ALCO 4000 Series User manual


CONTENTS
CONTROL PANEL DESCRIPTION
- Access Levels
- CONDITIONS
- TROUBLE SHOOTING GUIDE
- GLOSSARY AND REFRENCES
Access Levels 1
Access Levels 2
Access Levels 3
Alarm Condition
Actions During The Alram Condition
Actions During The Fault Condition
Fault Condition
Disable Condition
In Activity Timeouts
Test Condition
Reset Passcodes to Factory
Default Settings

Building Name
Building Address
Installation Company
Company Contact
Date Installed
Service Company
Contact
intelligent solutions
intelligent solutions

Indicates the alarm condition. Alarm zone information will also be displayed on the ZONE indicators.
Indicates the fault condition. Fault information will be displayed on the zone indicators or in the
Indicates at least one function (eg detection or auxiliary outputs) is disabled. Indicates the test condition.
Indicates the control and indicating equipment is active. The LED will repeatedly flash twice followed by a
pause, when the control and indicating equipment is in the Access Level 2. The LED will repeatedly flash
three time followed by a pause, when the control and indicating equipment is in the Access Level 3.
STATUS
FIRE
ZONES
FIRE
FAULTS
MAIN SUPPLY
BATTERY
AUX SUPPLY
EARTH
ALARM
SELECTED
ZONES
DELAYS
ACTIVE
ALARM
ZONES
AUXILIARY
OUTPUTS
FAULT
DISABLE
Indicates when a zone is in the test condition, the fault condition or the disabled condition.
Disables and enables relay outputs. When the indicator is active, the output devices are disabled.
faults area of the control panel, depending on the source of the fault.
TEST
SUPPLY
TEST FAULT
DISABLED
Indicates the alarm condition within a specific detection zone.
Indicates the mains supply is unavailable or less than the minimum required voltage.
Indicates the secondary (battery) supply or battery charger is faulty.
Indicates a fault in the auxiliary DC output.
Indicates an earth fault is detected in the fire detection and alarm system transmission path wiring.
A fault (including an open-or short-circuit in the transmission path) in an alarm zone circuit is
indicated by the FAULT LED in the STATUS area being on and the ALARM ZONE LED flashing.
DISABLEMENT
Selects specific detection zones for disablement. Used in conjunction with zone buttons and
SILENCE/ACTIVATE ALARMS button. The indicator is active when disablements are active.
Disables and enables delays of configured alarm devices. When the indicator is on, the delay is
active. Pressing the DELAYS ACTIVE button over-rides the delays and causes immediate actions.
Disables and enables alarm devices. When the indicator is active, the alarm devices are disabled.
intelligent solutions
intelligent solutions

CONTROL
ACKNOWLDGE
RESET
INDICATOR TEST
SILENCE
ACTIVATE
ALARMS
Activates audio/visual alarm devices. The LED illuminates when the alarm
devices are active.
Acknowledges a new alarm or fault event and silences the internal sounder.
The LED will illuminate when a new condition occurs.
Resets the fire detection and alarm system.
Illuminates all LEDs and activates the internal sounder.
intelligent solutions
intelligent solutions

Three access levels are used to operate or configure the control and indicating equipment.
Access Level 1 provides open access to perform the following functions:
- Acknowledge a new event and silence the internal sounder.
- Override any active delays in the alarm condition.
- Perform the indicator test.
- Place the panel into Access Level 2 or Access Level 3.
To enter the access level 2 passcode, take the following actions:
- Press and hold the ACKNOWLEDGE button for 10 seconds. The SUPPLY LED will flash rapidly.
- Enter the access level 2 passcode using the buttons numbered 1 ~ 8.
Each button press will cause the following indicator to light:
Access Level 2 provides access to functions for authorized users:
- Acknowledge a new event and silence the internal sounder.
- Override any active delays.
- Perform the indicator test.
- Silence and re-active alarms (including for a building evacuation).
- Reset the fire detection and alarm system.
- Disable or enable the following:
- Zones
- Alarms
- Auxiliary outputs
- Active delays (if configured).
When there are no new events to acknowledge, pressing and holding the ACKNOWLEDGE button for 3 seconds
will cause the SUPPLY LED to flash rapidly and permit the entry of the Access Level 2 passcode.
The factory default access level 2 passcode is 6688.
First Button Press Zone 1 Test Fault Disabled
Zone 2 Test Fault Disabled
Zone 3 Test Fault Disabled
Zone 4 Test Fault Disabled
Second Button Press
Third Button Press
Forth Button Press
intelligent solutions
intelligent solutions

