manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Allied
  6. •
  7. Air Conditioner
  8. •
  9. Allied RHP 3 Phase Series User manual

Allied RHP 3 Phase Series User manual

506863-02 Page 1 of 17Issue 909647
Installation and servicing of air conditioning equipment
can be hazardous due to internal refrigerant pressure
and live electrical components. Only trained and
qualified service personnel should install or service
this equipment. Installation and service performed by
unqualified persons can result in property damage,
personal injury, or death.
WARNING
If this unit is to be installed in a mobile or manufactured
homeapplication,theductworkmustbesizedtoachieve
static pressures within the manufacturer’s guidelines.
All other installation guidelines must also be followed.
Failure to do so may result in equipment damage,
personal injury, and improper performance of the unit.
WARNING
For your safety, do not store or use gasoline or other
flammablevaporsandliquidsinthevicinityofthis or any
other appliance. Such actions could result in property
damage, personal injury, or death.
WARNING
Theinstallationofthisappliance must conform totherequirementsof the National Fire ProtectionAssociation;theNational
Electrical Code,ANSI/NFPANo. 70 (latest edition) in the United States; the Canadian Electrical Code Part 1, CSA22.1
(latest edition) in Canada; and any state or provincial laws or local ordinances. Local authorities having jurisdiction
should be consulted before installation is made. Such applicable regulations or requirements take precedence over the
general instructions in this manual.
CAUTION
Improper installation, adjustment, alteration, service, or maintenance can cause injury or property
damage. Refer to this manual. For assistance or additional information, consult a qualified installer
or service agency.
WARNING
Save these instructions for future reference
INSTALLATION AND MAINTENANCE INSTRUCTIONS
RHP and RCE 3 Phase Series
Self-Contained Heat Pump and Air Conditioner
Manufactured By
Allied Air Enterprises, Inc.
A Lennox International Company
215 Metropolitan Drive
West Columbia, SC 29170
TABLE OF CONTENTS
INSTALLATION .................................................................2
OPERATION......................................................................9
MAINTENANCE .............................................................. 11
WIRING DIAGRAMS.......................................................12
WARRANTY....................................................................16
(P) 506863-02
*p506863-02*
Page 2 of 17 506863-02Issue 90964
LocaƟon
The unit is designed to be located outdoors with sufficient
clearance for free entrance to the air inlet and discharge air
openings. Thelocationmustalsoallow for adequate service
access. Figure 1 shows a typical installation.
The unit must be installed on a solid foundation that will not
settleorshift.Adequatestructural support must beprovided.
Maintain minimum clearances as shown in Figure 1 and
Table 1 and install the unit in level position. Isolate the base
fromthe building structure to avoidpossible transmission of
sound or vibration into the conditioned space.
The heat pump unit foundation should be raised to
a minimum of 3” above finish grade. In areas which
have prolonged periods of temperature below freezing and
snowfall, the heat pump unit should be elevated above the
average snow line. Extra precaution should be taken to
allow free drainage of condensate from defrost cycles to
prevent ice accumulation. The unit should not be located
near walkways to prevent possible icing of surface from
defrost condensate.
Avoid placingtheunit nearquietareassuchas sleeping
quarters or study rooms. Normal operating sound levels
maybeobjectionableiftheunit is placed near certainrooms.
Do not permit overhanging structures or shrubs to
obstruct condenser air discharge inlet or outlet.
For improved start-up performance, the indoor coil
should be washed with suitable detergent to remove
any residue from manufacturing processes.
Roof Curb InstallaƟon
If a roof curb is used, follow the manufacturer’s Installation
Instructions and be sure that all required clearances are
observed (see Clearances on page 3).
These units are shipped with four corner brackets in place
on the underside of the unit (see Figure 2). For heat
pumps the two rear corner brackets must be removed
before unit is installed onto roof curb assembly. For
air conditioner units remove all four corner brackets
before installing on roof curb.
These instructions explain the recommended method of
installation of the heat pump and air conditioner units and
associated electrical wiring.
This unit is designed and approved for use as a self-
contained air-to-air outdoor heat pump and air conditioner
system.
Theunitsarefactoryequippedwithatransformerandblower
control for applications without auxiliary heat. Electric heat
accessory kits (AHSA-) can be ordered for field installation
of additional heat where required.
