AMIC OOT550-DL3B2 User manual

LPWA - LoRa
Outdoor LoRa Data Logger
OOT550-DL3B2
User Manual

Outdoor LoRa Data Logger
2
Chapter 1 Introduction........................................................................................................................................... 3
1.1 Introduction..............................................................................................................................................3
1.2 Contents List............................................................................................................................................4
1.2.1 Package Contents...........................................................................................................................4
1.3 Hardware Configuration ..........................................................................................................................5
1.4 LED Indication.........................................................................................................................................6
1.5 Installation & Maintenance Notice..........................................................................................................7
1.5.1 SYSTEM REQUIREMENTS.......................................................................................................7
1.5.2 WARNING....................................................................................................................................7
1.5.4 Product Information for CE RED Requirements..........................................................................9
1.6 Hardware Installation.............................................................................................................................10
1.6.1 Open the Top Cover....................................................................................................................10
1.6.2 Install Battery..............................................................................................................................12
1.6.3 Connecting to External Devices..................................................................................................15
1.6.4 Connecting USB cable for PC Configuration Tool.....................................................................24
1.6.5 Power On the OOT550 ...............................................................................................................25
1.6.6 Setup with Windows-based Configuration Tool.........................................................................27
1.6.7 Device Mount and Screw Back the Top Cover...........................................................................29
Chapter 2 Device Configuration.......................................................................................................................... 30
2.1 Device Status .........................................................................................................................................30
2.2 LoRa Configuration...............................................................................................................................31
2.3 I/O Configuration...................................................................................................................................35
2.4 Modbus Configuration...........................................................................................................................38
2.5 Event Configuration...............................................................................................................................40
2.6 System Configuration ............................................................................................................................42
2.7 CLI Console Log....................................................................................................................................44
Chapter 3 Commands for the LoRa Node............................................................................................................ 45
3.1 Command Basics ...................................................................................................................................45
3.2 Commands .............................................................................................................................................47

Outdoor LoRa Data Logger
3
Chapter 1 Introduction
1.1 Introduction
Congratulations on your purchase of this outstanding product: Outoor LoRa Data Logger. For IIoT applications,
AMIT LoRa Data Logger is absolutely the right choice. With built-in world-class LoRaWAN module, you can
easily deploy the LoRa Data Logger with LoRaWAN compliant LoRa Gateway / NS / AS for a public or private
LoRaWAN service.
The OOT550-DL is a cost-effective low complexity solution for simple data acquisition and wireless telemetry.
LoRa and LoRaWAN are optimized for low bandwidth IoT traffic over wide area to transmit data at low data
rates. It allows massive deployment of wireless IoT with carrier-level security. Thanks to the power saving
technology, the OOT550-DL has ultra-low power consumption which allows it to operate on a single battery
for years 1.
Main Features:
Simple device with various interfaces (AI / DI / RS485) for IIoT field data acquisition.
Transfer of field data to associated LoRa Network Server at pre-defined time interval, or on an event at
the site.
Internal battery-powered design for easy deployment; Low power consumption and work without
changing the battery for years.
Automatic issuing low battery power alerts to remote server for device or battery replacement.
Configuring the LoRa node via a PC with a convenient configuration utility.
Water-resist, dust-resist IP65 enclosure for installing in severe environment.
Before you install and use this product, please read this manual in detail for fully exploiting the functions of
this product.
1 The battery life time depends on actual usage (frequency of data acquisition and data uploading) of the LoRa Data Logger.

Outdoor LoRa Data Logger
4
1.2 Contents List
1.2.1 Package Contents
#Standard Package
Items
Description
Contents
Quantity
1
OOT550-DL3B2
Outdoor LoRa Data Logger
1pcs
2
Battery
1pcs
3
Cable Tie
2pcs
4
AI Jumper
3pcs
5
Water/Dust-proof Stopper
3pcs

Outdoor LoRa Data Logger
5
1.3 Hardware Configuration
Front View
M16 Water/Dust-proof Connectors,
with two-hole cable gland inserted

Outdoor LoRa Data Logger
6
1.4 LED Indication
LED Icon
Indication
LED Color
Description
LED
Device Status
Blue / Red
Steady OFF:Device is powered off.
Blue Flash per second: Device is boot up.
Red Flash: Battery Low.
Blue and Red Steady ON: Device is in Recovery mode, or FW
Upgrading.

