2 InfiLink 200 Installation Guide
About the InfiLink 200
Without the InfiLink 200, the maximum cable length for all arms on
Infinet is 4,000 ft. at 19,200 baud (up to 32 local controllers). The In-
fiLink 200 amplification module lets you extend Infinet beyond 4,000
ft. or have more than 32 local controllers.
It is also an active hub that can connect up to 127 local controllers to the
Infinet in a star configuration.
Before you can install the InfiLink 200, you need to know some basic
information aboutit:itsdimensionsandenclosure,power requirements,
grounding requirements, and environmental requirements.
Note
This equipment generates, uses, and canradiate radio frequency energy
and if not installed and used in accordance with the instruction manual
may cause interference to radio communications. It has been tested and
found to comply with the limits for a Class A computing device
pursuant to Subpart J of Part 15 of the FCC Rules, which are designed
to provide reasonable protection against such interference when
operated in a commercial environment. Operation of this equipment in
a residential area is likely to cause interference in which case the user
at his own expense will be required to take whatever measures may be
required to correct the interference.
InfiLink 200 Dimensions
Each InfiLink 200 is 8.5 ×7.5 ×2.75 in. The unit is inside a hinged
aluminum enclosure that meets UL standards.