These instructions, and any instructions packaged with
matingcomponents and/or accessories, shouldbe carefully
read prior to beginning installation. Note particularly any
CAUTIONS or WARNINGS in these instructions and all
labels on the units.
These instructions are intended as a general guide only,
for use by qualified personnel and do not supersede any
national or local codes in any way. Compliance with all
local, state, provincial, or national codes pertaining to this
typeofequipment should bedetermined prior to installation.
InspecƟon of Shipment
Upon receipt of equipment, carefully inspect it for possible
shipping damage. If damage is found, it should be noted
on the carrier’s freight bill. Take special care to examine
the unit inside the carton if the carton is damaged. File a
claim with the transportation company.
If any damages are discovered and reported to the carrier
DO NOT INSTALL THE UNIT, as claim may be denied.
Check the unit rating plate to confirm specifications
are as ordered.
LimitaƟons
The unit should be installed in accordance with all national
and local safety codes.
Limitations of the unit and appropriate accessories must
also be observed.
The unit must not be installed with any ductwork in the
outdoor air stream. The outdoor fan is not designed to
operate against any additional static pressure.
Minimum and maximum operation conditions must be
observed to assure maximum system performance
with minimum service required. Refer to Table 1 for the
application limitations of the unit.
INSTALLATION
506863-02 Page 3 of 17Issue 909647
Typical Field Wiring
Figure 1
To Unit Power Entry
Weatherproof
Disconnect Switch To
Power
Supply
NEC Class 1 Wiring
Thermostat
NEC Class 2 Wiring
To Low Voltage Entry
NOTE: All outdoor wiring must be weatherproof.
Low Voltage
Entry
Heater Accessory
Power Entry
Power Entry
Figure 2
Corner Brackets
Remove rear corner brackets before installing on roof curb.
Leave front corner brackets on unit for support.
Heat Pump Roof Curb Assembly
Figure 3
Clearances
All units require certain clearances for proper operation
and service. Refer to Table 1 on page 4 for the minimum
clearances to combustibles required for construction,
servicing, and proper unit operation.
In the U.S., units may be installed on combustible floors
made from wood or class A, B, or C roof covering material.
In Canada, units may be installed on combustible floors.
Units must be installed outdoors.
Page 4 of 17 506863-02Issue 90964
Rigging and Handling
Before lifting a unit, make sure that the weight is
distributedequallyon the cablesso that itwilllift evenly.
CAUTION
When connecting electrical power and control wiring
to the unit, waterproof-type connectors must be used
so that water or moisture cannot be drawn into the unit
during normal operation.
CAUTION
Three Phase 230V (-T models) are factory wired for a
230-volt power supply. If power supply is 208 volts, it
will be necessary to change a wire connection on the
unit transformer from 240V terminal to 208V terminal
as shown on the wiring diagram.
Use only copper conductors.
If any of the original unit wiring is replaced, the same size
and type wire must be used.
Exercise care when moving the unit. Do not remove any
packaging until the unit is near the place of installation.
Spreaders whose length exceeds the largest dimension
across the unit must be used across the top of the unit.
Units may also be moved or lifted with a forklift while still in
the factory-supplied packaging. The lengths of the forks
of the forklift must be a minimum of 42”.
Compressor
Units are shipped with compressor mountings factory
adjusted and ready for operation. Do not loosen
compressor mounting bolts.
Electrical Wiring
All field wiring must be done in accordance with National
Electrical Code recommendations, local codes, and
applicable requirements of UL, or in accordance with
CanadianElectricalCoderecommendations, local codes, or
CSAStandards.Powerwiring, disconnect means, andover-
current protection are to be supplied by the installer. Refer
to the unit rating plate for maximum over-current protection
andminimum circuit ampacity, as wellas operatingvoltage.
The power supply must be sized and protected according
to specifications supplied.
The unit must be grounded with a separate ground
conductor. See Figure 4 for typical field wiring connection.
The wiring diagram can be found on the unit inside the
access panel. Low voltage control wiring are pigtail leads
located on the main control box and are color-coded to
match the connection called out on the wiring schematic.
Figure 4
Power Wiring
If 208 volt is supplied, transformer connections must be
changed.
Line Voltage 208/230 Volts (- T Models)
460 Volts (- F Models)
FIELD-SUPPLIED
FUSED
DISCONNECT
CONTACTOR
GROUND
LUG
THREE
PHASE
POWER
SUPPLY
Table 1
Minimum Clearances
Combustibles Installation/
Service
Front of Unit 0 24”
Back of Unit 0 0
Left Side 0 24”
Right Side
(Condenser Coil) 0 24”
Below Unit 0 0
Above Unit 0 48”
