Alber Cellcorder CRT-300 User manual

Albér CRT- 300 Cellcorder®Quick Start
On - Press power key.
Off - Press and hold the
green power key until
“Release power button”
appears.
Connect the voltage
probes to the CRT-300.
Select Mode|Voltage.
Connect the resistance
leads to the CRT, but not
to the cell under test.
Select Mode|Resistance.
If “Stored in Memory”
appears, either Retest or
change cell number.
If “Resume Testing”
appears, place voltage
probes on the cell.
When the CRT beeps,
remove the probes. The
cell number advances
automatically.
Save the readings when
done.
Specify the number of
intercell connections per
cell or select Combined
or Computed.
Select the amp hour rate
of the cell being tested.
At “Ready to Test,”
connect the three clip
resistance probes to the
cell and intercell under
test. If testing cells with
single intercell
connectors, connect the
probes as follows:
1. Red clip to the
positive post of the cell
being tested.
Power On / Off
Voltage Readings
Resistance Readings
2. Red/black clip to the
negative post of the cell
being tested.
3. Black clip to the
positive post of the next
cell.
Note: If testing cells that
require two to four
intercell measurements,
refer to Application Note
CC-002 in the manual.
Press the Test key. After
the cell or intercell
reading appears, move
probes to the next cell or
intercell. Press Test to
continue.
If the cell requires two or
more intercell resistance
readings, move the
red/black and black
leads across the next
intercell connection.
Press Test to continue.
The cell number
advances automatically.
990 South Rogers Circle, Ste. 11
Boca Raton, FL 33487
(561) 997-2299
When done, save the
readings as described
on the other side.
001
2.250
001
0.000 ©2004
4200-042R1.0
Specific Gravity and Temperature Readings
To transfer SG and
temperature readings to
the CRT-300 via IR
(infrared), first choose a
file to add the readings
to by selecting Load|
Access Cell Data.
Albér CRT- 300 Cellcorder®Quick Start
Save the Readings to
Memory Card
To save readings, insert
a memory card into the
CRT. Press Shift then
Save.
Type a file name (8 char
max, no spaces).
Press the Save (F2) key.
After the file is saved,
you can copy it from the
memory card to a PC.
Note: Saving readings
does not delete them
from the CRT. The
memory card does not
support subdirectories.
Highlight a CDF file
name and press Select.
Select Mode|SG/Temp,
then press Import.
Power on the hydro-
meter data module and
select a string (A to H)
on the module.
Align the CRT and data
module IR ports. Press
Continue on the CRT.
When the CRT displays
SG and Temp for Cell
001, upload is done.
On the CRT, press
Cancel then Back to
display the main menu.
Save the file.
A site setup lets you record details for a particular
location and use the same information for future
testing. You may select a site before testing cell
voltage or resistance, but this is not required. To
access sites, insert the memory card then select
Load|Access Setup Data. If no sites exist, the “New
Site” screen appears. Press the arrows to view sites.
To select a site before testing, select Load|Access
Setup Data. Press the arrows to step to a site, then
press Select. If “Active Site” displays the correct site
name, press Continue to return to the main menu.
Working with Cellcorder Sites Thresholds
To set up CRT (not site
file) thresholds, select
Setup|Threshold. Select
a parameter (voltage,
etc.). Press the arrows
to change values, then
press Accept.
Thresholds changed
here override those
loaded from a site.
Thresholds remain in
CRT memory until reset
or a new site is loaded.
Out-of-tolerance
readings are indicated
by two beeps or reverse
video.
Don’t insert / remove the
memory card when the
Smart Media LED is lit.
Doing It Right

Other manuals for Cellcorder CRT-300

1

Other Alber Test Equipment manuals

Alber Cellcorder CRT-300 User manual

Alber

Alber Cellcorder CRT-300 User manual

Alber Cellcorder CRT-400 User manual

Alber

Alber Cellcorder CRT-400 User manual

Popular Test Equipment manuals by other brands

Spinner SmartLoad 50 kW product manual

Spinner

Spinner SmartLoad 50 kW product manual

McKesson Consult user manual

McKesson

McKesson Consult user manual

Fluke 6109A Operator's manual

Fluke

Fluke 6109A Operator's manual

Hasco Z141/3 operating instructions

Hasco

Hasco Z141/3 operating instructions

Lifeloc FC20BT Operator's manual

Lifeloc

Lifeloc FC20BT Operator's manual

multicomp pro MP720780 quick guide

multicomp pro

multicomp pro MP720780 quick guide

LION ATTACK user manual

LION

LION ATTACK user manual

IDEAL 61-517 GFCI Operation and safety manual

IDEAL

IDEAL 61-517 GFCI Operation and safety manual

abi SYSTEM 8 instruction manual

abi

abi SYSTEM 8 instruction manual

sauter HN-D instruction manual

sauter

sauter HN-D instruction manual

sauter TVO-N instruction manual

sauter

sauter TVO-N instruction manual

Agilent Technologies N9360A Programming manual

Agilent Technologies

Agilent Technologies N9360A Programming manual

Spirent Tech-X Flex user guide

Spirent

Spirent Tech-X Flex user guide

ProsKit NT-309 Operation manual

ProsKit

ProsKit NT-309 Operation manual

Swagelok M200 User instruction

Swagelok

Swagelok M200 User instruction

GW Instek PEL-3000 Series user manual

GW Instek

GW Instek PEL-3000 Series user manual

Sperry instruments ST6401 operating instructions

Sperry instruments

Sperry instruments ST6401 operating instructions

ABB SACE PR010/T instructions

ABB

ABB SACE PR010/T instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.