alarco ATA User manual

ATA
Axial Fan Unit Heaters
Operation Manual

Revision Date: 180806 Published on: 180806
Revision No: 2

ATA
Axial Fan Unit Heaters
Operation Manual
Contents
Introduction .............................................................................5
Guarentee and Service ...........................................................6
General Characteristics ..........................................................7
Dimensions ..............................................................................8
Other Technical Characteristics.............................................8
Air Distribution Distances .....................................................................9
Coil Water Pressure Drop Graphic .......................................................9
Installation Rules...................................................................10
Location Selection and Mounting .......................................................10
Water Pipes Installation...................................................................... 11
Electricity ............................................................................................14
Trouble-Shooting Manual .....................................................15
Product Ordering Notation ...................................................15

Introduction
First of all, thanks for preferring ALARKO.
This manual includes operation and maintenance information
regarding ALARKO ATA axial fan unit heaters.
Please, carefully read this manual for that you can operate your
heater with high output, cheap, trouble free and long-term
use. In addition to the operation and maintenance information, the
manual includes a summary of advertising and technical data,
installation, commissioning of the heater.
For more detailed information of the heater, you can consult
the product advertising booklet and ALARKO CARRIER
authorized vendors and services.
Keep this manual for further consulting, as required.
Our authorized vendors and services will inform you about the
utilization and maintenance of the heater, after they mount and
operate your unit. You can ask repeatedly the issues that are not
well-understood.
Our experts shall be pleased to answer your questions.
5

6
Guarantee and Service
In the terms of obeying the instructions, warnings, points in this
manual and the standards in charge (EN norms and directives
must be applied if mentioned standards are not in use) heater is
under 2 (two) years guarantee. Alarko Carrier is responsible for
repairing or renewing if the following conditions are available.
Guarantee Document must be filled by the franchiser that you have
bought the heater and must be send to Alarko Carrier.
Assembling and installing faults and problems, problems that will
be occured because of wrong upkeeping and working are not under
guarantee. Problems related to lime coating or/and any other mate-
rials coating and corrosion on the heat transfer units of the heater
are not under guarantee conditions.
Minimum life of these kind of products is mentioned as 10 (ten)
years by the minister of industry and commerce. Manufacturer and
sales companies are to supply all spare parts and services to the
clients in this period.
The problems happened by the following mentioned issues are out
of guarantee conditions:
- Heater without guarantee document.
- Heater fixed,repaired or adjusted by unauthorized services.
- Heaters with wrong type selection, wrong installing and assemb-
ling.
- Heaters used wrong conditions and out of aim.
- Problems occured while transportation, stocking or problem oc-
cured under atmospheric conditions.
- The problems occured by physical or chemical effects.
- Wrong installation or connection to water plumbing systems.
- The problems occured by scratching,touching to control and safety
systems of the heater.

7
General Characteristics
The objective of the apparatus is to heat the ambient air using water
and vapor. The apparatus consists of three main parts; (Figure 1)
1. Coil
2. Fan
3. Air Directors
Coil: Hot water or vapor circulates in the coil. It consists of
aluminum or steel fins arranged on copper or steel pipe in order
to increase the heat transfer surface.
Fan and Motor: It is located behind the coil. As the fan
operates, the heat in the coil is more rapidly transferred into
ambient.
Air Directors: It helps direction of the air blown by the fan.
Figure 1: Main parts of the heater
Air Directors
Hot Air
Output
Axial Fan
and Motor
Cold Air
Input

8
Dimensions
A
B
E
DF
C
G
R
r
CD FG
Boyutlar
(mm)
EAB
560 579
490 529
415
415
730 280 610
655 280 545
615 260 530 460 432 400
560 260 465 410 432 380
500 240 405 360 330 360
320 330 360440 240 350
720
640
600
550
490
440
Other Technical Characteristics
Elektrik
220V, 1faz
Ak›m (A)Güç (W)
4,60 38 75 245
3,80 32 65 160
2,30 26 70 160
1,80 21 65 130
50 80
1,10 17 60 100
ATA 28
ATA 36
Çal›flma
A¤›rl›¤›
(kg)
Ses
Seviyesi
dB(A)
ATA 6
ATA 12
ATA 17
ATA 22
0,85 16
Batarya
Su Hacmi
0,80
1,10
0,25
0,32
0,57
0,72
(lt)
ATA 28
ATA 36
ATA 6
ATA 12
ATA 17
ATA 22
Dimensions
Dimensions
(mm)
(mm)
Coil
Coil
Water Vol.
Water Vol.
Sound
Sound
Level
Level
Electricity 220V, 1
phase
Working
Weight
Power (W) Current (a)