506863-02 Page 5 of 17Issue 909647
When fastening ductwork to side duct flanges on unit,
insert screws through duct flanges only. Do not insert
screws through casing. Outdoor ductwork must be
insulated and waterproofed.
CAUTION
Thermostat
The room thermostat should be located on an inside
wall where it will not be subject to drafts, sun exposure,
or heat from electrical fixtures or appliances. Follow the
manufacturer’s instructions enclosed with the thermostat
for general installation procedure. Color-coded insulated
wires (#18AWG) should be used to connect the thermostat
to the unit. A minimum of five wires are required for proper
installation depending on thermostat used. For thermostat
wire runs up to 60 feet(18 m), use 18 gauge wire. For 60 to
90 foot (18 to 27 m) runs, use 16 gauge wire. (Depending
on thermostat used.)
Ductwork
Ductwork should be designed and sized according to the
methods in Manual Q of the Air Conditioning Contractors
of America (ACCA).
A closed return duct system shall be used. This shall not
preclude use of economizers or outdoor fresh air intake. It
is recommended that supply and return duct connections
at the unit be made with flexible joints.
The supply and return air duct systems should be designed
fortheCFMand static requirements ofthejob.They should
not be sized to match the dimensions of the duct
connections on the unit.
Filters
Filters are not supplied with the unit. Filters must always be
installed on the upstream side of the evaporator coil and
must be kept clean or replaced. Dirty filters will reduce the
airflow of the unit. Filters should be sized in accordance
with Table 2 on page 6.
This unit is equipped with an internal filter clip which is
located in the indoor coil compartment attached to the side
of the unit drain pan.
Figure 5
Typical Wiring Connections
Typical Wiring Connection
3 Phase
Page 6 of 17 506863-02Issue 90964
Condensate Drain
The package unit is equipped with a 3/4” fpt coupling for
condensate line connection. Plumbing must conform to
local codes. Use a sealing compound on the male adaptor
pipe threads.
The condensate drain line must be properly trapped and
routed to a suitable drain. See Figure 6 for proper drain
arrangement. The drain line must pitch to an open drain or
pump to prevent clogging of the line. Seal around the drain
connectionwith suitable material to prevent air leakageinto
the return air system.
Heater Kit Accessory (if used)
The unit is fully equipped for cooling operation without
auxiliary heat.Aheater kit accessory may also be used. To
install the heater kit accessory (see Figure 7):
1. Disconnectthepowerandopenthemaincontrolaccess.
2. Disconnect the plug separating the high voltage wire
harness. Remove the high voltage wire harness plug
and discard.
3. Removetheheaterblockoffbyremovingthefourscrews
holding it in place. Cut away the insulation covering the
opening, using the hole in the panel as a template.
4. Insertthe heater into the control panel and fasten in the
same mounting holes.
5. Plug the heater wiring harness into the wire harness
on the control assembly. Field wiring of the auxiliary
heater is separate from the unit power supply. Wire the
power supply wiring for the heater to the appropriate
connections on the heater kit.
Crankcase Heater (if used)
Some models may be equipped with insertion crankcase
heaters to prevent excessive migration of liquid refrigerant
into the compressor. The following steps should be taken
on initial start-up to prevent possible compressor damage.
The procedure must be followed at initial start-up as well as
any time power has been interrupted for 12 hours or longer.
1. Insure that the room thermostat is in OFF position to
prevent the compressor from starting.
2. Apply the main power supply to the outdoor unit. This
will energize the crankcase heater.
3. Maintain power to the unit for a minimum of 8 hours.
4. After reaching minimum elapsed time, the unit can be
safely started.
Except as required for safety while servicing, do not open
the system disconnect switch.
Drain Connection
Figure 6
UNIT
1 INCH
MIN
DRAIN
CONNECTION
POSITIVE LIQUID SEAL REQUIRED
3 INCH
MIN
12 INCH
MAX
Minimum Required Surface Area
for Disposable Filters
Table 2
Cooling BTU/HR Filter Area
48,000 (4 Ton) 800 Square Inches
60,000 (5 Ton) 900 Square Inches
Unit Model Internal Filter Size
RHP/RCE 36 28” X 25”
RHP/RCE 48-60 30” X 30”
506863-02 Page 7 of 17Issue 909647
Removal of Unit from Common Venting System
When an existing furnace is removed from a common
ventingsystemservingotherappliances,the venting system
is likely to be too large to properly vent the remaining
attachedappliances.Thefollowingtestshouldbeconducted
with each appliance while the other appliances connected
to the common venting system are not in operation.
1. Seal any unused openings in the common venting
system.
2. Visually inspect the venting system for proper size and
horizontal pitch and determine there is no blockage or
restriction, leakage, corrosion, or other deficiencies
