Anie BEINAT BX449F User manual

CONFORMITY
Installation
and user guide INSTALL IN SAFE
AREA, NO ATEX
EN 50270
EN45544-1-3
EN61010-1
ConformeEN60079-29-1
Reports issued by Eurofin Italia
Din omega modular Gas/Fire control unit 4 Conventional zones
BX449F V3
With a
maintenance program
Belonging to
BEINAT S.r.l. always attentive to the needs of the market and new technologies, has overhauled a previous
versatile control unit, BX449F, for GAS and/or FIRE detection for industrial applications. To which can connect
sensors to detect: Toxic / Explosive Gases, Oxygen, and to detect fire principles.
Gas detection
The control unit has two danger levels:
1st LEVEL, pre-alarm. This is set at 13% of L.E.L. (200ppm) for all sensors.
2nd LEVEL, main alarm. This is set at 20 % of L.E.L. (300ppm) for all snsors.
To facilitate event readings, the control unit has a front panel with 4 LEDs indicating which probe is currently being
monitored in rotation, and a display showing the gas concentration measured on each pass.
GAS configurations
Connection from 1 to 4 conventional sensors, for different types of GAS up to max 4 sensors, 1 for each zone.
Fire detection
To the BX449F you can connect up to 5 fire detectors per each zone, either temperature or optical smoke detectors,
through a balanced line:
Optical smoke detectors, Temperature, Velocimetric temperature
The control unit’s microprocessor checks the detectors and connection line efficiency, open or short-circuited.
When the sensors detect a fire, theyl switch the proper relay.
FIRE configurations
Each zone can be connected up to a Max 5 sensors, even mixed, Smoke or Temperature, for a total Max of 20.
Automatic recognition of the type of probe connected, be it GAS OR FIRE.
Configurations Mixed GAS FIRE
For each zone assigned, the detection of only GAS or FIRE can be connected without distinction
OXYGEN configurations
When the operation is selected to detect OXYGEN, other types of sensor cannot be connected.
OXYGEN ALARM for <Oxygen deficiency and> Oxygen Excess
For oxygen pre-alarm and main alarm levels, see references on page 5.
Maintenance TEST.
With special measures, the function can be enabled to exclude the alarm relay for a maximum duration of 60
minutes. This allows the technician to perform all functions without having to interrupt the gas flow or activate sirens
Important: Assembly / maintenance of the appliance must be carried out by qualified personnel
and in accordance with applicable laws and regulations.
The manufacturer assumes no responsibility for the use of products that have to comply with
particular environmental and / or installation standards.
Important note
Before connecting the equipment, it is recommended that you read the instruction manual carefully
and keep it for future reference. It is also recommended to perform the electrical connections
correctly as per enclosed drawings, observing the instructions and the Standards.
N.B. Refer to the documentation in all cases where the symbol is on the side
Channel: Beinat gas solutions
Electricconnectionsalsoavailableon

Page 2
90 mm
45 mm
37 mm
90 mm
45 mm
159 mm
FaultMain AlarmPre Alarm BX449F probes battery
RESET TEST
Explosive Toxic
000LEL
ppm
1 2 3 4
OVER LOAD
1
2
3
4
OpenLine
CloseLine
FIRE
Alarm
Precautions
CHECK the integrity of the unit after having removed it from the box.
Check that the data written on the box correspond to the type of gas used.
When doing the electrical connections, follow the drawing closely.
Any use of the detector for purposes other than the intended one is considered improper,
and as a result of which BEINAT S.r.l. therefore disclaims any responsibility for possible
damages caused to people, animals or objects.
IMPORTANT: the functional test must not be carried out with the gas tap open as this does not guarantee
sufficient concentration to activate the main alarm.
TERMS and EXPECTATIONS: The installation of the BX449F control unit, its ordinary and extraordinary
maintenance, every six months, and its out of service removal at the end of the functional life guaranteed by
the manufacturer, must be carried out by authorized or specialized personnel.
Do not allow it to become wet.
The unit can be seriously damaged as it is not waterproof so when immersed in water or exposed to high
humidity levels.
Do not drop it.
