Amana MBVB Series User manual

SS-AMBVC www.amana-hac.com 10/23
Amana® is a trademark of Maytag Corporaon or its related companies and used under license to Goodman Company, L.P., Houston, Texas.
* Complete warranty details available from your local dealer or at www.amana-hac.com. To receive the
10-Year Parts Limited Warranty, online registraon must be completed within 60 days of installaon. Online
registraon is not required in California or Québec. The duraon of warranty coverage in Texas and Florida diers
in some cases.
MBVB
Multi-position, Variable speed
ECM-based, Modular Blower
ComfortbridgeTM Compatible
Contents
Air Handler Nomenclature ....................2
Heater Kit Nomenclature.......................2
Product Specicaons ...........................3
Airow Data ............................................4
Heat Kit Data...........................................5
Dimensions ............................................6
Wiring Diagram.......................................7
Accessories .............................................8
Product Features Cabinet Features
• Variable-speed ECM blower motor
• Integrated communicang
ComfortBridge™ Technology
• Commissioning and diagnoscs via
on board Bluetooth with the CoolCloud™
phone and tablet applicaon
• Advanced conguraon of the airow
and tonnage in communicang mode
• Provides constant CFM over a wide
range of stac pressure condions
independent of duct system
• CFM indicator
• Fault recall of six most recent faults
• Provides adjustable low CFM for ecient
fan-only operaon
• Improved humidity and comfort control
• Built-in compability with mul-stage heat
pump and cooling applicaons
• UL 60335 2-40 Compliant
• AHRI cered; ETL listed
• Blower secon usable as electric heater
• Horizontal or vercal conguraon capabilies
• 21” depth for easier ac access
• Foil-faced insulaon covers the internal
casing to reduce cabinet condensaon
• Galvanized, leather grain-embossed nish
• Cabinet air leakage less than 2% at
1.0 inch H₂0 when tested in accordance
with ASHRE standard 193
• Cabinet air leakage less than 1.4% at
0.5 inch H₂0 when tested in accordance
with ASHRE standard 193
• Field Installed 3 kW – 20 kW electric
heater kits available

2www.amana-hac.com SS-AMBVC SS-AMBVC www.amana-hac.com 3
Nomenclature
M B V B 1 2 B P 1 X 0 0 A A
1 2 3 4 5 6 7 8 9 10 11 12 13 14
A
A
B- 17.5"
C- 21.0"
D - 24.5"
T A 2 5 1
1 2 3 4 5 67 8 9
Unit Type
3 3.00 kW 6 6.00 kW 10 10.00 kW
5 5.00 kW 8 7.00 kW 15 15.00 kW
20 20.00 KW

2www.amana-hac.com SS-AMBVC SS-AMBVC www.amana-hac.com 3
Product Specifications
MBVB12BP1X00 MBVB16CP1X00
Diameter 10" 10" 11"
Width 8" 8" 10"
Voltage (V) 208/230 208/230 208/230
MCA (A) 4.9 6.5 6.5
MOP (A) 15
½¾¾
Width 17½" 21" 24½"
Depth 21" 21" 21"
Height 26" 30" 30"
67 80 86
• Minimum Circuit Ampacity and Maximum Overcurrent Protecon Device (MOD) for blower without supplemental heat installed.
Refer to unit nameplate for these specicaons with approved accessory heaters installed.
• Condensate management kits are available for units installed in high temperature and high humidity areas. Kit number MBK0002
has been developed to resolve condensate issues in the eld and is available from the Service Parts Department. Refer to IO-849
for installaon instrucons.

4www.amana-hac.com SS-AMBVC SS-AMBVC www.amana-hac.com 5
Airflow Data
MBVB12
BP1X00A*
ALow 420 415 400 400 395 390 390 390 380
BLow 550 545 540 540 535 530 530 525 520
CLow 680 675 670 665 660 655 655 650 640
DLow 810 805 800 800 800 795 790 785 785
AHigh 615 605 600 600 595 590 590 585 580
BHigh 805 805 800 800 800 795 790 785 780
CHigh 1010 1005 1000 1000 995 995 990 985 975
DHigh 1210 1205 1200 1200 1200 1195 1195 1190 1180
MBVB16
CP1X00A*
ALow 690 680 670 665 660 655 625 595 575
BLow 850 830 800 795 790 785 775 750 725
CLow 980 970 940 935 930 910 890 865 860
DLow 1110 1085 1070 1055 1045 1025 1000 990 975
AHigh 1045 1015 1000 990 975 950 935 920 900
BHigh 1245 1215 1200 1180 1175 1165 1150 1130 1115
CHigh 1415 1410 1400 1365 1360 1350 1340 1330 1320
DHigh 1605 1600 1600 1540 1530 1520 1510 1500 1490
MBVB20
DP1X00A*
ALow 835 815 800 800 795 795 790 775 750
BLow 1075 1070 1070 1065 1050 1045 1045 1040 1035
CLow 1210 1205 1200 1200 1195 1190 1190 1185 1175
DLow 1345 1340 1340 1320 1320 1315 1315 1305 1305
AHigh 1210 1205 1200 1195 1150 1150 1145 1135 1115
BHigh 1610 1605 1600 1540 1535 1535 1530 1520 1510
CHigh 1830 1805 1800 1785 1760 1760 1755 1750 1715
DHigh 2020 2010 2000 1995 1995 1970 1970 1965 1955
MBVB12BP1X00
MBVB16CP1X00
o o A600 1000 1200
on o B800 1200 1600
o on C1000 1400 1800
on on D1200 1600 2000
S3 S4 Trim Value S5 S6
o o 0o o A
on o 10% on o B
o on -10% o on C
on on 0on on D
MBVB12BP1X00
MBVB16CP1X00
o o on 20 NA NA 2000
o on o 15 1400 1500 1500
o on on 10 1000 1000 1200
on o o 8740 1000 1000
on o on 6635 800 800