which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and
windows between the space in which the appliances
remaining connected to the common venting system
are located and other spaces in the building. Turn on
clothes dryers and any appliance not connected to the
common venting system. Turn on exhaust fans, such
as range hoods and bathroom exhausts, so they will
operate at maximum speed. Do not operate a summer
exhaust fan. Close fireplace dampers.
4. Following the lighting instructions, place the unit being
inspected in operation. Adjust the thermostat so the
appliance will operate continuously.
5. Test for spillage at the draft control relief opening after
5 minutes of main burner operation. Use the flame of a
match or candle.
6. Follow the preceding steps for each appliance
connected to the common venting system.
7. After it has been determined that each appliance
remaining connected to the common venting system
properly vents when tested as outlined above, return
doors, windows, exhaust fans, fireplace dampers,
and any other fuel burning appliance to their previous
condition of use.
8. If improper venting is observed during any of the
above tests, the common venting system must be
corrected. See National Fuel Gas Code,ANSI Z223.1
(latest edition) or CAN/CGA B149.1 & .2 Canadian
Installation Codes to correct improper operation of
common venting system.
Heater Kit Accessory Installation
Figure 7
Page 8 of 17 506863-02Issue 90964
Figure 8
Defrost Control Board
RHP Models
Cooling
When the thermostat is in the cooling mode, the O circuit is
poweredwhich energizes thereversing valve. Upon cooling
demand, the thermostat closes circuit R and Y. Closing R
and Y closes the unit contactor, starting the compressor
and outdoor fan. Closing R to Y also brings on the indoor
blower at the same time. Upon satisfying cooling demand,
the thermostat will open the above circuits and open the
main contactor, stopping the compressor and outdoor fan.
The blower will continue to operate for 60 seconds which
improves system efficiency.
NOTE: There is no blower off delay when there is only a
cell for G (fan only).
Heating
Upon first stage heating demand, the thermostat closes
circuit R to Y, which closes the unit contactor, starting the
compressor and outdoor fan. The reversing valve is not
energizedintheheatingmode.Thethermostatautomatically
bringsontheindoorblower at the selected heatpumpspeed
at the same time. Upon satisfying the heating demand,
the thermostat opens the above circuits and stops the
compressor and outdoor fan. The blower will continue
running for an additional 60 seconds.
Units with Electric Heater (If accessory is field installed)
Ifduring a first stage heating demand the thermostat closes
theRtoWcircuit calling for a secondstageheatingdemand,
theelectric heater is energized. The compressor continues
to operate in heating mode. At the same time the indoor
blower is energized on the selected heting speed. If the
second stage heat demand is satisfied, the electric heat
stages off and indoor blower returns to the selected heat
pump speed.
Sequence of Operation
RCE Models
Cooling
Whenthethermostatcalls for cooling, Risclosed to G andY
(seewiring diagram). This actioncompletes the low voltage
control circuit, energizing the compressor, condenser fan
motor and blower motor.
Unit compressors have internal protection. If there is an
abnormalrise in the compressor temperature, the protector
will open and the compressor will stop.
Blower Delay-Cooling
In cooling mode, the circulating air blower operation is
delayed for five (5) seconds after the compressor starts.
The blower continues to operate for 60 seconds after the
compressor is de-eneregized. The feature is a function of
the blower motor itself and cannot be changed.
NOTE: There is no blower off delay when there is only a
call for G (fan only).
Electric Heat (If accessory is field installed)
When the thermostat calls for heat, R is closed to W (see
wiring diagram). This action energizes the blower motor
at the selected heat speed and also energizes the electric
heat elements through the sequencer (located on the field
installed electric heater panel). Upon satisfying heating
demand, the thermostat opens the W circuit, de-energizing
theelectricheater. The blower motorwillcontinuetooperate
for an additional 2 minutes before stopping.
506863-02 Page 9 of 17Issue 909647
Compressor Delay
The defrost board has a field-selectable function to reduce
occasionalsounds that mayoccur while the unit is cycling in
and out of the defrost mode. The compressor will be cycled
offfor30secondsgoinginand out ofthedefrostmode when
thecompressordelayjumperis installed. For optimal energy
performance, remove the delay jumper.
NOTE: The 30-second “off” cycle is not functional when
jumpering the TEST pins.
Time Delay
The timed-off delay is 5 minutes long. The delay helps to
protectthe compressor fromshort cycling incase the power
to the unit is interrupted or a pressure switch opens. The