First button press Zone 1 TEST FAULT DISABLED
Zone 2 TEST FAULT DISABLED
Zone 3 TEST FAULT DISABLED
Zone 4 TEST FAULT DISABLED
Second button press
Third button press
Forth button press
- Press ACKNOWLEDGE button to confirm the passcode
(Note) The ACKNOWLEDGE LED does not flash during this process.
If the passcode is correct:
The Access level 2 passcode may be changed from the factory default setting. The access Level 2 passcode cannot
be the same as the access Level 3 passcode.
- Enter access level 3.
- Press and hold the ACKNOWLEDGE button for 10 seconds. The supply led will flash rapidly.
- Press 2. The ACKNOWLEDGE LED and the DELAYS ACTIVE LED will both flash.
- Press ACKNOWLEDGE button. The ACKNOWLEDGE LED will be off and the DELAYS
ACTIVE LED will illuminate.
- Enter the new 4-digit access level 2 passcode using the buttons numbered 1 ~ 8. Each
button press will cause the following indicators to light:
- The internal sounder will give a double short beep.
- The SUPPLY LED will flash twice, pause, then repeat.If the passcode is incorrect:
- The internal sounder will give a single long beep.
If an Alarm Condition or Fault Condition has occurred, the conditions must be acknowledged before entering
Access Level 2.
- The Zone indicators will turn off.
- A new passcode can be entered
To exit Access Level 2, press RESET.
To change the passcode, take the following actions.
- Press ACKNOWLEDGE button to confirm the passcode.
(Note) The ACKNOWLEDGE LED does not flash during this process unless more than 4 passcode numbers are
input.
- Repeat Steps 5 and 6 to confirm the passcode. The internal sounder will give a double short beep. Passcode is
now changed.
- The internal sounder will give a single long beep.
- The zone indicators will turn off.
- A new passcode can be entered.
If the two passcodes entered are different:
intelligent solutions
intelligent solutions

First button press Zone 1 TEST FAULT DISABLED
Zone 2 TEST FAULT DISABLED
Zone 3 TEST FAULT DISABLED
Zone 4 TEST FAULT DISABLED
Second button press
Third button press
Forth button press
Access Level 3 is used to configure the control and indicating equipment and accesses the following functions.
To enter the access level 3 passcode, take the following actions:
- Press and hold the ACKNOWLEDGE button for 10 seconds. The SUPPLY LED will flash rapidly.
- Enter the access level 3 passcode using the buttons numbered 1 ~ 8.
Each button press will cause the following indicator to light:
- Configuration of co-incidence detection
- Setting delay timer
- System Test
- Setting delays
Changes made at Access Level 3 affect the factory default settings and the operation of the system.
Changes should only be made by qualified personnel who are fully aware of the effects.
- Change access level passcodes.
- Reset to factory default settings.
When there are no new events to acknowledge, pressing and holding the ACKNOWLEDGE button for
10 seconds will cause the SUPPLY LED to flash rapidly and permit the entry of the access level 3 passcode.
The factory default access level 3 passcode is 8765.
- If a fire condition or fault condition has occurred, the conditions must be acknowledge before entering
access level 3.
- If a fire condition or fault condition occurs when in access level 3, the control and indicating equipment
will automatically revert to access level 2.
- Press ACKNOWLEDGE button to confirm the passcode
(Note) The ACKNOWLEDGE LED does not flash during this process.
- The internal sounder will give a double short beep.
- The SUPPLY LED will flash three times, pause, then repeat.
If the passcode is correct:
- The internal sounder will give a single long beep.
- The zone indicators will turn off.
- A new passcode can be entered.
If the passcode is incorrect:
intelligent solutions
intelligent solutions

