
17 RS1300004 Rev. 1
Troubleshooting Procedure
!WARNING
To avoid risk of electrical shock severe personal injury or death; disconnect power to unit before servicing, unless
testing requires power. Discharge capacitor through a 10,000 ohm resistor before handling. Wires removed during
disassembly must be placed on the correct terminals to ensure proper grounding and polarization.
NOTE: If a total restriction occurs on the discharge side
of the compressor, head-pressure and wattage
readings may be higher than normal – but only
while the compressor pumps the low side out
and the restriction resides between the
compressor and the first half of the condenser.
To diagnose for a restriction versus a refrigerant
shortage, first discharge the system. Then replace the
drier-filter, evacuate, and recharge with the specified
quantity of the correct refrigerant.
If, after doing so, the unit performs normally, three
possibilities exist: 1) refrigerant loss; 2) partially
restricted drier-filter; 3) moisture in system.
If, after doing so, the symptoms do not change, you may
have a restricted capillary, condenser or possibly a
kinked line. You must find the restriction and correct it.
What about gauge readings? If the restriction is on the
low side, suction pressure will probably be in vacuum
and head pressure will be near normal. If the restriction
is on the high side, suction pressure, again, will probably
be in vacuum. Head pressure will be higher than normal
– but only during the pump-out period, as noted above.
In any case it takes longer than normal (10 minutes) for
pressures to equalize after the compressor stops.
Symptoms of Air in System
The presence of air in a sealed system causes
inefficient cooling. Longer-than-normal compressor run
times result. Where enough air is present, the
compressor runs continuously and the system doesn’t
cool at all. Head pressure readings are abnormally high
because air does not mix with refrigerant but
nevertheless takes up space inside the system.
One way to determine if air is in the system is to read
the head pressure gauge when the unit is shut down
and evaporator and condenser are at the same
temperature. When these conditions have been
achieved, take the temperature of the condenser outlet
tube. Condenser-outlet temperature should be within 3°
or 4°F of what the Pressure-Temperature Relation
(PTR) chart shows for the given idle head pressure. If
the condenser-outlet temperature is substantially lower
than the PTR chart says it ought to be, air is present in
the system.
When air in the system is suspected, a thorough leak-
check is necessary. The leak, if it exists, must be
identified and properly sealed. Once the leak has been
sealed, the system must be discharged; the drier must
be replaced; the system must be evacuated and then
recharged with a correct amount of the specified
refrigerant.
Do not attempt to save time by merely purging air from
the system. Should you do so, you will have an
inefficient, incorrectly charged unit that will soon give
more trouble.
Symptoms Due to Improper Ambient Temperature
Lower ambient air temperature reduces the condensing
temperature and therefore reduces the temperature of
liquid entering the evaporator. The increase in
refrigeration effect due to operation in a low ambient
results in decreased power consumption and run time.
Lower ambients also reduce cabinet heat leak, a fact
partially responsible for reduced power consumption and
run time.
An increase in refrigeration effect cannot be expected
below a certain minimum ambient temperature. That
minimum temperature varies with the type and design of
the product. Generally, ambient temperatures cannot be
lower than 55°F without reducing operational efficiency.
Refrigerators installed in ambients below 55°F do not
perform as well because pressures within the system
are generally reduced and unbalanced. This means that
lower head pressures force less refrigerant through the
capillary, resulting in symptoms like those produced by a
refrigerant shortage. The lower the ambient
temperature, the more pronounced these symptoms
become. At a point where ambient temperature is lower
than the cut-in of the temperature control, the
compressor won’t run. Defrost drain taps freeze up
where ambient temperatures are below 32°F.
Conversely, the higher the ambient temperature, the
higher system head pressure must be in order to raise
high-side refrigerant temperature above that of the
ambient, condensing medium. In other words: head
pressures must rise as the ambient temperature rises.
Where ambient temperatures are too high, operating
efficiency is again reduced.
Heavy Heat Load
Increased heat loads result when an abnormally large
supply of foods is laid in, as is typical after the weekly
shopping. Other factors contributing to an increased
heat load include excessive door openings, poor door
sealing, failure of an interior light to shut off, etc.
An increase in heat absorbed by refrigerant in the
evaporator affects the temperature and pressure of gas
returning to the compressor. Compartment
temperatures, power consumption, discharge and
suction pressures are all affected by heat load.
Pressures will be higher than normal under a heavy heat
load.