Heavy knocks or falls during transportation or installation can damage the appliance.
Technical Specifications
Main power ........................................................................................... 110/240VAC 50/60Hz ±10%
Insulation ..................................................................................................................... Class II
Secondary Power Through Battery Max 2,2 Ah (Optional) ........................................................ 12 V ±10%
Battery charger max. 2.2 Ah ..................................................................................................... Controlled
Power demand ....................................................................................................... 11W max. 230 VAC
Power demand ........................................................................................................ 6W max. @ 12 VDC
Range of the contacts on the gas pre-alarm, alarm and fault relay ............................... 10A 250 VAC resistive
Range of the contacts on the fire alarm relay ............................................................ 10A 250 VAC resistive
Detection
Pre alarm ......................................................................................... 13% of L.E.L. or 200 ppm for CO
Final alarm .............................................................................. Set to 20% of L.E.L. or 300 ppm for CO
The LEL is calcuaded for Gas Methane .................................................................... 5000 ppm = 5% V/V
Data refresh ............................................................................................................................ 2 ms
OXYGEN alarm ............. <Oxygen deficiency,> Excess Oxygen ......................... see thresholds on page 5
Monitored events .................................................................................... Through backlit color display
Zones ............................................................................................................................................ 4
Number of connectable gas sensors ......................................................................... 4 (1 for each zone)
Types of conventional gas sensors ....................... Semiconductor, Catalytic, Electrochemical cell, Pellistor
Number of connectable fire sensors ....................................................................... 20 (5 for each zone)
Types of fire sensors connectable ......................... Optical smoke - fixed temperature - increment temperature
Micro-switches to include or exclude the gas sensors, Exclusion only for CO ....................... 1 for each zone
Microswitches to select the OXYGEN detection ................................................... ................ incorporated
Microswitches to display ............................................... ......................... Over Range and Under Range
Type of faults detected by fault circuit ..................................................... Interruption, short circuit, or wear
OVER LOAD Check .....................................................................................................1 for each sensor
OVER LOAD Check ............................................................................................................ 1 for battery
Input signal GAS................................................................................................. 4 ÷ 20 mA on 220 Ohm
Input signal FIRE....................... 2.2 VDC at rest, 8.7VDC in alarm, 13.92 VDC with short-circuited cables
Functioning temperature ................................................................................................. -10°C ÷ +60°C
Waiting, blinking time (warm-up) ................................................................................. About 2 minutes
Manual test ............................................................................................................................. Built in
Max. distance between sensors and unit ..................................................................................... 100 m
Max. distance between battery and unit.......................................................................................... 0,5 m
Cable diameter to connect the senors ....................................... .................................................. 1 mm2
Connection: The cable of connection of the sensor must not be installed together with the power cables.
Otherwise, make sure to use a shielded cable
Omega-type size DIN EN 50092 9 modules ................................................................................. 158*90*58
Degree of protection .................................................................................................................... IP20

Protec. Zone Detected Working Automatic
Application in:
Domestic: family accommodation. Local boilers up to 70 kW-h
Tertiary Areas: Large Rooms Boilers, Workshops, Material Deposits, Industrial Kitchens, Large Buildings, Buildings.
Zone 2 - Mixed IP66 ATEX: High probability of escape, high risk locations, premises for which applicable regulations apply.
Zone 1 - Hazardous Area, High Risk Hazards, Rooms for Which Regulations, Tanks, Control Valves are in force.