delayis bypassed by placing thetimer select jumper across
the TEST pins for 0.5 seconds.
Pressure Switch Circuit
Highandlowpressureswitches are connected to thedefrost
control board on heat pump models (see Figure 8 on page
8). Air conditioning models have a high pressure switch
installed in line with compressor contactor coil.
NOTE: If both first and second stage heating demand
are satisfied at the same time or if the unit is operating in
emergency heat mode and the demand is satisfied, the
heat pump and heaters are de-energized while the blower
will continue to operate for an additional 2 minutes before
stopping.
Defrost System
The defrost system includes two components: the defrost
thermostat and the defrost control.
Defrost Thermostat
The defrost thermostat is located on the liquid line between the
check/expansion valve and the distributor. When the defrost
thermostat senses 42°F or cooler, the thermostat contacts close
and send a signal to the defrost control board to start the defrost
Ɵming. It also terminates defrost when the liquid line warms up
to 70°F.
Defrost Control
The defrost control board includes the combined funcƟons of
Ɵme/temperature defrost control, defrost relay, diagnosƟc LEDs
and terminal strip for field wiring connecƟons (see Figure 8).
The control provides automaƟc switching from normal heaƟng
operaƟon to defrost mode and back. During the compressor
cycle (call for defrost), the control accumulates compressor run
Ɵme at 30, 60, 90 minute field-adjustable intervals. If the defrost
thermostat is closed when the selected compressor run Ɵme
interval ends, the defrost relay is energized and the defrost begins.
Defrost Control Timing Pins
Each timing pin selection provides a different accumulated
compressorruntimeperiodduringone thermostat run cycle.
Thistimeperiodmustoccurbeforeadefrostcycleisinitiated.
Thedefrostintervalcanbeadjustedto30(T1), 90 (T2), or 90
(T3) minutes. The defrost timing jumper is factory installed
toprovide a 90-minute defrost interval. If the timing selector
jumper is not in place, the control defaults to a 90-minute
defrost interval. The maximum defrost period is 14 minutes
and cannot be adjusted. For optimal system performance,
move the jumper to the 60 minute defrost interval.
A test option is provided for troubleshooting. The test mode
may be started any time the unit is in the heating mode and
the defrost thermostat is closed or jumpered. If the jumper
is in the TEST position at power up, the control will ignore
the test pins. When the jumper is placed across the TEST
pins for 2 seconds, the control will enter the defrost mode. If
the jumper is removed before an additional 5-second period
has elapsed (7 seconds total), the unit will remain in defrost
mode until the defrost thermostat opens or 14 minutes have
passed. If the jumper is not removed until after the additional
5-second period has elapsed, the defrost will terminate and
the test option will not function again until the jumper is
removed and reapplied.
Defrost Control Board
Diagnostic LEDs
Table 3
Mode Green LED
(DS2) Red LED
(DS1)
No Power
to Board Off Off
Normal Operation/
Power to Board Simultaneous Slow Flash
Anti-Short Cycle
Lockout Alternating Slow Flash
Low Pressure
Switch Fault Off Slow Flash
Low Pressure
Switch Lockout Off On
High Pressure
Switch Fault Slow Flash Off
High Pressure
Switch Lockout On Off
Page 10 of 17 506863-02Issue 90964
During a single demand cycle, the defrost control will
lock out the unit after the fifth time that the circuit is
interrupted by any pressure switch wired to the control
board. In addition, the diagnostic LEDs will indicate a
locked-out pressure switch after the fifth occurrence of
an open pressure switch (see Table 3).
The unit will remain locked out until power to the board
is interrupted, then re-established, or until the jumper
is applied to the TEST pins for 0.5 seconds.
NOTE: Thedefrost control board ignores input from the low
pressure switch terminals as follows:
• During the TEST mode
• During the defrost cycle
• During the 90-second start-up period
• For the first 90 seconds each time the reversing
valve switches heat/cool modes
If the TEST pins are jumpered and the 5-minute delay
is being bypassed, the LO PS terminal signal is not
ignored during the 90-second start-up period.
Diagnostic LEDs
The defrost board uses two LEDs for diagnostics. The
LEDs flash a specific sequence according to the condition
as shown in Table 3.
System Performance (RCE, RHP Models)
This equipment is a self contained, factory optimized
refrigerant system, and should require no adjustments
when properly installed. If however unit performance is
questioned, perform the following checks.
Insure unit is installed per manufacturer’s instructions and
that line voltage and air flows are correct. Refer to Table 4
for proper superheat values. Check super heat settings by
measuringpressureatthesuction line service port. ForTXV
systems, measure pressure at the liquid service port. Take
