manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. albinus
  6. •
  7. Water System
  8. •
  9. albinus WPS 4.0 User manual

albinus WPS 4.0 User manual

Albinus
Water Pressure System WPS 4.0 12V / 24V,
WPS 5.3 12V / 24V
Albinus 500-series 5-chamber diaphragm Water Pressure System pumps for providing
pressurized water on demand! Our WPS pumps supply continuous, pulsation-free,
pressurized ow of both hot and cold water to faucets, shower heads and more.
• Easy to install
• Integrated extra heavy duty sealed pressure switch
• Smooth & Pulsation-free ow
• Quiet operation
• Serves up to 5 outlets (WPS 4.0) or 6 outlets (WPS 5.3)
• Self-priming up to 2.5 m (8.2 ft)
• Quick disconnect ports
• Connection with ½" and ¾" hose
• Click-on 40 µm mesh strainer included
• Manufactured according to CE standard; EN55014-1, ISO 88461 & ISO10133.
Under approval
part no. 02-02-006 Water Pressure Pump WPS 4.0 15 L/min (4.0 GPM) 12V 10A ½" and ¾" hose
part no. 02-02-007 Water Pressure Pump WPS 4.0 15 L/min (4.0 GPM) 24V 5A ½" and ¾" hose
part no. 02-02-008 Water Pressure Pump WPS 5.3 20 L/min (5.3 GPM) 12V 15A ½" and ¾" hose
part no. 02-02-009 Water Pressure Pump WPS 5.3 20 L/min (5.3 GPM) 24V 8A ½" and ¾" hose
Operation:
When water is tapped from the system, for example from a faucet or a shower head,
the pressure in the water supply system will drop. At the factory-set cut-in pressure of
1.7bar (25psi) the WPS pump's integrated pressure switch will automatically turn on
the pump to boost the water system pressure, providing continuous, pulsation free
ow. The WPS pump automatically turns o when the pre-set cut-o pressure of 2.8 bar
(40psi) is reached.
A check valve on the outlet maintains the pressure in the water system between uses
so that pressurized water is always available. For the optimum Water Pressure System:
install the WPS pump together with Albinus Accumulator Tank 02-66-022.
Technical Specications:
Body: Nylon/Polypropylene
Valve housing: Polypropylene/Polyamide
Valves: Santoprene/EPDM
Diaphragm: Santoprene
Connection: ½" and ¾" hose
Inlet strainer: 40µm mesh, included
Max. liquid temperature: Max +50°C/+120°F
Fasteners: Stainless steel
Max. suction lift: WPS 4.0 – 2m/6.5ft
WPS 5.3 – 2.5m/8.2ft
Cut in pressure: 1.7bar (25psi)
Cut-o pressure: 2.8bar (40psi)
Duty cycle: Intermittent, max 20 min
Motor: WPS 4.0 – 100W
WPS 5.3 – 150W
12/24V DC with built in thermal protection
Manufactured according to CE standard;
EN55014-1, ISO 88461 & ISO10133. Under approval
Installation:
The pump must be mounted in a dry, ventilated location and must not be submerged.
Selection of a cool ventilated location will generally extend pump motor life. Mount the
pump horizontally with space for maintenance. If you choose to mount the pump
vertically, mount with the motor pointing upwards.
Mark screw positions and drill pilot holes (see drilling template). Mount the pump
using stainless steel screws and with the accompanying washers; do not over tighten
the screws so that the vibration dampening of the composite base is not compromised.
For connecting to the water piping, it is recommended to use reinforced, high pressure
exible tubing. If rigid piping is used for the connection, a length of exible tubing
(225mm/9 inches minimum) should be installed between the pump and the rigid
pipe. This will stop noise and/or damage caused by any vibrations transmitted to rigid
pipe. Use stainless steel hose clamps to secure tubing to the quick disconnect ttings
and any other hose barbs present in the system.
NOTE:
The included strainer must be installed at the pump intake, to prevent debris from
entering pump, causing damage and interfering with the proper functioning of valves.
Electrical connections:
The pump must be installed according to SS-EN ISO 10133 (Small craft – Electrical
system – Extra low voltage DC installation for continuous current). Note: The fuse
must be ignition protected. The motor is equipped with built-in thermal protection to
prevent the motor from overheating. The protection is automatically reset when the
motor has cooled. If the pump is connected with a separate earth lead, connect it to
metallic part of the motor. See the wiring diagram for correct installation. In keeping
with standard electrical nomenclature, the Negative wire must be black and the Earth
lead (if used) should be yellow/green. Choose wire size in accordance with total wire
length.
+–
Black –
Red +
Fuse
Earth
Inlet
Battery
12 V / 24 V
Discharge
Flexible
hose
Accumulator
Tank
Flexible
hose
Connect black wire to negative (–) terminal of battery. The red wire should run to the
positive (+) terminal of battery, with a properly sized fuse must be placed between the
battery's positive terminal (+) and the pump. Other electrical devices, such as switches
or circuit breaker, must be installed between the pump and the positive (+) lead on
the battery (on the red wire). Use proper wire size as determined by wire table below.
Wiring must comply with applicable electrical standards.
All wire connections must be sealed with a marine sealant. Note!: Before the
installation of electrical control systems, check that the capacity of the equipment to
be used is of sucient rating to accept the amperage draw of the motor. Low voltage
will cause the motor to overheat.
WPS 4.0
Wire size
(based on 3%
voltage drop)
Max wire length (total
distance from the battery to
the pump and back to the
battery)
12V 24V
2.5mm² (14ga) 7 m (23') 30 m (98.4')
4 mm² (12ga) 11 m (36') 49 m (161')
6mm² (10ga) 16 m (52.5') 73 m (240')
10mm² (6ga) 27 m (88.6') 122 m (400')
WPS 5.3
Wire size
(based on 3%
voltage drop)
Max wire length (total
distance from the battery to
the pump and back to the
battery)
12V 24V
2.5mm² (14ga) 5 m (16') 22 m (72.2')
4 mm² (12ga) 8 m (26') 34 m (111')
6mm² (10ga) 12 m (39.4') 52 m (170')
10mm² (6ga) 20 m (65.6') 86 m (282.2')
16mm² (4ga) 31 m (102') 138 m (452.8')
Start-up procedure
After installing the pump, initiate the water system as follows:
1. Fill the water tank
2. Open one tap fully
3. Turn on the pump
4. Close the tap once the water begins owing
5. Open each additional tap until all air has been purged from system
6. The pump will shut o after taps are closed and pressure builds to the pre-set cut-
o pressure of the integrated pressure switch
Maintenance:
Periodically sanitize the system as follows:
1. Fill the water tank with a solution of household bleach and potable water – 1 ml
(.03oz.) bleach/1 L (33 oz.) water.
2. Open all faucets and let run until owing water smells of bleach
3. Close all faucets.
4. Drain the bleach/solution from the tank.
5. Rell the water tank with potable water.
6. Open all of the faucets and let the water run until bleach has been emptied from
the system.
Winterizing
If water is not drained from the system at freezing ambient temperatures, damage will
occur to the water pipes and in the pump. To prevent this follow these instructions:
1. Drain the water storage tank.
2. Open all taps.
3. Run the pump until the remaining water is expelled from the system.
4. Disconnect the inlet and outlet tubing.
5. Run the pump briey to conrm that all water has been expelled.
6. Switch o the electrical power to the pump.
7. Keep the taps open and the pump ttings disconnected until temperatures are
above freezing again.
8. To re-instate the pump, follow the directions under "Start up procedure"
Never start a frozen pump. Even when drained it might contain a small amount of ice
that will lock the pump.
wiring diagram
Self-priming
The pump is self-priming up to 2m (6.5ft) for WPS 4.0 and 2.5m (8.2ft) WPS 5.3. The
inlet pipe must be airtight to ensure self-priming.
Dry running
Pump will not be damaged by shorter periods of dry running. It will, however,
unnecessarily reduce your battery power.
Temperature
Max liquid temperature: +50°C/+120°F
Max ambient temperature: +60°C/+140°F
Trouble shooting
Pump does not run? Check the following:
A. Fuse blown? Motor overheated? Allow motor to cool down before restarting.
B. Battery fully charged? Check all wiring.
C. Faulty pressure switch? Replace switch.
D. Faulty motor? Replace pump.
E. Frozen pump/motor? Thaw the pump and system and check for ice damage
Pump does not prime? Check the following:
A. Empty water tank?
B. Debris under the valves? Gently ush the valves in direction of ow with tap
water.
C. Perforated diaphragm? Replace diaphragm kit.
D. Leakage on inlet side of pump? Check tightness of hose connections at pump,
lter and tank
E. Check inlet and outlet piping for restrictions.
Pump cycles on and o rapidly when a tap is opened? Check the following:
A. Restriction / too high pressure on outlet side of pump? Outlet tubing is too
small; must be same diameter as outlet connection.
Pump cycles on and o rapidly when no tap is open? Check the following:
A. Leakage on outlet side of pump? Tighten connections and check hose for
possible damage.
Pump continues running after tap is closed? Check the following:
A. Leakage on inlet or outlet side of pump? Tighten connections and check hoses
for possible damage.
B. Perforated diaphragm? Replace diaphragm kit.
C. Empty water tank?
D. Faulty pressure switch? Replace switch.
E. Low voltage to pump? Charge / replace battery.
Low ow/ pressure? Check the following:
A. Leakage on inlet or outlet side of pump? Tighten connections and check hoses
for possible damage.
B. Perforated diaphragm? Replace diaphragm kit.
C. Faulty motor? Replace pump.
D. Debris under the valves? Gently ush the valves in direction of ow with tap
water.
Pump is excessively noisy? Check the following:
A. Pump connected directly to rigid piping? Install exible pipe according to
instructions under “Installation”
B. Pump head or mount loose on motor? Tighten screws.
C. Pump mounting too rigid? Use exible tubing on the inlet and outlet
connections, make sure you are using the provided composite base
D. Faulty motor? Replace pump.
Pump performance WPS 4.0 and WPS 5.3
WPS 4.0
Pressure Flow
L/min GPM
Amperage
12V
Amperage
24VBar kpa psi
0 0 0 14.6 3.9 3.3 1.7
0.8 80 12 12.7 3.4 4.9 2.5
1.6 160 23 11 2.9 6.3 3.2
2.4 240 29 10 2.6 7.7 3.8
2.8 280 41 9.5 2.5 8.4 4.1
Recommended Fuse 10A 5A
WPS 4.0 at 13.6V & 27.2V (battery charge)
Pressure Flow
L/min GPM
Amperage
13.6V
Amperage
27.2VBar kpa psi
0 0 0 16 4.2 3.8A 1.8A
WPS 5.3
Pressure Flow
L/min GPM
Amperage
Bar kpa psi 12V 24V
0 0 0 19.6 5.2 4.9 2.6
0.8 80 12 17.1 4.5 7 3.5
1.6 160 23 15 4 8.2 4.2
2.4 240 29 13.3 3.5 11.3 5
2.8 280 41 12.5 3.3 12.2 5.2
Recommended Fuse 15 A 8 A
WPS 5.3 at 13.6V & 27.2V (battery charge)
Pressure Flow
L/min GPM
Amperage
Bar kpa psi 13.6V 27.2V
0 0 0 21.2 5.6 7.5A 3A
Dimensions and weight
C
F
H4 x Ø 4.0 mm/0.2"
J
GE
A
B
D
WARNING
WARNING
WARNING
WARNING
Keep all wire connections above the highest water level. Wires must be joined with butt
connectors and a marine grade sealant to prevent wire corrosion.
Disconnect power from the system before working on the unit to avoid personal injury,
damage to the surrounding environment and/or damage to the unit.
Always install proper fuse size to prevent damage to product should a short occur. Failure
to install proper fuse could increase risk of pump malfunction potentially resulting in
personal injury and/or re hazard.
Do not pump gasoline, solvents, thinners, highly concentrated or organic acids. Use with
hazardous, caustic, or corrosive material could result in damage to the pump and the
surrounding environment, possible exposure to hazardous substances and injury.
WARRANTY
Two year limited warranty
Waste handling &
material recycling
At the product's end of
life, please dispose of
the product according
to applicable law. Where
applicable, please
disassemble the product
and recycle the parts
according to material.
Dimension mm inch
A215 8.5
B112 4.4
C63 2.49
D63.4 2.5
E82 3.2
F122 4.8
G20 0.8
H108 4.3
J70 2.75
WPS 4.0 2.5 kg / 5.5 lbs
WPS 5.3 2.5 kg / 5.5 lbs
Albin Group AB
Kämpevägen 17
55302 Jönköping, Sweden
[email protected]
www.albin.group