4www.amana-hac.com SS-AMBVC SS-AMBVC www.amana-hac.com 5
MCA¹ MOP² MCA¹ MOP² MCA¹ MOP²
MBVB12BP1X00AB
HKTAN031
HKTA*051
HKTAN061
HKTA*081
HKTA*101
HKTAD151
0/0
10.8/12.5
18.1/20.8
21.7/25.0
25.3/29.2
36.1/41.7
36.1/41.7
4.9/4.9
18.4/20.5
27.4/30.9
32.0/36.1
36.5/41.3
50.0/57.0
50.0/57.0
15/15
20/25
30/35
35/40
40/45
50/60
50/60
---
---
---
---
---
---
18/20.8
---
---
---
---
---
---
22.5/26.0
---
---
---
---
---
---
25/30
---
---
---
---
---
---
72.6/83.0
---
---
---
---
---
---
80/90
MBVB16CP1X00AB
HKTAN031
HKTA*051
HKTAN061
HKTA*081
HKTA*101
HKTAD151
0/0
10.8/12.5
18.1/20.8
21.7/25.0
25.3/29.2
36.1/41.7
36.1/41.7
6.5/6.5
20.0/22.1
29.1/32.5
33.6/37.8
38.1/43.0
51.6/58.6
51.6/58.6
15/15
20/25
30/35
35/40
40/45
60/60
60/60
---
---
---
---
---
---
18/20.8
---
---
---
---
---
---
22.5/26.0
---
---
---
---
---
---
25/30
---
---
---
---
---
---
74.2/84.6
---
---
---
---
---
---
80 / 90
MBVB20DP1X00AB
HKTAN031
HKTA*051
HKTAN061
HKTA*081
HKTA*101
HKTAD151
HKTAD201
0/0
10.8/12.5
18.1/20.8
21.7/25.0
25.3/29.2
36.1/41.7
36.1/41.7
36.1/41.7
6.5/6.5
20.0/22.1
29.1/32.5
33.6/37.8
38.1/43.0
51.6/58.6
51.6/58.6
51.6/58.6
15/15
20/25
30/35
35/40
40/45
60/60
60/60
60/60
---
---
---
---
---
---
18/20.8
36.1/41.7
---
---
---
---
---
---
22.5/26.0
45.2/52.1
---
---
---
---
---
---
25/30
50/60
---
---
---
---
---
---
74.2/84.6
96.8/111
---
---
---
---
---
---
80/90
100/125
All ampacies noted above include air handler motor amps
Circuit 1: Single-phase for Air Handlers / Circuit 2: Three-phase for HKR3 Heater Kits
¹ Minimum Circuit Ampacity (Heater Amps + Motor Amps) X 1.25
² Maximum Overcurrent Protecon = 2.25 X Motor Amps + Heater Amps
* Revision level that may or may not be designated
C = Circuit Breaker Opon
--- indicates Not Required
• Only applicable when HKA kits are included in table
HKA meets the new UL1995 requirements for 15 and 20KW heaters
• MBVC and MBR models
Heat Kit Data
Heating kW Correction Factor
240 230 220 210 208
1.00 0.92 0.84 0.77 0.75
Mulply the 240-volt heang capacity by correcon factors.