If the CFS-FAP is reset to the factory default settings, all configuration settings will be lost.
The default settings for the CFS-FAP are as follows:
To reset the CFS-FAP to the factory default settings, including the access level passcodes, take the following actions:
The access level 3 passcode may be changed from the factory default setting. The access level 3 passcode
cannot be the same as the access level 2 passcode.
To change the passcode, take the following actions:
- Enter access level 3.
- Press and hold the ACKNOWLEDGE button for 10 seconds. The SUPPLY LED will flash rapidly.
- Press 3. The ACKNOWLEDGE LED and the alarm zones led will both flash.
- Press ACKNOWLEDGE button. The ACKNOWLEDGE LED will be off and the alarm zones led
will illuminate.
- Enter the new 4-digit access level 3 passcode using the buttons number 1 ~ 8.
Each button press will cause the following indicators to light:
- Press ACKNOWLEDGE button to confirm the passcode.
(Note) The ACKNOWLEDGE LED does not flash during this process unless more than 4
passcode numbers are input.
- Repeat steps 5 and 6 to confirm the passcode. The internal sounder will give a double
short beep. Passcode is now changed.
If the two passcodes entered are different:
- The internal sounder will give a single long beep.
- The zone indicators will turn off.
- A new passcode can be entered.
- Detection zones are latching.
- Delay timers are disabled.
- Zone dependency (coincidence detection) is disabled.
- Access level 2 passcode is set to 6688.
- Access level 3 passcode is set to 8765.
- In access level 1, press and hold RESET. After 10 s, SUPPLY LED will flash rapidly.
- While holding RESET button, enter 1, then 2, then 3, then 4. The relevant LEDs for
buttons 1, 2, 3 and 4 will illuminate. The ACKNOWLEDGE LED will flash.
- Press ACKNOWLEDGE button to confirm.
First button press Zone 1 TEST FAULT DISABLED
Zone 2 TEST FAULT DISABLED
Zone 3 TEST FAULT DISABLED
Zone 4 TEST FAULT DISABLED
Second button press
Third button press
Forth button press
intelligent solutions
intelligent solutions

When the control and indicating equipment enters the alarm condition, the alarm sounders and output modules
will operate according to their configuration programming.
The ZONES FIRE LED(s)
will flash.
The FIRE LED will flash. The internal
sounder will operate.
The
ACKNOWLEDGED
LED will flash.
The ACTIVATE/SILENCE ALARMS
LED will illuminate
After the control and indicating equipment enters the alarm condition, take the following actions.
- Press ACKNOWLEDGE to acknowledge the alarm and silence the internal sounder.
The FIRE and relevant detection zone LEDs will be on steady, and the internal sounder
will silence.
- Investigate the source of the alarm condition.
- If the building or area needs to be evacuated, once the area(s) is cleared, silence the
alarm devices by pressing the SILENCE/ACTIVATE ALARMS button. Alarm devices
can be re-started by pressing the button a second time.
DO NOT RESET THE CONTROL AND INDICATING EQUIPMENT UNTIL THE SOURCE OF THE ALARM
HAS BEEN DETERMINED.
intelligent solutions
intelligent solutions
CONDITIONS

