Alpha Power TST200 series User manual

TST200User sManual
1/11
TST200 series
StaticTransferSwitch
USER MANUAL
Version 1.0
Date: Nov2009

TST200User sManual
2/11
A
Ab
bo
ou
ut
t
T
TB
BB
B
AlphaPowerisadedicated designerandmanufacturerof sophisticated andenvironmentally
rugged powerelectronics equipmentforvariousmarkets:telecom,utility,automotive,
railwayand solaretc.
Weareofferingawide range ofpowerconversionproductfromstandalone inverter,N+1
redundantinverter,UPStobatterycharger,inverterchargercombination andsolarcharge
controller.
Weensureconsistentproductqualitybysubjecting everyproducttostrictlychoiceof
superiorqualitycomponents,rigoroustestingand burn-inthroughouttheproduction
process.Poweriscertified byTUVinaccordancewithISO9001and canbeyour
reliablepowersolution provider.
D
Di
is
sc
cl
la
ai
im
me
er
r
Unless speciallyagreed inwriting,,
ØTakeno warrantyastothe accuracy,sufficiency ofsuitabilityofanytechnicalorother
informationprovidedinthismanualorotherdocumentation.
ØAssumesnoresponsibilityorliabilityforlossordamage,whetherdirect,indirect,
consequentialorincidental,whichmight ariseoutoftheuseofsuchinformation
A
Ab
bo
ou
ut
t
t
th
hi
is
s
M
Ma
an
nu
ua
al
l
Thismanualdescribesourproductfeaturesandprovidesprocedureofinstallations.This
manualisforanyone intendingtoinstall ourequipment.
Alpha
Alpha Power System Pty Ltd

TST200User sManual
3/11
G
Ge
en
ne
er
ra
al
l
I
In
ns
st
tr
ru
uc
ct
ti
io
on
n
Thanks forchoosingourproductsandthismanualweresuitableforTST200seriesstatic
transferswitch.
Thischaptercontainsimportant safetyand operation instructions. Read andkeepthisUser
Guidewell forlaterreference.
The TST200 needstobe installedbyprofessionalsandpleasepayattentiontothe
followingpointspriortoinstallation:
1>Pleasechecktheinputvoltageorvoltageofbatteryissametothenominalinput voltage
ofthisinverter.
2>Whileconnecting,pleasesecuretheconnectionand avoidshort cut.
3>STSwill havehigh voltage inside.Onlyauthorizedelectriciancanopenthe case.
4>The inverterWASNOTdesignedtouseinanyliferetaining equipment.

TST200User sManual
4/11
1
1.
.
G
Ge
en
ne
er
ra
al
l
S
Sa
af
fe
et
ty
y
I
In
ns
st
tr
ru
uc
ct
ti
io
on
n
1
1.
.1
1
S
Sa
af
fe
et
ty
y
I
In
ns
st
tr
ru
uc
ct
ti
io
on
n
Asdangerousvoltagesandhightemperatureexist withintheonlyqualifiedand
authorizedmaintenancepersonnelarepermitted toopenandrepairit.
Thismanualcontainsinformationconcerningtheinstallationandoperationof theTST200.
All relevantpartsof themanualshouldbereadpriortocommencingtheinstallation.Please
followthelocalstipulationmeantime.
Anyoperationagainstsafetyrequirementoragainstdesign,manufacture,safetystandard,
andareoutofthemanufacturerwarranty.
1
1.
.2
2
G
Ge
en
ne
er
ra
al
l
P
Pr
re
ec
ca
au
ut
ti
io
on
n
1.2.1Donotexposetodust, rain, snoworliquidsofanytype it isdesignedforindooruse.
DO NOTblock offventilation,otherwisetheequipment wouldbeoverheating.
1.2.2Toavoidfireandelectricshock makesureall cablesselectedwithrightgaugeand
beingconnectedwell.Smallerdiameterandbrokencablearenotallowedtouse.
1.2.3Pleasedonotput anyinflammablegoodsnearto.
TST200