6www.amana-hac.com SS-AMBVC SS-AMBVC www.amana-hac.com 7
Dimensions
Top View
Side and Front Views
MBVB12BP1X00 17½" 21" 26"
MBVB16CP1X00 21" 21" 30"
MBVB20DP1X00 24½" 21" 30"
MBVC_TOP_VIEWS
987654321
987654321
F
C
D
E
B
A
F
C
D
E
B
A
SC
CC
11.3"
11.1"
20.0"
10.9"
16.5"
10.3"
13.2"
11.3"
23.5"
SPECIAL CHARACTERISTICS: (REFER MSP 822-01 FOR DETAILS)
= CRITICAL CHARACTERISTIC REQUIRES AN INITIAL CPK OF 1.33 AND USE OF STATISTICAL PROCESS CONTROL.
= SIGNIFICANT CHARACTERISTIC REQUIRES AN INITIAL CPK OF 1.00 AND USE OF STATISTICAL PROCESS CONTROL.
INABILITY TO MEET THE REQUIRED INITIAL CPK VALUE WILL REQUIRE 100% INSPECTION.
COMPONENTS AND MATERIALS SPECIFIED HEREIN WILL ALSO CONFORM TO THE APPLICABLE SECTION OF GOODMAN MSP
860-01 WORKMANSHIP STANDARD.
CONFIDENTIAL PROPERTY OF GOODMAN MANUFACTURING COMPANY, L.P. OR ITS AFFILIATES NOT TO BE DISCLOSED TO
OTHERS, COPIED, OR USED FOR ANY PURPOSE EXCEPT AS AUTHORIZED IN WRITING. MUST BE RETURNED UPON DEMAND,
ON COMPLETION OF ORDER, OR OTHER PURPOSE FOR WHICH IT WAS LENT
GOODMAN MANUFACTURING COMPANY,L.P.
DRAWING TO BE INTERPRETED IN
ACCORDANCE WITH ASME Y14.100
TITLE
MBVC_DIMENSIONS
DIMENSIONS ARE IN INCHES
UNLESS OTHERWISE NOTED.
TOLERANCES UNLESS
OTHERWISE NOTED
ANGLES 1.5
.X .1
.XX .03
.XXX .015
HOLES : .005
TUBE CUT LG: .063
DWN: HCL-BS ENG: SCALE: NTS
DATE: CHK: SHEET: 1 OF 1
DWG.
NO. MBVC_TOP_VIEWS
21"
17½" 24½"
W"
H"
D"
10.9"
16.5"
4.0 (10.6 cm)
2.5" (6.35 cm) 2.5" (6.35 cm)
4.0 (10.6 cm)
10.3
5.8" (14.73 cm)
7.3" (18.54 cm)
17½"
4.0" (10.6 cm)
5.8" (14.73 cm)
7.3" (18.54 cm)
2.5" (6.35 cm)16.1" (40.89 cm)
11.3"
11.1"
20.0"
4.0" (10.6 cm)
21"
4.0" (10.6 cm)
5.8" (14.73 cm)
7.3" (18.54 cm)
2.5" (6.35 cm)19.6" (49.78 cm)
4.0" (10.6 cm)
13.2"
11.3"
23.5"
24½"