Probe Sensor Degree Suitable for Gas Range Output Precis. Calibration Relay
FIREDETECTORS
RF500 Optical Smoke Detection - ECO EC500 Series Optical Smoke Detection
RF570 Fixed Temperature Detection at 70 ° C - ECO EC500 Series Fixed Temperature Detection at 70 ° C
RF540 Increased Temperature Detection - ECO EC540 Series Increased Temperature Detection -
ZF300 Universal socket - Series ECO ZFC200 universal socket - Series ECO ZFRC250 Universal socket with relay
SG500 Ca talyt ic I P 3 0 Domestic Use C H 4 - LP G 0÷100% LEL 4÷20 mA ±5 % N O N O
SG544 Ca talyt ic I P 4 4 Tertiary C H 4- L P G 0÷100% LEL 4÷20 mA ±5 % N O N O
SGM595 Catalytic I P 5 5 Tertiary See catalogue 0÷100% LEL 4÷20 mA ±5 % Y e s N O
SGM595/A Catalytic I P6 6 Zone 2 See catalogue 0÷100% LEL 4÷20 mA ±5 % Y e s N O
SGM533 Catalytic I P 5 5 Tertiary See catalogue 0÷100% LEL 4÷20 mA ±5 % Y e s Y e s
SG800 Catalytic I P6 6 Zone 2 See catalogue 0÷100% LEL 4÷20 mA ±5 % Y e s Y e s
HCF100 SemiCondut I P 5 5 Tertiary F R E O N 0÷300% ppm 4÷20 mA ±5 % N O Y e s
SG895 Pellistor ATEX Zone 1 See catalogue 0÷100% LEL 4÷20 mA ±5 % Y e s N O
SG580 Catalytic I P6 6 Zone 2 See catalogue 0÷100% LEL 4÷20 mA ±5 % Y e s N O
SGF100 Catalytic I P6 4 Zone 2 Methane 0÷100% LEL 4÷20 mA ±5 % Y e s Y e s
SGF102 Catalytic I P6 4 Zone 2 L P G 0÷100% LEL 4÷20 mA ±5 % Y e s Y e s
SGF104 OpticalFluores I P 6 4 Zone 2 Ox yg en In % 4÷20 mA ±5 % Y e s Y e s
SGF106 SemiCondut I P 6 4 Zone 2 F R E O N 0÷300% ppm 4÷20 mA ±5 % Y e s Y e s
SGF108 ElectrochemicalIP64 Zone 2 H 2 S 0÷300% ppm 4÷20 mA ±5 % Y e s Y e s
SGF110 ElectrochemicalIP64 Zone 2 C O 0÷300% ppm 4÷20 mA ±5 % Y e s Y e s
SGF112 Catalytic I P6 4 Zone 2 Hydrogen 0÷100% LEL 4÷20 mA ±5 % Y e s Y e s
CO100r ElectrochemicalIP55 Tertiary C O 0÷300% ppm 4÷20 mA ±5 % Y e s Y e s
CO100Ar ElectrochemicalIP66 Zone 2 C O 0÷300% ppm 4÷20 mA ±5 % Y e s Y e s
SG800duct Catalytic I P6 6 Zone 2 C H 4 L P G 0÷100% LEL 4÷20 mA ±5 % Y e s Y e s
CO200duct ElectrochemicalIP66 Zone 2 C O 0÷300% ppm 4÷20 mA ±5 % Y e s Y e s
Page 3
The installation of the detector does not exempt from the compliance with all regulations concerning the characteristics,
installation and use of gas appliances. The ventilation of the spaces and the elimination of combustion products are described
in the UNI norms according to ART. 3 LAW 1083 / 71 and relevant legal provisions.
Gas
1) Put out all free flames.
2) Close the main gas tap or the LPG cylinder tap.
3) Do not turn any lights on or off; do not turn on any electrical device or appliance.
4) Open windows and doors in order to increase ventilation.
If the alarm stops, its cause must be found and the relevant consequent measures taken.
If the alarm continues and the cause of gas presence cannot be found or removed, abandon the building
and call the emergency services when outside (fire department, distributors, etc.)
IMPORTANT: lproof operation should not be carried out with the gas tap since this does not guarantee a
sufficient concentration to activate the alarm.
Fire
*Keep calm
*Open the windows and request assistance
*Do not turn lights on or off, do not operate electrically powered equipment and devices
*If possible, press the nearest emergency button.
*If possible use the nearest fire extinguisher, do not use foam extinguishers or water near electrical devices
or directly on switchboards.
*If the fire developed in an environment, get out, closing the door.
*If the fire is in another room and the smoke makes impracticable stairs and corridors, close well the
doors and try to seal fissures using possibly wet cloths.
*If the smoke makes breathing difficult, ffilter the air through a handkerchief, (better if wetted), lie on
the floor (ithe smoke tends to rise to the top).
*If the alarm stops, is necessary to identify the cause that provoked and act accordingly.
*If lthe fire continues and the cause is not vacate the building and abandon the building and call the emergency
services when outside
WARNING! Actions to be taken in case of alarm

- Power supply 110/240 VAC
- Controls up to 4 remote sensors, referred to Gas
- Manages explosive and toxic gases.
- Controls up to 20 remote sensors, referred to Fire
- Manages smoke and temperature sensors
- Manual alarm managed by remote button
- Various possibilities of parameter configuration
- Status indications with LED
- Output signals in alarm supplied via 2 relays, referred to gas
- Output signals in alarm supplied via 1 relay, referred to fire
- Fault output signals supplied via 1 relay, referred to gas and fire
- wall support 6 DIN modules.
- Conforms to the operating regulations EN60079-29-1
The BX449F is a control unit capable to control the concentration of gas up to 4 input channels, each of
which can be connected via a 4-20 mA communication to a toxic or explosive gas detection/measurement
device. The control unit is built with the following I/O interfaces.
page 4
Instructionmanual
{a} OVERVIEW
{b} GENERAL DESCRIPTION
1) Group of two switches.
DIP-SWITCH 1. Used to enable the OXYGEN DETECTION. ON ENABLED, OFF DISABLED.
In this condition the display turns blue and the LEDs (6 and 7) "Explosive and Toxic" turn off. OTHER TYPES OF
DETECTION ARE NOT POSSIBLE
DIP-SWITCH 2. Used to enable the deadband zone suppression for all sensors
Setting this two switch ON or OFF it is possible to enable or disable the suppression of the signaling of any under
range in the input signal at the corresponding input.
Instead, over ranges will always be reported.
The condition is signaled by the flashing of the "Explosive Gas" LED of the corresponding input. (7)
In this case, pressing the "TEST" button you will nsee that the detection starts at minus 29 ppm.
2) Group of three switches.
DIP-SWITCH 1. RELAY MODE. Used to select the relay working mode: Continuous or Pulsed
ON: PULSED - OFF: CONTINUOUS.
DIP-SWITCH 2. MEMORY LOG. Used to enable or disable memory logging.
ON ENABLED, OFF DISABLED. Warning! It is possible to disable the function only for the toxic gas detection
DIP-SWITCH 3. POSITIVE SAFETY. Used to select positive safety.
ON ENABLED, OFF DISABLED.
Main AlarmPre Alarm BX449F probes battery
RESET TEST
Explosive Toxic
000LEL
ppm
1 2 3 4
6
5
2
4
811
OVER LOAD
1
2
3
4
OpenLine
CloseLine
FIRE
Alarm
15
1
13
2under Range
1oxygen
14
Fault
sensor 1
sensor 2
sensor 3
sensor 4
3positive safety
2memory on/off
1working mode
7
9
12
3
10 16
Control unit from 1 to 4 conventional sensors BX449F Rev. 3
DIP-SWITCH of the deadband suppression of the sensor 1 and 2

3) Group of four double switches to select sensor and type of gas.
DIP-SWITCH 1. Sensor 1 - DIP-SWITCH 2. Sensor 2 - DIP-SWITCH 3. Sensor 3 - DIP-SWITCH 4.
Sensor 4
Setting the first switch of each group to ON or OFF enables or disables the corresponding input.
Setting the second switch of each group to ON or OFF switches to detect from explosive gas to toxic.
Depending on the type of gas, appears on the display LEL for explosive gases or ppm for toxic gas and the
corresponding LEDs light up (6/7)
WARNING! When a sensor is excluded, all the memories will be restored.
5) RESET BUTTON
A "RESET" button allow the user to cancel the events that occurred and are contained in the memory by an
intentional manual reset action.
Warning!
Pressing the RESET button once only resets the alarm and fault memories.
Pressing three times in succession restarts the entire system.
000
1 2 3 4
LEL
0 13
1 2 3 4
LEL
020
1 2 3 4
LEL
fau
1 2 3 4
LEL
4) TEST BUTTON, to check the operation of the entire system, TOXIC Gas
Press the "TEST" button its displays the progressive increase in the ppm followed by the
number of the monitored sensor.
When the pre-alarm of 200 ppm is reached, the display changes color to red, the preset relay
switches its status and the buzzer emits an intermittent low frequency sound, the corresponding
LED (13) lights up and the sensor number stays for a few seconds.
Keeping the button pressed, the in ppm increases until it reaches the main alarm of 300 ppm,
the preset relay switches its status and the buzzer emits an intermittent high frequency sound,
the corresponding LED (12) lights up and the number of the sensor stays for a few seconds.
Continuing to hold the% in ppm button increases until reaching the Over Range FAULT
Releasing the "TEST" button turns off the lights and stops the acoustic alarm
000
1 2 3 4
ppm
200
1 2 3 4
ppm
300
1 2 3 4
ppm
fau
1 2 3 4
ppm
4) TEST BUTTON, to check the operation of the entire system, OXYGEN Gas
Press the "TEST" button the control unit starts in alarm on the red Display appears 00.0
and you see the progressive increase of% of oxygen, followed by the number of the monitored
sensor.
When the pre-alarm of 19.5% of oxygen is reached, the preset relay switches its status and
the buzzer emits an intermittent low frequency sound.
Continuing to keep the button pressed, the oxygen percentage increases up to the percentage
of oxygen 20.9%; Ideal percentage for a civil environment.
When 22.5% is reached, it enters the pre-alarm condition, the preset relay switches its
status and the buzzer emits an intermittent low frequency sound.
When 23.5% is reached, it enters the alarm condition, the preset relay switches its status
and the buzzer emits an intermittent high frequency sound.
Keeping the TEST button pressed, the% of the LEL increases until it reaches the Over Range
FAULT
Releasing the "TEST" button turns off the lights and stops the acoustic alarm fau
1 2 3 4
%
22.5
1 2 3 4
%
23.5
1 2 3 4
%
20.9
1 2 3 4
%
19.5
1 2 3 4
%
00.0
1 2 3 4
%
4) TEST BUTTON, to check the operation of the entire system, EXPLOSIVE Gas
Press the "TEST" button and its displays the progressive increase of the % of the LEL followed
by the number of the monitored sensor.
When the 13% of LEL of the pre-alarm is reached, the display changes color to red, the preset
relay switches its status and the buzzer emits an intermittent low-frequency sound, the
corresponding LED (13) lights up and the sensor number stays for a few seconds.
Continuing to keep the button pressed, the % of gas increases up to the 20% of LEL of the
main alarm, the preset relay switches its status and the buzzer emits an intermittent high
frequency sound, the corresponding LED lights up (12) and the sensor number stays for a few
seconds.
Keeping pressed the button of the% of the LEL will go up until you reach the Over range FAULT
Releasing the "TEST" button turns off the lights and stops the acoustic alarm
page 5

6) TOXIC GAS LED selection .
Turning on, this LED indicates that the corresponding input is configured to detect toxic gases.
7) EXPLOSIVE GAS LED selection .
Turning on, this LED indicates that the corresponding input is configured to detect explosive gases.
WARNING! The flashing of this LED can also indicates the presence of under/over range entering the
corresponding input.
8) LED OVERLOAD BATTERY
This LED lights up when there is a short circuit or excessive absorption in the backup battery supply lines.
9) LED OVERLOAD SENSOR
This LED lights up when there is a short circuit or excessive absorption in the sensor supply lines.
10) Color backlit display to control all functions.
a) The battery icon turn on when the BX449F is powered by an external battery.
The battery icon also indicates the charge status of the battery , when itflashes the battery is low.
b) The % symbol on the display is reserved for oxygen detection.
c) The numbers indicate the detected gas concentration or mean some
warnings.
d) The numbers from 1 to 4 represent the sensors. These light up every
2 seconds.
e) The ppm turn on when the sensor is detecting toxic gas.
f) The LEL turn on when the sensor is detecting explosive gas.
g) The clock, the timing icon turns on when the control unit is in the Warm
up phase, the display starts the count down.