- If the cause of the alarm condition was not a fire, enter access level 2 and press the RESET
button to reset the fire detection and alarm system.
- If the cause of the alarm condition has not cleared, the control and indicating equipment will
re-enter the alarm condition. If this occurrence repeats, disable the zone and contact the
service company.
- Enter access level 2.
- Press SILENCE/ACTIVATE ALARMS button. The SILENCE/ACTIVATE ALARMS LED and the
ACKNOWLEDGE LED will flash.
- Press the ACKNOWLEDGE button. The ACKNOWLEDGE LED and the alarm devices will be off.
- To exit to access level 2, press RESET. The ACKNOWLEDGE LED will flash.
- Press the ACKNOWLEDGE button. Check that the ACKNOWLEDGE LED is off.
To reactivate the alarm devices, take the following actions:
- Enter access level 2.
- Press SILENCE/ACTIVATE ALARMS button. The SILENCE/ACTIVATE ALARMS LED and the
ACKNOWLEDGE LED will flash.
- Press the ACKNOWLEDGE button. The ACKNOWLEDGE LED will be off.
The alarm devices will operate and the SILENCE/ACTIVATE ALARMS LED will be on.
- To exit to Access Level 2, press RESET. The ACKNOWLEDGE LED will flash.
- Press the ACKNOWLEDGE button. Check that the ACKNOWLEDGE LED is off.
The audio/visual alarm devices will activate during the alarm condition. If all occupants have
evacuated the building, or the cause of the alarm condition was not a fire, then the alarm
devices (both audible and visual) can be silenced. To silence alarm devices, take the following.
When a fault occurs with a device or within the control and indicating equipment, the control and indicating equipment
will enter the fault condition. In the fault condition, the internal sounder will operate.
If the fault is a Zone
Fault, the Zone LED
will flash.
The fault type will be
displayed as a flashing
LED.
The ACKNOWLEDGED
LED will flash. Pressing
the ACKNOWLEDGE
button will silence the
sounder and cause the
LED to be off.
The FAULT LED will
flash. The internal
sounder will operate.
intelligent solutions
intelligent solutions

- Press ACKNOWLEDGE to acknowledge the fault and silence the internal sounder. The FAULT
LED will be on steady and the sounder will silence.
- Consider any known activities that may be current in the building that is a possible cause of
the fault condition.
- Try to reset the fire detection and alarm system by pressing the RESET button by entering
access level 2 and pressing the RESET button.
- If the cause of the fault condition has not cleared, the control and indicating equipment will
re-enter the fault condition. If the occurrence repeats, contact the service company to investi
gate the source of the fault condition.
After the control and indicating equipment enters the fault condition, take the following actions:
A function may be disabled. The disabled condition is used to:
- Prevent events from within the zone (e.g. Detector Alarm) being actioned by the control and
indicating equipment.
- Actions initiated by the control and indicating equipment from occurring with in the zone
activation of an alarm device
- Signals being sent to auxiliary outputs
To disable pre-configured delays to the alarm condition, take the following actions:
- Enter access level 2.
- Press the SELECTED ZONES button. The SELECTED ZONES LED will flash and the acknowledge
led will flash.
- Press the ACKNOWLEDGE button. SELECTED ZONES LED will be on and the ACKNOWLEDGE
LED will flash.
- Press the SILENCE/ACTIVATE ALARMS button to scroll through the detection zones 1 ~ 8.
button is pressed, the selected zone TEST FAULT DISABLED yellow LED will be on.
- Once the desired Zone LED indicator is on, confirm the selection by pressing the ACKNOWLEDGE
button. The FIRE LED in the selected Zone will be on steady. The ACKNOWLEDGE LED will continue
to flash. This gives the user an option to re-enable the selected zone.
- To exit the disablement selection press the SELECTED ZONES button.
- When the alarm condition is not present, enter access level 2.
- Press the DELAYS ACTIVE button. The DELAYS ACTIVE LED will flash, and the ACKNOWLEDGE
LED will flash.
- Confirm the selection by pressing the ACKNOWLEGE button.
The ACKNOWLEDGE LED will be off and the DELAYS ACTIVE LED will be off.
intelligent solutions
intelligent solutions