TST200User sManual
5/11
2
2.
.0
0
I
In
nt
tr
ro
od
du
uc
ct
ti
io
on
n
a
an
nd
d
S
Sp
pe
ec
ci
if
fi
ic
ca
at
ti
io
on
n
2
2.
.1
1
I
In
nt
tr
ro
od
du
uc
ct
ti
io
on
n
TheTST200StaticTransferSwitchisahotpluggablesingle-phasetransferdevice,providing
automaticswitchingbetween twoindependentACpowersources.It couldachieveveryfast
switchwithoutinterrupting powerand itissuitableforimportantITequipmentwhichcan not
affordpowerdisruption and ATScannotsatisfy.Meantime,itintegrated amaintenancebypass
inside whichcouldachieveautomaticswitchtomaintenancebypass (MTS)incaseofSTS
maintenance.
lHot pluggable
lTransfertimeless than 4mswhen inputpoweraresynchronization and transfertimeisless
than 10msincaseofinput non-synchronization.
lIntegrated MaintenanceBypass
lIntelligent monitor, diagnostics and alarming
lProtection and alarmagainst HighVoltage, LowVoltage, PowerFailureand Overload.
lOverload protection: STSshutdownincaseof150%overload and will reconnect after10s
lShortcutprotection:incaseofoutputshortcut, systemwouldcutoutoutputoffering
protection forinput power.
lUsercan set upeitherinput asmainandtheotherwill bestandbyautomatically
lSupportmanualselect
lIncaseofSTSfail,the systemwill chooseone inputsourceasfixsource,toensure
uninterruptiblepowersupply
lRS232 orRS485communication
lStructure: 19”2U

TST200User sManual
6/11
2
2.
.2
2
S
Sp
pe
ec
ci
if
fi
ic
ca
at
ti
io
on
n
Model TST220 TST232
ratedAmps 20A 32A
Dimension 19"2U(87x483x259mm -- HxWxD)
Weight 6kgs
Input voltage 220±15%
Outputvoltage 220±15%
Input ratedfrequency 50Hz/60Hz
Overload Capability 150%
<4ms-synchronization
transfertime <10ms-non-synchronization
Efficiency >99%
Transfermode Breakbeforemake
Peakfactor 4:1
OperationTemp .-5C-40C
StorageTemp .-25C-60C
Humidity <93%noncondensing
Communication RS485+Drycontacts
2
2.
.3
3
S
Sy
ys
st
te
em
m
P
Pr
ri
in
nc
ci
ip
pl
le
e
MAIN CNTROL
CUR
LED
DRYCONTACT
RS485
CUR
K1-3
INPUT1-L
INPUT1-N
INPUT2-L
INPUT2-N
OUTPUT-L
K1
S1
S2
K2 K3
OUTPUT-N
T1
1 3
2 4
Note:
1. K3 automaticbypass switch.Whensystemerror,INPUT1offeruninterruptedpowertothe
load.
2. K2 outputrelay.Wheninput1andINPUT2haveissueatthesametime,thesystemcutdown
theoutputbyK2.
3. K1 switchrelaybetweenINPUT1 andINPUT2.
4. S1 inputswitchofINPUT1
5. S2 inputswitchofINPUT2.

TST200User sManual
7/11
3
3.
.0
0
S
St
tr
ru
uc
ct
tu
ur
re
e
a
an
nd
d
D
Di
is
sp
pl
la
ay
y
3
3.
.1
1
S
St
tr
ru
uc
ct
tu
ur
re
e
3
3.
.2
2
F
Fr
ro
on
nt
t
p
pa
an
ne
el
l
LED Color Status
1 Syn Green indicateinput 1and input 2areinsynchronization
Green input 1normal
2 Input 1 Red input 1fault
3 Output 1 Green output using input1
Green Output normal
4 OutputRed Outputfault
5 Switch switching between input 1and input 2underMANUALCondition
6 Auto/Manual chooseworking mode.Underautomode,input1willbenamed as
priorityautomatically
Green input 2normal
7 Input 2 Red input 2fault
8 Output 2 Green output using input2
9 Mute Mutethe alarm

TST200User sManual
8/11
3
3.
.3
3
R
Re
ea
ar
r
p
pa
an
ne
el
l
No. Description
Left 1 Overload
Left 2 CH1 fault
Left 3 Synchronization fault
1 Dry
contact Left 4 Input 2fault
2 Circuit breaker Input 1circuitbreaker
3 Connector Input 1 –L
4 Connector Input 1 –N
5 Connector Earth
6 Connector Input 2 –L
7 Connector Input 2 –N
8 Circuit breaker Input 2circuitbreaker
9 Connector Output –L
10 Connector Output –N
11 Connector Output –Earth
12 Communication port RS485