This manual suits for next models

5

Popular Water System manuals by other brands

Kärcher WATERCLEAN 600 CD Service handbook

Kärcher

Kärcher WATERCLEAN 600 CD Service handbook

Biontech BTH-101T user guide

Biontech

Biontech BTH-101T user guide

Puretec SH SERIES user guide

Puretec

Puretec SH SERIES user guide

BIO-MICROBICS FAST owner's manual

BIO-MICROBICS

BIO-MICROBICS FAST owner's manual

Wesco ES50-E-FLUSH instructions

Wesco

Wesco ES50-E-FLUSH instructions

BIO-MICROBICS BioBarrier Service manual

BIO-MICROBICS

BIO-MICROBICS BioBarrier Service manual

AquaticLife RO Buddie 75 GPD Installation, operation, maintenance guide

AquaticLife

AquaticLife RO Buddie 75 GPD Installation, operation, maintenance guide

SunEarth SolaRay 2 Installation, operation and maintenance manual

SunEarth

SunEarth SolaRay 2 Installation, operation and maintenance manual

Angel Water PurASure ARO - 50 manual

Angel Water

Angel Water PurASure ARO - 50 manual

Kessel Aqualift S LW 1000 installation instructions

Kessel

Kessel Aqualift S LW 1000 installation instructions

AquaLiv FS300 instructions

AquaLiv

AquaLiv FS300 instructions

Hellenbrand 109248 owner's manual

Hellenbrand

Hellenbrand 109248 owner's manual

FLOWTECH flowvess Operation and maintenance manual

FLOWTECH

FLOWTECH flowvess Operation and maintenance manual

Kemper KHS-HS2 689 03 001 Installation and operating instruction

Kemper

Kemper KHS-HS2 689 03 001 Installation and operating instruction

ENERGY KINETICS EK-Pak Owners and installation manual

ENERGY KINETICS

ENERGY KINETICS EK-Pak Owners and installation manual

PolyJohn FWD3-1000 manual

PolyJohn

PolyJohn FWD3-1000 manual

Sime NATURAL 300/5.84 EV Installation and service instructions

Sime

Sime NATURAL 300/5.84 EV Installation and service instructions

Vetus HF1208 Operation manual and installation instructions

Vetus

Vetus HF1208 Operation manual and installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.