- In the alarm condition, delays can be disabled at Access level 1.
- If there is an alarm waiting to be processed when the delays are disabled, the control and indicating
equipment will immediately enter the alarm condition.
- For the delays active disabled function, the zones must first be configured to enable the delay
access level 3.
To disable alarm devices, take the following actions:
- Enter access level 2.
- Press the ALARM ZONES button. The ALARM ZONES LED will flash and the
ACKNOWLEDGE LED will flash.
- Confirm the action by pressing the ACKNOWLEDGE button. The ACKNOWLEDGE
LED will be off. The ALARM ZONES LED will be on.
- To exit the disablement selection press the ALARM ZONES button. The ALARM
ZONES LED will flash and the ACKNOWLEDGE LED will flash.
To disable the auxiliary outputs, take the following actions:
To re-enable a disabled function, follow the steps above and note that the relevant disablement LED indicator is off.
Tests can be conducted by a single person. To enter the test condition and undertake tests of the CFS-FAP and
connected devices, follow these steps:
- Enter access level 1 or access level 2.
- Press the INDICATOR TEST button. The internal sounder will operate. All LED indicators on the control panel and
any connected remote display will be illuminate until the
INDICATOR TEST button is released.
- Enter access level 2.
- Press the AUXILIARY OUTPUTS button. The AUXILIARY OUTPUTS LED will flash and the
ACKNOWLEDGE LED will flash.
- Confirm the action by pressing the ACKNOWLEDGE button. The ACKNOWLEDGE LED will
be off. The AUXILIARY OUTPUTS LED will be on.
- To exit the disablement selection press the AUXILIARY OUTPUTS button. The AUXILIARY
OUTPUTS LED will flash and the ACKNOWLEDGE LED will flash.
- Confirm the action by pressing the ACKNOWLEDGE button. The ACKNOWLEDGE LED will be off.
The AUXILIARY OUTPUTS LED will be off. The control and indicating equipment will remain in Access Level 2.
intelligent solutions
intelligent solutions

To re-enable a disabled function, follow the steps above and note that the relevant disablement LED indicator is off.
Timeouts are set to revert to access level 1 if there is not activity, and for system safety in the event that the system is
left without restoring it to access level 1.
When in Access Level 2:
- Enter Access Level 3.
- Press INDICATOR TEST button. The TEST LED will flash and the ACKNOWLEDGE LED will
flash.
- Press the ACKNOWLEDGE button. The ACKNOWLEDGE LED will be off. The TEST LED in
the STATUS section and the TEST FAULT DISABLED LEDs in the ZONES section will be on.
- Test a device connected to each alarm zone circuit. Upon activation of the device:
The FIRE LED will illuminate for 5 seconds;
The Detector Zone indicator will illuminate for 5 seconds;
Any connected remote display Detection Zone indicator will illuminate for 5 seconds and
The internal sounder, and alarm devices will operate for 10 seconds
Zones will automatically reset after 10 s.
- At the completion of the tests and to exit the Test Condition, press the INDICATOR TEST
button. The TEST LED will flash and the ACKNOWLEDGE LED will flash.
- Press the ACKNOWLEDGE button. The ACKNOWLEDGE LED will be off. The TEST LED in
the STATUS section and the TEST FAULT DISABLED LEDs in the ZONES section will be off.
The control and indicating equipment will remain in access level 3.
- Enable access level passcode: No action for 20 seconds causes return to access level 1.
- Enter access level 2 passcode: No action for 20 seconds causes return to access level 1.
- When performing functions in access level 2, no manual input for 20 seconds causes the
process to be cancelled. The control panel will return to access level 2.
- With no specific function selected, no manual input for 10 seconds causes return to access .
When in Access Level 3:
- Enter Access Level 3 passcode: No action for 20 seconds causes return to access level 1.
- No activity (e.g. a button press) for 20 seconds causes return to access level 1.
- When in device test mode, no activity for 10 seconds causes return to access level 1.
intelligent solutions
intelligent solutions