line temperature within 2 inches of service port connection
to its main tube. If unit superheat/subcooling varies by
more than table allowance, check internal seals, service
panels and duct work for air leaks, as well as restrictions
and blower speed settings. If unit performance remains
questionable, remove charge, evacuate to 500 Microns,
and weigh in refrigerant to name plate charge. It is critical
that the exact charge is re-installed. Failure to comply will
compromisesystemperformance. Ifunit performance is still
questionable, check for refrigerant related problems such
as,blocked coil or circuits, malfunctioningmetering devices
or other system components.
Suction Superheat
Table 4
* These letters will vary according to unit series.
Outdoor
Unit Model
Suction Superheat
+/- 3° @ AHRI
Conditions 82° OD
80° IDDB/67° IDWB
RHP13(*)36 16
RHP13(*)48 19
RHP13(*)60 16
RCE13(*)36 17
RCE13(*)48 15
RCE13(*)60 15
506863-02 Page 11 of 17Issue 909647
MAINTENANCE
Periodic inspection and maintenance normally consists of
changingorcleaningthefiltersandcleaningtheoutdoorcoil.
On occasion, other components may also require cleaning.
Filters
Filters are not supplied with the unit. Inspect once a month.
Replacedisposable or clean permanent type as necessary.
Do not replace permanent type with disposable.
Motors
Indoor and outdoor fan and vent motors are permanently
lubricated and require no maintenance.
Some models may be equipped with a permanent magnet,
constanttorque indoor blower motor. Thesemotors remain
energized and are controlled by 24V signals. For high
static applications, use tap 3 for cooling speed and tap 5 for
heatingspeed. Refertothe heater install labelforlimitations
to blower tap selection on heating speeds.
Outdoor Coil
Dirt and debris should not be allowed to accumulate on the
outdoorcoil surface or other partsin the air circuit. Cleaning
shouldbeasoftenasnecessarytokeepthecoilclean.Usea
brush,vacuumcleanerattachment,or other suitable means.
If water is used to clean the coil, be sure the power to unit
is shut off prior to cleaning. Care should be used when
cleaning the coil so that the coil fins are not damaged.
Before performing maintenance operations on the
system, shut off all electrical power to the unit. Turn off
accessory heater power switch if applicable. Electrical
shock could cause personal injury or death.
WARNING
Page 12 of 17 506863-02Issue 90964
Figure 9
230V 3 PHASE HEAT PUMP
506863-02 Page 13 of 17Issue 909647
230V 3 PHASE ELECTRIC/ELECTRIC
Figure 10
Page 14 of 17 506863-02Issue 90964
Figure 11
460V 3 PHASE HEAT PUMP
506863-02 Page 15 of 17Issue 909647
460V 3 PHASE ELECTRIC/ELECTRIC
Figure 12
Page 16 of 17 506863-02Issue 90964
EQUIPMENT LIMITED WARRANTY
APPLIES IN U.S.A. AND CANADA ONLY
FAILURE TO MAINTAIN YOUR EQUIPMENT WILL VOID THIS WARRANTY.
COVERED EQUIPMENT
The following heating and cooling equipment is covered by the Limited
Warranty:
Oil Furnaces: LG14.
Unit/Duct Heaters: LD24 (all units), LF24 and TUA (100,000 to 400,000 btuh units).
Evaporator Coils:
C17.
Air Handlers:
ACBX32, CB17, CBH17, TAA.
Condensing Units:
4SCU13LC, TSA.
Heat Pumps:
4SHP13LC, TPA.
Packaged Equipment: KCA, KGA, KHA, TCA, TGA, THA, RGE13, RHP13, RCE13.
Electric Heat Sections:
AECB29, ECH16, EH17, ECH24.
ONE (1) YEAR COVERAGE −− ALL APPLICATIONS
The covered equipment and covered components are warranted by the
manufacturer for a period of one (1) year from the date of the original unit
installation, when installed and operated in accordance with the manufac-
turer’s recommendations. If, during this period, a covered component fails
because of a manufacturing defect, the manufacturer will provide a free
replacement part to the owner. The owner must pay shipping charges and
all other costs of warranty service.
EXTENDED COVERAGE
This limited warranty provides extended coverage on the components
outlined below. The extended warranty coverage begins with the date of
the original unit installation and represents the total warranty period for the
specific component.
Heat Exchangers:
KGA and TGA (Aluminized −− All applications) −− Ten (10) years.
KGA and TGA (Stainless −− All applications) −− Fifteen (15) years.
RGE13, RHP13 and RCE13 −− Ten (10) years.
LF24 and TUA (Aluminized −− All applications) −− Ten (10) years.
LF24 and TUA (Stainless −− All applications) −− Fifteen (15) years.
LD24 (Aluminized −− All applications) −− Two (2) years.
LD24 (Stainless −− All applications) −− Five (5) years.
LG14 (All applications) −− Five (5) years.
Burners:
LG14
−− Three (3) years.
Compressors:
4SCU13LC, 4SHP13LC −− Five (5) years.
TSA, TPA −− Five (5) years.
KCA, KGA, KHA, TCA, TGA, THA −− Five (5) years.
RGE13, RHP13, RCE13 −− Five (5) years.
NOTE − If the date of original installation cannot be verified, the warranty
period will be deemed to begin six (6) months after the date of manufac-
ture.
COMPONENT AVAILABILITY
In the event that a component covered by this warranty is no longer available, the