9
Air Distribution Distances
Yüksek 900 7
5
3
7
5
4
9
7
4
10
8
6
11
9
7
10
7
5
Orta 600
Düflük 400
Yüksek 1800
Orta 1400
Düflük 1000
Yüksek 2600
Orta 2000
Düflük 1400
Yüksek 3600
Orta 2900
Düflük 2200
Yüksek 4000
Orta 3000
Düflük 2000
Yüksek 5200
Orta 4000
Düflük 2800
ATA 22
ATA 28
ATA 36
Üfleme Uzakl›klar›
(metre)
ATA 6
ATA 12
ATA 17
Fan
Kademe Üfleme Debisi
(m3/saat)
Not: Üfleme uzakl›klar› fanla düz aç›da, ortam s›cakl›¤›n›n 18°C oldu¤u
koflullarda 0,2 metre/saniye'lik hava h›z›n›n ölçüldü¤ü mesafelerdir.
Coil Water Pressure Drop Graphic
Air Flow
(m3/hour)
Air Throw
(meter)
Fan
Speed
Not: Throwing distances are at straight angle with the fan and at the distance
where the 0,2 meter/second air velocity is measured at the ambient temperature
of 18°C.
High
Medium
Low
High
Medium
Low
High
Medium
Low
High
Medium
Low
High
Medium
Low
High
Medium
Low
Ç
0,20
0,15
0,25
Su Debisi (m
3
/saat)
Bas›nç Kayb› (Bar)
15
20
Bas›nç Kayb› (Kpa)
0,10
0,09
0,08
0,07
0,06
0,05
0,04
0,03
0,02
0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,5 2,0
10
9
8
7
6
5
4
3
2
ATA 6
ATA 12
ATA 17
ATA 28
ATA 22
ATA 36
Water Flow (m3/hour)
Pressure Drop (Bar)
Pressure Drop (Kpa)

10
Installation Rules
Location Selection and Mounting
The heater should be mounted in a closed area where it shall not
be exposed to outer effects like rain, frost. The fan section of the
unit should be accessible.
The wall-mounting or ceiling-mounting of the heater should be
performed in different ways. The examples are illustrated in Figure
2. The hanging legs can be both secured by the client or bought as
ready from Alarko.
Sufficient space should be left between the heater and wall orceiling
for that the air emission can be realized easily and the motor can
be serviced easily as required.
It is at the user’s disposal weather the heater shall be placed on the
brackets or hanged.
Generally, they are hanged. Hanging has two advantageous. 1.
Since the legs are on the apparatus, they are not visible; they do not
destroy the decorative look. 2. When it is placed, there is a possibility
that the cartoons, sags be put between the wall and the heater. But, if
it is hanged, no material can be placed between the wall and heater.
En az 35 cm
En az
35 cm
ekil 2: Apareyin duvara montaj alternatifleri
Apareyin
Oturtulmas
Apareyin
Aslmas
Placing the
heater Hanging the
heater
Min.
35 cm
Figure 2: Wall-mounting alternatives for the apparatus
Min. 35 cm

11
Thus, the possibility of them to block the fan is eliminated.
Water Pipes Installation
Please, find water pipe diameters we suggest in the Table 1.
Inserting valve at water inlets and outlets is advantageous.
These valves can be heat system valves or spherical valves.
Attention should be paid that the water flow ratio allowed by the
valves should be appropriate for the water flow ratio to pass in
the heater.
While the coil water pipe connections are made, attention
should be paid that the pipe connections be loose not to give
way to any force or stress. Use of flexible fixings (if possible) in
pipe connections is advantageo-
us. After the connections are
completed, leak and stress test
should be applied.
Countertightening should be
applied as shown in Figure 3
during the pipe connection. The
inlets and outlets of the heater
are not strong enough to resist
the tightening.
F
C
G
R
r
ATA 28
ATA 36
ATA 6
ATA 12
ATA 17
ATA 22
Table 1
Is›t›c› Ak›flkan Ba¤lant›lar›
Buhar
1/2”
3/4”
3/4”
1”
1”
1 1/4”
1/2”
1/2”
1/2”
3/4”
3/4”
1”
r
(Diflli)
R
(Flanfll›)
DN20
DN25
DN32
DN32
DN32
DN40
R
(Diflli) r
(Diflli)
1/2”
3/4”
3/4”
1”
1”
1 1/4”
S›cak ve K›zg›n Su
Heating Liquid Connections
Steam
(Threaded) (Threaded) (Flanged)(Threaded)
ekil 3: Cihaza boru balants yaplrken
"kontra skma" uygulamas yaplmas
Figure 3: “Counter-tightening” as the pipe connections
are made
Hot Water

12
Figure 4 and 5 illustrates various alternatives for connections.
These illustrations are just suggestions; the installation should be
made by qualified personnel.
ekil 4A: Scak veya kzgn su tesisatna balant
Cihazn ana borulardan aada olduu durum
ekil 4B: Scak veya kzgn su tesisatna balant
Cihazn ana borulardan yukarda olduu durum
Scak/kzgn su gidi borusu
Scak/kzgn su dönü borusu
Vana
Vana
Su Boaltma
Vanas
Hava Tahliye
Vanas (Pürjör)
Vana
Vana
Su Boaltma
Vanas
Scak/kzgn su gidi borusu
Scak/kzgn su dönü borusu
Hot water flow pipe
Hot water return pipe
Figure 4A: Connection to hot water
installation The case of the heater under the
main pipes
Figure 4B: Connection to hot water
installation The case when the heater is above
the main pipes
Hot water flow pipe
Hot water return pipe
Valve
Valve
Water Discharge
Valve
Air Discharge Valve
(Purger)
Valve
Valve
Water Discharge
Valve