General Fault Indicator
The FAULT indicator in the STATUS area of the display is always illuminated when ever the
control and indicating equipment is in the fault condition. The General fault indicator is
associated with a specific fault that will be indicated in the ZONES or FAULTS area of
the display.
CONDITION
Zone Fault
Mains
Supply Fault
Baery
Fault
System
Fault
Eah Fault
DESCRIPTION ACTION
Indicates a fault in the alarm zone transmission path
between the control and indicating equipment and
connected devices (eg detectors, manual call points,
modules, etc).
Indicates the unavailability of the baery power, or a voltage
level less than DC 20V. The baery may be depleted because the
mains supply has been unavailable for an extended period of
time, or there is a fault in the baery charger that prevents the
baeries from being charged.
Indicates a fault with the internal supply voltages used to
supply power to the microprocessor, or to the running of
the control program.
Check the wiring for damage or
disconnection.
Check the power supply fuse.
replace the fuse if it is faulty.
Contact the service company to
replace the main controller.
Check that the baery
connections are secure.
Measure the baery voltage. If
the baery voltage is less than
the manufacturer's minimum.
Indicates the unavailability of the mains power.
Eah Fault Indicates a current leakage from any of the re
detection and alarm system wires to Eah. This may
occur if there is damage to a single conductor, and it
contacts some conductive equipment connected to Eah.
Isolate each of the transmission
paths in turn until the wires causing
the Eah have been identied.
Trace the faulty wires to locate the
source of the connection to Eah,
and prevent the connection path.
intelligent solutions
intelligent solutions

5. GLOSSARY AND REFERENCES
TERM
Access
Levels
Alarm
Condition
Control and
indicating
equipment
Disable
Condition
DESCRIPTION REFRENCE
EN 54-2, Control and
indicating equipment
EN 54-2, Control and
indicating equipment
EN 54-2, Control and
indicating equipment
EN 54-1, General and
denitions
Hierarchical levels to gain access to specic control
and conguration functions.
This equipment, that monitors devices displays
events, initiates alarm devices, and allows control of
the re detection and alarm system.
When an alarm zone (input devices or outputs) will
not repo alarm or fault events, nor respond to any
event even repoed by another zone.
Fault
Condition
EN 54-2, Control and
indicating equipment
When an event (either from an input device, a transmission
path, or within the control and indicating equipment) is
recognized as a fault.
Fire
Detection and
Alarm System
EN 54-1, General and
denitions
All detection, control and alarm equipment, including
detectors, manual call points, control and indicating
equipment, and audio & visual alarm devices.
When an event from an input device (e.g. detector) is
recognized as a re.
The following terms are associated with the CFS-FAP non-addressable control panel.
intelligent solutions
intelligent solutions

NOTES
intelligent solutions
intelligent solutions

intelligent solutions
intelligent solutions

intelligent solutions
Table of contents
Popular Control Panel manuals by other brands

technoswitch
technoswitch TEC601 Installation & operation manual

Siemens
Siemens Series 2300 installation instructions

Texecom
Texecom Premier 888 user manual

NEC
NEC Attendant Xen IPK Attendant user guide

XIM Technologies
XIM Technologies C3-X60 Series installation guide

Pulsar
Pulsar AWO 300 Assembly instructions

Plymovent
Plymovent CONTROLPRO/DILUTER installation manual

Global Fire
Global Fire Gekko Installation & commissioning manual

Pentair Pool Products
Pentair Pool Products EasyTouch 8 Installation and user guide

AEG
AEG S 64.9 L Instructions for use

Siemens
Siemens SINUMERIK MCP-S Series Equipment manual

Siemens
Siemens SIMATIC HMI 177 operating instructions