Outdoor LoRa Data Logger
7
1.5 Installation & Maintenance Notice
1.5.1 SYSTEM REQUIREMENTS
Network Requirements
LoRaWAN compliant Gateway and Network Server
Configuration Tool Requirements
Computer with the following:
Windows®7 or Windows 10
An installed Ethernet adapter
A USB 2.0, or later for device configuration
1.5.2 WARNING
Only use the Battery that comes with the package or
the external DC Power Supply that complies to
device spec. Using a different voltage rating power
adaptor is dangerous and may damage the product.
DO NOT remove or repair the control board by
yourself. If the product is too hot or malfunctioning,
turn off the device and have it repaired at a qualified
service center.
Place the product on a stable surface, or screwed it
on a solid plate or wall.
Attention

Outdoor LoRa Data Logger
8
Federal Communication Commission Interference Statement
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may
not cause harmful interference, and (2) this device must accept any interference received, including interference that may
cause undesired operation.
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the
FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential
installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee
that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct
the interference by one of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
FCC Caution: Any changes or modifications not expressly approved by the party responsible for compliance could void the
user's authority to operate this equipment.
This transmitter must not be co-located or operating in conjunction with any other antenna or transmitter.
FOR PORTABLE DEVICE USAGE (<20m from body/SAR needed)
Radiation Exposure Statement:
The product comply with the FCC portable RF exposure limit set forth for an uncontrolled environment and are safe for
intended operation as described in this manual. The further RF exposure reduction can be achieved if the product can be
kept as far as possible from the user body or set the device to lower output power if such function is available.
FOR MOBILE DEVICE USAGE (>20cm/low power)
Radiation Exposure Statement:
This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment. This
equipment should be installed and operated with minimum distance 20cm between the radiator & your body.
FOR COUNTRY CODE SELECTION USAGE (WLAN DEVICES)
Note: The country code selection is for non-US model only and is not available to all US model. Per FCC
regulation, all WiFi product marketed in US must fixed to US operation channels only.

Outdoor LoRa Data Logger
9
1.5.4 Product Information for CE RED Requirements
The following product information is required to be presented in product User Manual for latest CE RED
requirements. 2
(1) Frequency Band & Maximum Power
1. Frequency Band for LoRa Connection
Band
Operating Frequency
Max. Output Power
EU868
863 - 870MHz
100 mW (20dBm)
(2) DoC Information
You can get the DoC information of this product from the following URL:
http://www.amitwireless.com/products-doc/
(3) RF Exposure Statements
The antenna of the product, under normal use condition, is at least 20 cm away from the body of user.
(4) Unit Mounting Notice
The product is suitable for mounting at heights <= 2m (approx. 6 ft), or in a cabinet.
Ensure the unit is fixed tightly to reduce the likelihood of injury due to exposure to mechanical hazards if
dropped.
(5) Manufacture Information
Manufacture Name: AMIT Wireless Inc.
Manufacture Address: No. 28, Lane 31, Sec. 1, Huandong Rd., Xinshi Dist., Tainan 74146, Taiwan (R.O.C.)
2 The information presented in this section is ONLY valid for the EU/EFTA regional version. For those non-
CE/EFTA versions, please refer to the corresponding product specification.

Outdoor LoRa Data Logger
10
1.6 Hardware Installation
Hereunder list the available H/W ports of OOT550:
•SIM Slot: 1* nano-SIM (4FF)
•Analog Input: 3* AI ports (AI1,AI2 supports 0-10V / 4-20mA; AI3 supports 0-20V / 0-40mA)
•Digital Input: 2* DI ports (isolated, “Logic 1”: 2V~25V, “Logic 0”: 0~1V or floating;
supports Pulse Counter, Dry Contact)
•Digital Output: 1* DO port (isolated, Non-Relayed Output, Maximum 24V/300mA)
•Field Bus: 1* RS-485 for Modbus RTU
•Configuration : 1* Micro USB port for device configuration
•Wake-up Port: 1* dedicated DI for external device wake-up triggering.
•Power Source : 4000mAh 3.6V Li-SOCL2 battery (ER18505, A Size), or
external 5V~12V DC power.
This section describes how to install and configure the hardware.
1.6.1 Open the Top Cover
The OOT550 series is design for universal data logging use. There are various interfaces for connecting to your
field devices, and enclosed with an IP65 grade enclosure. All the connection cables to the field devices must be
wired properly through the M16 connectors.
Therefore, prior to connecting and configuring the OOT550, you have to open the top cover to get access to
the control board.
Unscrew the four screws and remove the top cover to the side carefully.
You can see there are lots of hardware connectors available for you to configure. There are two spring-type
Terminal Blocks, a nano-SIM slot, Battery Stand, Power Socket and Switch, etc...

Outdoor LoRa Data Logger
11
Internal View
After removed the top cover, you can see all the available hardware connectors.
Note:
1. By default S2 (Power Switch) is in OFF state, and J6 (Power Source) is in BAT state.
2. Before proceed to the following H/W configuration details, be sure to keep S2 at OFF state till the moment
you finished the required configuration and need to Power Up the device.
3. The RESET button provides user with a quick way to reboot the device.
Status
LED
J1:
Micro-USB for
Device Config.
Nano-SIM
Socket
(reserved)
CON4:
16-pin spring-type
Terminal Block for I/Os
trigger
CON3:
2x3 headers for AIs.
w/o Jumper: Voltage
/w Jumper: Current
S2:
Power Switch
(ON/OFF)
CON2:
8-pin spring-type
Terminal Block for
RS485, ext. power,
wake-up
Battery
Stand
S1:
RESET
Button
J6:
Power Source
Jumper
Antenna
Cable
CON1:
Battery
Power
Socket
J2:
Console for
Device Config.
(reserved)

Outdoor LoRa Data Logger
12
1.6.2Install Battery
Step 1:
Insert the two cable ties and go through the battery stands.
Step 2:
Load the battery over the stands as the illustrated, and pull tightly for each cable tie.

Outdoor LoRa Data Logger
13
WARNING :
1. It is strictly forbidden to have the battery positive and negative short circuit,
charging, discharging, heating over 100 ℃, remove, anatomy, or may cause
explosion, combustion, internal acid leakage.
2. The Li-SOCL2 battery is an one-time battery. DO NOT re-charge, crush,
disassemble, the battery in any situation.
3. Discharged battery is a hazardous waste, and should be recycled or brought
to a hazardous waste disposal facility.
4. Battery Replacement: You can purchase a new (full power) battery and
replace it by yourself. The Battery Specification and Power pin must be
compliant to the Original Design:
A. 4000mAh 3.6V Li-SOCL2 battery (ER18505, A Size) with power cable.
B. Re-use the power connecter: Red pin for V+, and Black pin for GND.
C. Follow the Battery Installation procedure mentioned above.
Step 3:
Cut off the extra cable tie, and plug the power cable onto CON1 (Battery Power Socket).

Outdoor LoRa Data Logger
14
Li-SOCL2 Battery Specification
If you purchase the battery from 3rd-party, please make sure it comply to the following electrical
characteristics. Not only Nominal Capacity and Voltage, but also Max. Continuous Current andf Max. Pulse
Capacity specifications are important.

Outdoor LoRa Data Logger
15
1.6.3Connecting to External Devices
There are lots of available I/O interfaces for connecting the OOT550 data logger with external devices.
As indicated in the I/O pinout sheet, you can easily find out the pin location and connect to your devices with
appropriate conductive cables. However, there are only two dual-hole M16 water/dust-proof connectors for
you to route the conductive cables out of the enclosure. That is, up to four cables can be routed to connect
external devices.

Outdoor LoRa Data Logger
16
Run External cable to desired Connectors:
Step 1: a) Find a conductive cable with 15mm tinned terminals; b) Remove the external part of the M16
connector; c) Run the cable through the external parts as indicated below.
Step 2: a) Place the tinned terminal over the connector; b) Use a flathead screwdriver and push down the
clip; c) Insert the tinned terminal to very bottom; d) Release and verify the terminal is well locked.