TST200User sManual
9/11
4
4.
.0
0
I
In
ns
st
ta
al
ll
la
at
ti
io
on
n
4
4.
.1
1
M
Ma
at
te
er
ri
ia
al
l
l
li
is
st
t
The unitispackedwithfollowingmaterials:
ØEquipment: the19”2Ucabinet andSTSmodulearepackedseparately
ØUser smanual
ØPleaseconfirm the seriesnumberonthe eachmoduleandsubrack issametothaton
outercarton.
4
4.
.2
2
L
Lo
oc
ca
at
ti
io
on
n
Pleaseinstall the equipmentinalocation ofDry, Clean, Coolwithgoodventilation.
lWorkingtemperature:0-40
lStoragetemperature:-40-70
lRelativeHumidity:0%-95% non-condensing
lCooling:forcedair
lVerticalangle:Novibrationandhangingangleless than5degree
4
4.
.3
3
W
Wi
ir
ri
in
ng
g
Please find the following recommended wire size
ACwiring
System
capacity 110VAC 220VAC
20A 6mm²6mm²
32A 8mm²8mm²

TST200User sManual
10/ 11
4
4.
.4
4
I
In
ns
st
ta
al
ll
la
at
ti
io
on
n
4
4.
.4
4.
.1
1
P
Pl
la
ac
ce
e
t
th
he
e
c
ca
ab
bi
in
ne
et
t
Theequipment hastwopartsone isa19”2Ucabinetand aSTSmodule.
Putthe shelf on the rightlocation of 19inchrack (Caution:Additionalsupport must beadded as
bottom!).Trytopushtheunitfromthe frontandside toseeitmoves;and repeattheabove
action until it isfirmlysecured..
4
4.
.4
4.
.2
2
C
Co
on
nn
ne
ec
ct
ti
in
ng
g
t
th
he
e
c
ca
ab
bl
le
e
Fortheuseroperation safety,cutoffthepowerbeforeinstallation
ØConnectACinputand ACoutput
ØConnectdrycontact wireand communication wire
Pleasedoublecheck theACinput andACoutput wasright afterconnection.
Wrongconnectionwill causepermanentdamageofequipmentandit isoutof
warranty.
4
4.
.4
4.
.3
3
I
In
ns
se
er
rt
t
i
in
n
S
ST
TS
S
m
mo
od
du
ul
le
e
Pleaseinsert inthe STSmoduleintothecabinet andscrewthe module.

TST200User sManual
11/11
5
5.
.0
0
O
Op
pe
er
ra
at
ti
io
on
n
5
5.
.1
1
D
Do
ou
ub
bl
le
e
C
Ch
he
ec
ck
ki
in
ng
g
ØDoubleconfirmthe inputvoltagematchesthevoltageofthisequipment, donotconnect
different voltageotherwiseitwill damagethe equipment
ØCheck ifwiringofinput 1, input 2and outputareright
ØAfterabovecheck andeverythingisright, pleaseswitchon theinput1switchand input2
switch
5
5.
.3
3
S
Sw
wi
it
tc
ch
h
T
Te
es
st
t
ØSet theauto/manualswitchatmanual,you can chooseeitherinput asmain.
ØSetthe auto/manualswitchatauto,the input1willbe choseasmain.Switchoff the input1
and STSwill switchtoinput2. Then,closethe input 1switch,the STSwill resumetoinput1.
ØAt autoposition,youcan not manuallychooseinput1orinput 2
5
5.
.4
4
M
Ma
ai
in
nt
te
en
na
an
nc
ce
e
B
By
yp
pa
as
ss
s
T
Te
es
st
t
ØPlugout theSTSmodule, output shouldswitchtoMaintenancebypass automatically.
ØPluginthe STSmodule, output shouldswitchtooneoutput
5
5.
.5
5S
Si
il
le
en
nt
t
Incaseoffaultdetected, the monitormodulewill sendoutaudioalarm. You canturnoff the
audioalarm throughpressingthesilentswitchatfrontpanelfor3seconds.Ifyou wantto
activetheaudioalarm,pleasepressthesilentbutton foranother3seconds.
Notice:
ØForsamefault,systemwon tdeliveraudioalarm if it wasturnoff inprevioustime.
ØFordifferentfault, systemwill still deliveraudioalarm.
Alpha Power Systems
Unit 3, 30 Heathcote Rd
Moorebank NSW 2170
Ph: 02-9602 8331