13
ekil 5A: Buhar tesisatna balant.
Cihazn kondens borusundan aada olduu durum
Buhar borusu
Kondens borusu
Buhar borusu
Kondens borusu
Buhar Vanas
Vana
Vana
Vana
Pislik
Tutucu
Kondenstop
ekil 5B: Buhar tesisatna balant.
Cihazn kondens borusundan yukarda olduu durum
Buhar Vanas
Kondenstop
Pislik
Tutucu
Valve
Steam Valve
Steam Pipe
Condensation
pipe
Condenstop
Figure 5A: Connection to steam installation.
The case when the heater is lower than the condensation pipe
Figure 5B: Connection to steam installation.
The case when the heater is higher than the condensation pipe
Valve
Steam Valve
Valve
Dirt
Keeper
Steam Pipe
Condensation
pipe
Filter
Condenstop
Filter

14
Electricity:
All electrical connections should be made by a qualified
electrician.
The fan motors of the heater operate with 220 V, 50 Hz power.
Fan motors have their own thermal protections. Thus, there is no
need to install thermal protection. The cables to fans should be
min. 3x1 TTR cable.
The connection diagram is in Figure 6.
Kahverengi
Mavi
Siyah
Sar-Yeil Toprak
Motordan Gelen Kablolar
Kondansatör
Faz Nötr Toprak
ekil 6: Fana dorudan elektrik balants emas
EarthNeutralPhase
Brown
Blue
Black
Yellow-Green Earth
Condensate
Cables from the motor
Figure 6: Direct electric connection to fan
Condensator

15
Trouble-shooting Manual
If the unit does not operate:
Is it plugged?
Is there power in the plug?
Are the fuses OK?
Is there any mains power cut?
Does the propeller turns?
If the unit does not heat enough:
See if the coil surface is dirty or air suction is low.
If it is operated with a thermostat, see if the thermostat is wrongly adjusted.
See if there is any open door or window.
See if there air in water circuit.
There may not be enough hot water in water circuit.
See if the pipes of the heat coil are plugged.
There may be plastic bag, paper etc. stuck on the coil surface.
See if the propeller is dirty or its balance is disordered.
Product Ordering Notation
ATA 36 D S
S (for hot water and max. 2,5 atu steam, stan-
dard copper pipe - aluminum fin)
K (for red-hot water and max. 2,5 -5 atu steam,
thick pipe - aluminum fin)
Ç (for 5 -10 atu steam, steel pipe - steel fin)
D : Wall-mounted
T : Ceiling-mounted
Model
Fan Unit Heater

: GOSB - Gebze Org. San. Bölgesi, Ş. Bilgisu Cad. 41480 Gebze-KOCAELİ
Tel: (0262) 648 60 00 - Fax: (0262) 648 60 08
: Sedat Simavi Sok. No: 48, 06550 Çankaya - ANKARA
Tel: (0312) 409 52 00 - Fax: (0312) 440 79 30
: Şehit Fethibey Cad. No : 55, Kat.13, 35210 Pasaport - İZMİR
Tel: (0232) 483 25 60 - Fax: (0232) 441 55 13
: Ziyapaşa Bulvarı Çelik Ap. No : 25/5-6, 01130 ADANA
Tel: (0322) 457 62 23 - Fax: (0322) 453 05 84
: Metin Kasapoğlu Cad. Küçükkaya Sitesi A Blok No: 1 D. 4, ANTALYA
Tel: (0242) 322 00 29 - Fax: (0242) 322 87 66
İSTANBUL
ANKARA
İZMİR
ADANA
ANTALYA
web: www.alarko-carrier.com.tr
e-posta: info@alarko-carrier.com.tr
MDH: 444 0 128
Table of contents
Popular Heater manuals by other brands

STIEBEL ELTRON
STIEBEL ELTRON CKZ 20 S euro Operating and installation instructions

BVF
BVF REMINA Installation and user manual

Anslut
Anslut 013433 operating instructions

Rointe
Rointe Kyros Instruction manuals

L.B. White
L.B. White I17 Owner's manual and instructions

HIRED-HAND
HIRED-HAND Maywick SUPER-SAVER XL owner's manual

EQUATION
EQUATION YF01-7 Safety instructions

Linea 2000
Linea 2000 Domo DO7350CH Instruction booklet

Truma
Truma Ultraheat S 3004 Operating instructions & installation instructions

Nibe
Nibe ELK 15 Installation and maintenance instructions

Thermor
Thermor Riva 4 mixte Installation and operating manual

Micasa
Micasa MA0136PH instruction manual