SPECIFICATION
OPERATING VOLTAGE: 12 OR 24 VOLTS AC/DC, AUTO VOLTAGE SELECTION
CURRENT DRAW: 155 MA., (SOUNDER OFF), 200 MA., (SOUNDER MAXIMUM VOLUME)
RELAY CONTACT RATING: 1.3 A. @ 30 VOLTS DC OR 24 VOLTS AC
RELAY CONTACT ARRANGEMENT: DOUBLE POLE-DOUBLE THROW, (2 FORM C)
TEMPERATURE: FOR U.L. LISTED INSTALLATIONS +32 F TO +120 F, (0 C TO +49C)
HUMIDITY: 0% TO 93% NON-CONDENSING FOR ULC-S319 INSTALLATIONS, 0% TO 85%
NON-CONDENSING FOR UL-294 LISTED INSTALLATIONS.
REQUEST TO EXIT INPUT: NORMALLY-OPEN DRY CONTACTS
KEYPAD OR CARD READER INPUT: NORMALLY-CLOSED DRY CONTACTS
DOOR POSITION SWITCH INPUT: NORMALLY-OPEN DRY CONTACTS
SIZE: 6.875” L (174.63mm) x 1.875” H (47.63mm) x 2” W (51mm)
MATERIAL: BLACK ANODIZED ALUMINUM AND ABS PLASTIC
WIRING INTERFACE: 14 PIN CONNECTOR WITH 4 FEET OF CABLE
CERTIFICATIONS: UL/CUL 294/S319, FCC PART B
THE SREX-100 HAS A THREE YEAR WARRANTY
PAGE 1
The SREX-100 is an active infrared request to exit sensor for interior applications located
within the protected premise. It is U.L. listed as a request to exit device under the U.L.
UL294 and the CAN/ULC-S319 standard. The SREX-100 is rated a “class 1” as per the CAN/
ULC-S319 standard. The SREX-100 is designed to mount over the door header so that its de-
tection pattern is placed directly over the door handle. When the user reaches for the door
handle the exit device releases allowing the person to exit. The active detection curtain is well
defined to keep the door secure while rejecting parallel traffic and objects placed under it.
IF TECHNICAL ASSISTANCE IS REQUIRED CALL 1 800 645-5538
NOTE:
FOR U.L. LISTED INSTALLATIONS THE SREX-100 SHOULD ONLY BE POWERED BY A U.L. 294
LISTED POWER SUPPLY, AS WELL AS CONNECTED TO A U.L. LISTED ELECTRICAL LOCKING
(EL) DEVICE. FOR CAN/ULC-S319 LISTED INSTALLATIONS THE SREX-100 SHOULD ONLY BE
POWERED BY A ULC--S319 LISTED POWER SUPPLY AS WELL AS CONNECTED TO A ULC-
S319 LISTED ELECTRICAL LOCKING (EL) DEVICE, CARD READER/KEYPAD AND DOOR/REX
SWITCHES.
THE USE OF ANY ADD-ON, EXPANSION, MEMORY OR OTHER MODULE MANUFACTURED OR
SUPPLIED BY THE MANUFACTURER’S REPRESENTATIVE WILL INVALIDATE THE CAN/ULC-
S319 CERTIFICATION.
WHEN USED WITH ELECTRIC STRIKES ON SUPERVISED PORTALS, REQUEST-TO-EXIT DE-
VICES SHALL BY-PASS PORTAL ALERTS CAUSED BY EXITING. WHEN USED WITH ELEC-
TROMAGNETIC LOCKS ON SUPERVISED PORTALS, REQUEST-TO-EXIT DEVICES SHALL
SIGNAL THE ACCESS CONTROL UNIT TO RELEASE THE ELECTROMAGNETIC LOCKS AS
WELL AS TO BYPASS PORTAL ALERTS CAUSED BY EXITING.
TERMINAL AND LEADS COMPLY WITH CSA, C22.1, CANADIAN ELECTRICAL CODE, PART I,
SAFETY STANDARD FOR ELECTRICAL INSTALLATIONS.
FOR U.L. 294 AND NFPA 101 SECTIONS 7.2.6.2.1 WIRE THE LOCKING DEVICE FOR FAIL-SAFE
OPERATION.
CAN/ULC-S319 LIMITS THE RATED OUTPUT OF THE AUDIBLE SIGNAL DEVICE, (STATED AS A
SOUND PRESSURE LEVEL), (SPL), FROM 70 dBA TO A MAXIMUM OF 100 dBA AT 1 METER.
UL-294 LIMITS THE RATED OUTPUT OF THE AUDIBLE SIGNAL TO A MINIMUM OF 85 dBA AT
10 FEET.
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO
THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTER-
FERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED THAT MAY
CAUSE UNDESIRED OPERATION.