Standard Conductivity (Moderate/Hard Water) 350 to 750 S/cm
3 High Conductivity (Very Hard Water) 750 to 1250 S/cm
Conductivity is a measure of the ability of water to pass an electric current, measured in micro Siemens / centimetre (S/
cm).
$VVWDQGDUGWKHKXPLGL¿HUVKDOOEH¿WWHGZLWKWKHVWDQGDUGFRQGXFWLYLW\F\OLQGHUZKLFKVKDOOFRYHUWKHPDMRULW\RIZDWHUsupplies. Where the water conductivity is known, please specify at order. For further details please contact Airedale.
SmartCool™ 16 - 60 Precision Air Conditioning
20
Introduction
SmartCool Technical Manual 7525371 V1.2.0_03_2013