manufacturer will, at its option, provide a free suitable substitute component or
allow the owner to purchase an equivalent new unit at a reduced price of 20 per-
cent of the list price in effect on the date of the failure. The owner must pay ship-
ping charges and all other costs of warranty service.
EXCLUDED COMPONENTS
The following components are not protected by this warranty: cabinets,
cabinet pieces, air filters, driers, refrigerant, belts, wiring, fuses and unit
accessories.
REPAIRS
All repairs of covered components must be made with authorized service
parts by a licensed professional service contractor (or equivalent).
CARE OF EQUIPMENT
This new unit must be properly installed, operated and maintained by a li-
censed professional installer (or equivalent) or service agency in accordance
with the unit installation, operation and maintenance instructions provided
with each unit. Failure to provide maintenance per the manufacturer’s instruc-
tions will void this warranty. The owner may be asked to provide written docu-
mentation of annual and other periodic preventive maintenance.
506863-02 Page 17 of 17Issue 909647
WARRANTY PROCEDURE
When warranty parts are required:
1 − Be prepared to furnish the following information:
a − Complete model and serial number.
b − Proof of required periodic maintenance, installation date and location
if warranty claim.
c − An accurate description of the problem.
2 − Call your local installing contractor.
3 − If the installing contractor is unable to provide warranty parts, check the
yellow pages for another contractor in your area. If you are unable to se-
cure assistance from a contractor, contact the appropriate manufacturer
listed below:
Lennox Industries Inc. Allied Air Enterprises
P.O. Box 799900 215 Metropolitan Drive
Dallas, TX 75379−9900 West Columbia, SC 29170
1−800−9LENNOX 1−800−448−5872
WARRANTY LIMITATIONS
1 − The manufacturer will not pay labor involved in diagnostic calls, or in re-
moving, repairing, servicing, or replacing parts. Such costs may be cov-
ered by a separate warranty provided by the installing contractor.
2 − This warranty is void if the covered equipment is removed from the origi-
nal installation site.
3 − This warranty does not cover damage or defect resulting from:
a − Flood, wind, fire, lightning, mold, or installation and operation in a cor-
rosive atmosphere, or otherwise in contact with corrosive materials
(chlorine, fluorine, salt, recycled waste water, urine, fertilizers, or oth-
er damaging substances or chemicals).
b − Accident, neglect, or unreasonable use or operation of the equip-
ment, including operation of electrical equipment at voltages other
than the range specified on the unit nameplate (includes damages
caused by brownouts), or reverse rotation of compressors or motors
due to improper phasing.
c − Modification, change or alteration of the equipment, except as di-
rected in writing by the manufacturer.
d − Operation with system components (indoor unit, outdoor unit and re-
frigerant control devices) which do not match or meet the specifica-
tions recommended by the manufacturer.
e − Operation of packaged gas/electric units (equipped with aluminized
heat exchanger) with mixed air temperatures of less than 45°F (7°C).
f − Operation of furnaces with return air temperatures of less than 60°F
(16°C) or operation of a furnace field−installed downstream from a
cooling coil.
g − Use of contaminated or alternate refrigerant.
The installation of replacement parts under terms of this warranty will not ex-
tend the original warranty period.
The manufacturer makes no express warranties other than the warranty
specified above. All implied warranties, including the implied warranty
of merchantability and fitness for a particular purpose, are excluded to
the extent legally permissible. Should such exclusion or limitation of the
warranty be unenforceable, such implied warranties are in any event
limited to to a period of one (1) year. Liability for incidental and conse-
quential damages is excluded. Some states do not allow limitations on
the duration of an implied warranty or the exclusion or limitation of inci-
dental or consequential damages, so the limitations or exclusions may
not apply to you.
The manufacturer will not pay electricity or fuel costs, or increases in
electricity or fuel costs, for any reason whatsoever, including additional
or unusual use of supplemental electric heat. This warranty does not
cover lodging expenses.
The manufacturer shall not be liable for any default or delay in perfor-
mance under this warranty caused by any contingency beyond its con-
trol.
This warranty gives you specific legal rights, and you may also have other
rights which vary from state to state.
NOTE TO CUSTOMER
Please complete information below and retain this warranty for your re-
cords and future reference.
Unit Model Number:
Serial Number: Date:
Installing Contractor: Phone:
FORM W−024−L3 −− 9/1/2011
Supersedes 6/1/2009
Litho U.S.A.E2011
*PW-024-L3*

