
Remember the output power meter will only read half the power going out when
operating SSB. If the meter read 300 watts then it is close to 600 watts PEP, unlessthe
meter is a true active meter circuit.
If the amplifier is driven with exactly the same amount of power in SSB as it was during
tune up the output will be at least the same and normally more. Just the wattmeter can
not respond fast enough to give an accurate reading.
ALC Adjustment and Operation.
The ALC control ís another way to reduce the transceiver's output power.
Leave the ALC disconnected and tune the amplifier to the desired output level, not to exceed
maximum plate or grid current, or maximum output power.
ïhen connect the ALC line with the ALC adjust fully clockwise (facing the back of the amplifier).
Nexl lransmit with amplifier operating and adjust the ALC until the grid meter or output power
starts to drop. Stop at the point when the meter starts to drop.
The ALC is now set for the desired level of operation.
lncreasing the transceiver's power control should not make any change to the meters on
the amplifier or the drive power. This will verify the ALC is controlling the transceiver.
TROUBLE SHOOTING.
VSWR goes high on the output meter when tuning:
l. Try tuning the amplifier into a dummy load with the tuner in by-pass or direct.
If the amplifier tunes up ok with the dummy load connected, it could be the tuner, feed
line or antenna.
2, Place the dummy load at the output of the tuner and tune the antenna tuner into
the dummy load with amplifier in standby. Then tune the amplifier
If the VSWR reads ok with the amplifier
3. Place the dummy load at the end of the feed line (at the antenna end.). Measure
the VSWR with the amplifier in standby. If the VSWR is low then place the
amplifier into operate and measure the VSWR. If the VSWR is low then it would
have to be the antenna, unless the VSWR was cause by a loose connection.
Grid meter goes backward and the Ip reads forward with no drive, amplifier in standby.
I . 8l I A tube has a filament grid short. Try removing all tubes then insert.one in
at a time
2. If the tube arced then it could be a MOV shorted on the filament windins of
the transformer.
3. There could be a shorted .01 capacitor in the bias line to ground
Grid meter reads higher than normal with very little plate current.
l. D16 is shorted. It will also cause the plate and grid current meter to track
instead of moving in opposite directions.
Amplifier blow fuses on turn on.
l. Check the tubes for a short. Remove the connectors off the top of each tube
and let them hang in the air, not touching anything. The replace the fuse and turn on. If
it power up then there is a shorted tube.
2 Check the HV capacitors for shorts. Check rectiSring diodes for shorts.
http://www.classicinternational.eu
Authorized dealer: