EXTROL PRO®is designed for closed, low temperature systems with a
maximum operating temperature of 200° F. The product can be used
in glycol applications and features a plastic liner that is compatible with
barrier and non-barrier tubing.
Pre-Installation
1. Visually inspect for any damage. Ensure expansion tank is sized
properly for the intended application (Figure 1: Boiler Application,
Figure 2: Radiant Application).
2. With tank empty of water, remove plastic cap from air stem (Figure 3).
3. Check precharge pressure and adjust if necessary, charging with air
to match boiler fill valve setting.
4. Replace cap and tighten snugly, ensuring the cap is flush against the
tank surface.
Installation
1. Drain the boiler system or isolate the area where the EXTROL PRO will
be installed.
2. Install the EXTROL PRO on the supply side of the boiler, on the
suction-side of the heating circulator(s) (Figure 4).
Mount tank vertically in downward position
only. Ensure the piping can support the entire
weight of the tank when full of water.
Do not install the EXTROL PRO on a dead-end
pipe or wherever air can collect. This can cause
corrosion and possible leakage.
3. Pressurize the system and check for leaks. Repair as necessary.
4. Restart the boiler system and check for relief valve discharge. If the
relief valve drips, the tank may be improperly charged or undersized.
NOTE: Although the EXTROL-PRO does not have to be installed at the
base of an air purger, this installation is recommended to reduce air
in the system and provide a compact installation. Some method of air
elimination is required to ensure an oxygen-free system.
Figure 2. Radiant Application
PLEASE READ THE FOLLOWING INSTRUCTIONS CAREFULLY FOR
IMPORTANT GENERAL SAFETY INFORMATION AND ADDITIONAL SPECIFIC SAFETY ALERTS.
VISIT www.amtrol.com TO VIEW HELPFUL VIDEOS.
Sizing based on: 15 PSIG fill; 30 PSIG relief valve; 120° F average temperature.
System filled with water. For glycol and solar applications, consult AMTROL Technical Support.
* Contact AMTROL Technical Support.
System
Supply
Flow-Check
Valve Circulator Air Purger
Air Vent
EXTROL Fill Valve Assembly
Boiler
System
Return
Inspection
Cap
Relief
Valve
Drain Valve
Figure 4.
Maintenance
A professional plumber should check the complete system, including
the expansion tank, yearly and more frequently as the system ages.
Checking the precharge allows a small quantity of air to escape and can
result in an insufficient air charge. Always check the precharge while
the tank is isolated and empty of water, and be sure to maintain the
proper precharge whenever the tank is inspected. Monitor the tip of the
inspection cap for discoloration (Figure 5) in addition to regular product
inspection. Contact the installer or a plumbing professional if inspection
cap is discolored; tank replacement required. Do not rely on cap as sole
indication of tank condition.
Warranty
EX-PRO Models: Seven (7) Year Limited Warranty
Visit www.amtrol.com for complete warranty details.
Figure 5.
Clear / White
Normal
Operation
Discolored
Replace
Tank
InSight®Service Indicator Cap
© 2022 Worthington Industries Inc. Part #: 9015-968 (02/22)
One or more features of this product are covered by U.S. patents, visit www.amtrol.com/patents for more information.
1400 Division Road, West Warwick, RI USA 02893
T: 800.426.8765 www.amtrol.com
Figure 1. Boiler Application
Sizing based on: 15 psig Fill; 30 psig Relief Valve; 180°F Average Temperature.
* See Extrol EX and SX Sizing.
Boiler
Net Output
in 1000’S
of BTU/Hr.
Type of Radiation
Finned Tube
Baseboard or
Radiant Panel
Convectors
or Unit
Heaters
Radiators
Cast Iron
Baseboard
Cast Iron
25 EX-15PRO EX-15PRO EX-15PRO EX-15PRO
50 EX-15PRO EX-15PRO EX-30PRO EX-30PRO
75 EX-30PRO EX-30PRO EX-60PRO EX-60PRO
100 EX-30PRO EX-60PRO EX-60PRO EX-60PRO
125 EX-60PRO EX-60PRO * *
150 EX-60PRO EX-60PRO * *
175 EX-60PRO EX-60PRO * *
200 EX-60PRO * * *
250 * * * *
300 * * * *
Feet of
Tubing
Nominal Pex Tubing Size
3/8" 1/2" 5/8" 3/4" 1"
1,000 EX-15PRO EX-15PRO EX-15PRO EX-15PRO EX-15PRO
5,000 EX-15PRO EX-15PRO EX-15PRO EX-30PRO EX-60PRO
7,500 EX-15PRO EX-15PRO EX-30PRO EX-60PRO *
10,000 EX-15PRO EX-30PRO EX-60PRO EX-60PRO *
14,000 EX-15PRO EX-30PRO EX-60PRO * *
18,000 EX-30PRO EX-60PRO * * *
22,000 EX-30PRO EX-60PRO * * *
30,000 EX-60PRO * * * *
FAILURE TO PROPERLY SEAL CAP WILL
RESULT IN LOSS OF PRECHARGE CAUSING
PRODUCT TO FAIL.
Figure 3.
Remove cap and
charge to system
fill pressure.
Replace cap and
tighten until flush
with tank.
Precharge Adjustment