This manual suits for next models

1

Other Allied Air Conditioner manuals

Allied 4AC13 Instructions and recipes

Allied

Allied 4AC13 Instructions and recipes

Allied 4AC17 User manual

Allied

Allied 4AC17 User manual

Allied 4DHV Mini-Split Series User manual

Allied

Allied 4DHV Mini-Split Series User manual

Allied 4SCU13 Installation manual

Allied

Allied 4SCU13 Installation manual

Allied PRPGN14 Series User manual

Allied

Allied PRPGN14 Series User manual

Allied 4SCU14LE Series User manual

Allied

Allied 4SCU14LE Series User manual

Allied 4SHP22LX User manual

Allied

Allied 4SHP22LX User manual

Allied 4SCU18LT Series User manual

Allied

Allied 4SCU18LT Series User manual

Allied 4AC13/14 Quick setup guide

Allied

Allied 4AC13/14 Quick setup guide

Allied 4SCU20LX User manual

Allied

Allied 4SCU20LX User manual

Allied Lennox 4AC16LT Series User manual

Allied

Allied Lennox 4AC16LT Series User manual

Allied 4SHP20LX User manual

Allied

Allied 4SHP20LX User manual

Popular Air Conditioner manuals by other brands

Daikin SIESTA SERIES installation manual

Daikin

Daikin SIESTA SERIES installation manual

Sanyo 36XH72R Dimensional information

Sanyo

Sanyo 36XH72R Dimensional information

Daewoo DWC-051C Use & care manual

Daewoo

Daewoo DWC-051C Use & care manual

Danfoss Optyma OP-LPHE Series instructions

Danfoss

Danfoss Optyma OP-LPHE Series instructions

Stilevs ST-09UW4RMRCE00 Installation and user manual

Stilevs

Stilevs ST-09UW4RMRCE00 Installation and user manual

Airfel LBA160AV1B Operation & installation manual

Airfel

Airfel LBA160AV1B Operation & installation manual

vidaXL 50762 Operating and safety instructions

vidaXL

vidaXL 50762 Operating and safety instructions

Goodmans GMSG owner's manual

Goodmans

Goodmans GMSG owner's manual

LG Room air conditioner installation manual

LG

LG Room air conditioner installation manual

Fujitsu ASYG09KMCB Design & technical manual

Fujitsu

Fujitsu ASYG09KMCB Design & technical manual

Carrier 42GW installation manual

Carrier

Carrier 42GW installation manual

Mitsubishi Electric PLFY-P15VFM-E1 Technical & service manual

Mitsubishi Electric

Mitsubishi Electric PLFY-P15VFM-E1 Technical & service manual

Acare MRW 12HL installation manual

Acare

Acare MRW 12HL installation manual

Gree GWC09TB-S3DNA1B owner's manual

Gree

Gree GWC09TB-S3DNA1B owner's manual

Daikin EHVH04SU18CB6W Operation manuals

Daikin

Daikin EHVH04SU18CB6W Operation manuals

Gree GWC18QD-D3DNA6E (LC) Service manual

Gree

Gree GWC18QD-D3DNA6E (LC) Service manual

Daikin RXG-L Technical data

Daikin

Daikin RXG-L Technical data

Mitsubishi Electric PUMY-P200YKM installation manual

Mitsubishi Electric

Mitsubishi Electric PUMY-P200YKM installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.