Scholar IIITM (M&S) 8/09-1 15700 - 7 HVAC Equipment
2.2 VENTILATION SYSTEM CALIBRATION
The ventilation system requires calibration to ensure the appropriate amount of
fresh air is delivered to the classroom. Refer to the appropriate following ventilation
system and use the instructions to calibrate the system for correct air delivery.
A. Manual Fresh Air System. Fresh air ventilation by means of a damper with pressure
relief(openingtooutside,butnoexhaustblower),aventilationintakeblowerand
a fan speed controller provides up to 450 cfm of outside air. The damper can be
manuallyadjustedatinstallationtoprovidetherequiredventilationairow.
The fresh air door should be set in accordance with the amount of fresh air ow
required, up to a maximum of 450 CFM. Figure 3 illustrates the fresh air door
settings and air ow rates.
Follow the directions in Figure 3 to ensure proper air ow rate settings.
B. Motorized Fresh Air-CongurationB.Thisventilationoptionincludesamotorized
damper,afreshairintakeblowerandmotor,andablowermotorspeedcontroller.
This ventilation option can provide up to 450 CFM of outside air (but not to
exceed40%ofratedairow)andincludespressurerelief(openingtooutside,
but no exhaust blower). The motorized damper and blowers are controlled by
a Programmable Logic Controller (PLC). The PLC will operate the damper and
ventilationmotorsONLYwhentheIndoor/Evaporatorblowerisoperating.ThePLC
is factory wired for this operation by a 24 VAC signal to an input terminal on the
PLC. The damper is adjusted after installation for the required rate of ventilation. An
optional 24 VAC, 120 VAC or 240 VAC coil relay may be factory installed to control
thedamperandmotorfromanexternalsignal,e.g.anEMSorBASsystem.Alter
on the incoming outside air is standard.
PowerVent-CongurationJ(Optional).Thisventilationoptionincludesamotorized
damper,afreshairintakeblowerandmotor,anexhaustairblowerandmotorand
one blower motor speed controller. The blower speed controller operates both
blowers in tandem. (An optional blower speed control for the exhaust air blower can
be factory installed to provide independent control of the exhaust air blower motor
and allow pressurization of the classroom).The PowerVent can provide up to 450 CFM
ofoutsideair(butnottoexceed40%ofratedairow)andincludesactivepressure
relief. The motorized damper and blowers are controlled by a Programmable Logic
Controller(PLC).ThePLCwilloperatethedamperandventilationmotorsONLYwhen
the Indoor/Evaporator blower is operating. The PLC is factory wired for this operation
by a 24 VAC signal to an input terminal on the PLC. The damper is adjusted after
installation for the required rate of ventilation. An optional 24 VAC, 120 VAC or 240
VAC coil relay may be factory installed to control the damper and motor from an
externalsignal,e.g.anEMSorBASsystem.Alterontheincomingoutsideairis
standard.
The fresh air door is opened and closed by the motorized drive. Calibration, as
shown in Figure 4, will ensure the required amount of air, up to a maximum of 450
CFM, is delivered to the classroom.