Outdoor LoRa Data Logger
17
Screw back the External Parts of M16 Connector:
When you complete all the required hardware and software installation, and make sure it can work as what
you planned. You are ready to lock the cables and external parts of the M16 connectors.
Note:
1. Up to two cables can be run through the M16 connector. And to keep the IP65 water/dust-proof
performance, all the cable gland parts and also the stopper are required to be installed properly.
2. However, if you intend to run more than two cables through the M16 connector, or IP65 is not so critical for
the installation, you can decide not to put the cable glands, and skip step 1b) ~1d) for more IO flexibility.
Step 1: a) Just keep required length of cable inside the enclosure; b) Insert the first cable gland part; c)
Insert the second cable gland part; d) Insert the stopper if there is spare wire hole.
Verify all the insert parts are in positions.
Step 2: Place the last insert part of the M16 connector in position and fasten it clockwise direction.
You have to hold the wire to prevent it twisted while fastening the M16 external part.

Outdoor LoRa Data Logger
18
Connect to devices via AIs (Analog Input) :
The OOT550 provides 3 AI ports for connecting to those analog sensor/meters. To connect the device, you
have to identify the type of your device and properly connect and configure the OOT550 so that it can get the
correct readings from the connected devices.
AI1, AI2 supports either 0-10V voltage mode, or 4-20mA current mode analog signal; AI3 supports either 0-20V
voltage mode, or 0-40mA current mode analog signal.
Since the OOT550 can not detect what kind of device is connected to, not only hardware configuration (CON3,
CON4) is required, but also software configuration is mandatory.
CON3 is dedicated for AI configuration. There are 3 sets of jumper headers, one for each AI port (AI1, AI2, AI3).
Without Jumper : Voltage mode - (factory default)
With Jumper : Current mode - (You have to put the Jumper manually)
Pinout Definition @ CON4
Pin1
Pin2
Pin3
Pin4
Pin5
Pin6
Pin7
Pin8
3.6Vout
GND
AI1+
GND
AI2+
GND
AI3+
GND
Note: 3.6Vout @ CON4. 1 is only valid when external power source is applied. It is disabled for Battery power
source.
Analog Input Specification
Mode
AI1, AI2 Specification
AI3 Specification
Range
Precision
Range
Precision
Voltage Mode
0-10V
+/- 10mV
0-20V
+/- 20mV
Current Mode
4-20mA
+/- 20μA
4-20mA
+/- 40μA
The OOT550 is designed with 12-bit ADCs (Analog-to-Digital Converter), considering hardware scaling and 0.1%
resistance variation effects, the overall precision for the 0-10V is around +/-10mV.

Outdoor LoRa Data Logger
19
Example of AI Connection Diagram
If the signal range of your device will run out off the design spec. of OOT550, you have to add a certain scaling
circuit to prevent overflow readings and even damage the OOT550.

Outdoor LoRa Data Logger
20
Connect to devices via DIs / DO (Digital Input / Digital Output) :
The OOT550 provides 2 DI ports and 1 DO port for connecting to those digital sensor/meter devices. To
connect the device, you have to identify the type of your device and properly connect and configure the
OOT550 so that it can get the correct readings from the connected devices.
The DI port supports either Pulse counter mode, or just a Dry contact. Since the OOT550 can not detect what
kind of device is connected to, not only hardware configuration (CON4) is required, but also software
configuration is mandatory.
Pinout Definition @ CON4
Pin9
Pin10
Pin11
Pin12
Pin13
Pin14
Pin15
Pin16
DO+
DO-
DI1+
DI1-
GND
DI2+
DI2-
GND
Digital I/O Specification
I / O
Specification
Digital Input
(Isolated)
Trigger Voltage (high)
Logic level 1: 2V~25V
Normal Voltage (low)
Logic level 0: 0V~1V, or floating
Digital Output
(Isolated)
Non-Relay mode
Maximum 24V/300mA
(Depends on external device)
Example of Connection Diagram - DI