6www.amana-hac.com SS-AMBVC SS-AMBVC www.amana-hac.com 7
Wiring Diagram – Air Handler
TB3
TB4 TB7
DH/
Y2
GR CY
W
R1 2C
CIRCULATOR BLOW ER
1
1
CIRCULATOR
CIRCULATOR
RD
WH
TO
MICRO
AUX IN
AIR
230 VAC
PL1
SEE
NOTE 7
DEHUM
24 VAC
RD
4
BLWR
5
AIR
40 VA
8
40 VA TRANSFORMER, SEE NOTES 1 AND 14
L1
9
INDOOR
7
24 VAC
4
BK
1
5
BL
PL2
FUSE 3 A
208/230 VAC
GRND
ECM MOTOR
HARNESS
GRND
6
L2
6
L1
COM
BR
G
INTEGRATED CONTROL MODULE
W
BK
3
24V THERMOSTAT CONNECTIONS
COM
L2
DISCONNECT
BL
BK
TR2
C
3
GRND (4)
2
2
INDOOR
9
RD
TH2
+VDC (1)
Y
208 VAC
BK
RX (2)
RD
GRND
GRND
4
GN
R
8
5
EH1
RD
TX (3)
BL
3
GRND
ELECTRIC STAGE 2
RD
TRANSFORMER
ELECTRIC HEAT STAGE 1
GN
7
2
BLWR
EQUIPMENT GRND
TERMINAL
PLUG CONNECTION
LOW VOLTAGE FIELD
HI VOLTAGE FIELD
JUNCTION
HI VOLTAGE (230V)
PROT. DEVICE
INTEGRATED CONTROL
LOW VOLTAGE (24V)
FIELD SPLICE
INTERNAL TO
FIELD GRND
OVERCURRENT
0140A01418-A
1
2
3
CONDENSATE SWITCH
AUX OUT
EH2
RESISTOR
432
1
SEE NOTE 9
4 - GND
NC
SEE NOTE 6
GY PU WH GR BL RD BL RD GY BK
THERMOSTAT OUTDOOR UNIT
(SEE NOTE 13)
NOTES:
1. PLACE RED WIRES ON TRANSFORMER TERMINAL 2 FOR 208 VAC OPERATION.
2. MANUFACTURER'S SPECIFIED REPLACEMENT PARTS MUST BE USED WHEN SERVICING.
3. IF ANY OF THE ORIGINAL WIRES AS SUPPLIED WITH THIS UNIT MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL
HAVING A TEMPERATURE RATING OF AT LEAST 105°C. USE COPPER CONDUCTORS ONLY.
4. UNIT MUST BE PERMANENTLY GROUNDED AND CONFORM TO N.E.C AND LOCAL CODES.
5. TO RECALL THE LAST 6 FAULTS, DEPRESS THE RIGHT PUSH BUTTON FROM STATUS MENU ONCE AND THEN USE THE LEFT OR RIGHT
BUTTON TO REVIEW ALL THE FAULTS HISTORY.
6. 2 GREEN LEDS INDICATES CLIMATE TALK AND DATA AC NETWORK TRAFFIC STATUS. USE LEARN MENU FOR CLIMATE TALK NETWORK
RESET.
7. DISCARD CONNECTOR PL1 WHEN INSTALLING OPTIONAL HEAT KIT.
8. THE CONDENSATE ALARM SWITCH (AUX) TERMINALS CAN ONLY BE UTILIZED WITH COMMUNICATING MODE SETUPS AND MUST BE
ENABLED WITH COMMUNICATING THERMOSTAT. THIS FEATURE IS NOT OPERATIONAL WITH NON COMMUNICATING SYSTEMS.
9. USE N.E.C CLASS 2 WIRE.
10. SEE MANUAL FOR PUSH BUTTON OPERATION.
11. SEE MANUAL FOR 7-SEGMENT DISPLAY DIAGNOSTIC CODES AND MENU CODES.
12. SEE MANUAL FOR LEDS FUNCTIONALITY
13. R AND C TERMINALS (USED FOR 24VAC OUTDOOR CONTROL VOLTAGE) ARE OPTIONAL FOR 2 STAGE COMMUNICATING AIR
CONDITIONERS. R AND C TERMINALS ARE NOT TO BE USED FOR 2 STAGE COMMUNICATING HEAT PUMP APPLICATIONS.
FOR COMMUNICATING HEAT PUMP OR IF ONLY TWO THERMOSTAT WIRES ARE AVAILABLE, A SEPARATE TRANSFORMER MUST BE
INSTALLED IN THE OUTDOOR UNIT FOR CONTROL BOARD POWER.
1 AND 2 WIRES ARE REQUIRED FOR ALL APPLICATIONS. SEE INSTALLATION MANUAL FOR FULL SYSTEM WIRING EXAMPLES.
14. LOW VOLTAGE TRANSFORMER RATED 24VAC OUTPUT 40VA @AMP 1.67A
BL ---- BLUE
PK ---- PINK
GY ---- GRAY
WH ----WHITE
BR ---- BROWN
COLOR CODES:
OR ---- ORANGE
RD ---- RED
PU ---- PURPLE
YL ---- YELLOW
GN ---- GREEN
BK ---- BLACK
208 / 230 VAC
III
READ THE INSTRUCTIONS
CLASS III
III
SEE NOTES 1 AND 14
⚠Warning High Voltage: Disconnect all power before servicing or installing this unit. Mulple power
sources may be present. Failure to do so may cause property damage, personal injury, or death. ⚡
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

8www.amana-hac.com SS-AMBVC
Amana® is a registered trademark of Maytag Corporaon or its related companies and is used under license. All rights reserved.
Our connuing commitment to quality products may mean a change in specicaons without noce.
©2023 • Houston, Texas • Printed in the USA.
Accessories
Single Point Kit
X X
Can only be installed along with the above heat kits. This kit will t any MBVK blower as long
as a compable heat kit is installed in the unit.
MBVB Blower Performance Data Dipswitch Summary
S1 - S2* Cooling / HP Airow
A/B/C/D Airow D
S3 - S4* Cooling / HP / Aux Trim
(-10%, 0, +10%) No Trim
S5 - S6* Cooling Prole
A,B,C,D Prole 1
S7* Dehum
(on/o) O
S8 Unused On
S9 - S11 Heater Kit Kw O/O/O
* Valid only if the system is wired in legacy mode. If system is wired in the 4-wire communicang
mode, these funcons are selected via the user menu in the CTK01AA T-STAT.
Heat Kit Selection
MBVB12BP1X00 MBVB16CP1X00
X X X
X X X
X X X
X X X
X X X
X X X
X X X
X X X
X X X
--- --- X
This manual suits for next models
3
Table of contents
Other Amana Blower manuals