11) FAULT LED. This LED blinks when one of the connected sensors is faulty, if there is an interruption in the
cable connection, or if an error was made during wiring.
The sensor can be identified by reading on display the number from 1 to 4.
When this LED is on, the device is no longer capable of detecting, and stops.
To reactivate the device, the damaged probe must be repaired or disabled using the internal micro-switch, and
then the RESET button must be pressed. (See chapter on page 6)
12) LED MAIN ALARM
This LED starts to flash when the gas concentration level reaches the main alarm threshold (20% LEL for
explosive gases, 300 ppm for toxic gases).
This signal is the "latching" type and maintains its status until the "RESET" button is pressed, for compatibility
with the current performance standards.
13) LED PRE-ALARM
This LED lights up when the gas concentration level reaches the second pre-alarm threshold (13% LEL for
explosive gases, 200 ppm for toxic gases).
This signal is the "auto-reset" type.
14) SENSORS. This number represents the gas sensor connected from 1 to 4.
000 all ope clo
Normal condition
The display with color
green, represents an
absence of fire detection
Fault condition
The display shows that
the connection line is
short-circuited or that
the sensor is fault
The BX449F , in addition to detecting various gas types, is also built for fire detection
Up to 5 fire detectors can be connected to each zone via a balanced line up to a maximum of 20 detectors,
Smoke optics, Temperature, Velocimetric temperature
The microprocessor of the control unit controls both the efficiency of the detectors and the connection
line, open or short-circuited.
If necessary in case of fire or fault by switching the appropriate relay.
15) Section reserved for Fire detection.
Fault condition
The display shows that
the connection line is
open, or thatthe
sensor is fault
Alarm condition
The display with red
color represents a fire
alarm. Check from the
display in which area
e
000
cf
ppm
LEL
a
1 2 3 4 d
%
b
g
page 6
FIRE
1 2 3 4

- FAULT RELAY: this "latching" relay switches when there is an error signal from the connected sensor (see
image below).
- PRE-ALARM RELAY: this "autoreset" relay switches when the detected gas concentration exceeds the second
pre-alarm threshold.
- MAIN ALARM RELAY: this "memory" relay switches when the detected gas concentration exceeds the main
alarm threshold.
WARNING!
All relay outputs of the control unit are voltage free.
The maximum range of such contacts is specified in the next chapters.
btn
16) External manual alarm button.
The control unit is designed to be connected to a manual alarm button.
Pressing the button the control unit will go directly into alarm even when it is in programming
or warm up status; Closing all the auxiliaries connected to it.
When pressed, BTN appears on the display and turns red.
page 7

ELECTRICAL CONNECTION
- Terminals 1, 2 and 3: Main power supply
- Terminals 4 and 5: Fault relay contacts
CNC
NO CNC
NO
CNC
NO
1 2 3 4 5 6 7 8
GAS Main Alarm Fire Main Alarm
Pre-Alarm
C
NC
NO
PH N 4 5
Fault
Power supply
110/240 VAC
12V
+ +
Optional
R1 R2 R3 R4
1 2 3 4 5 6 7 8 9 10
3 2 1
Sensor 1 3 2 1
Sensor 2 3 2 1
Sensor 3 3 2 1
Sensor 3
- Terminals 1 and 2: GAS pre-alarm threshold relay contacts
- Terminals 3,4 and 5: GAS main alarm relay contacts
- Terminals 6, 7 and 8: Main alarm relay contacts
a) Connect terminal 1 to ground, terminal 2 to phase, terminal 3 to neutral.
b) Power the system only when all the parameters have been configured.
c) Connect the desired utilities to the output relays described above according to your needs.
Then connect the sensors and the battery (optional) to the signal terminal block
The signal terminal block for the GAS detection (previous figure) is composed as follows:
- Terminals 1 and 2: Optional back-up battery connection.
- Terminals 3 and 4: Sensor power supply. The voltage is generated by the control panel.
- Terminals 5, 6, 7 and 8: Connection return signal of 4-20 mA GAS sensors.
- Terminals 9 and 10: Connection of the optional manual alarm button.
WARNING! The optional battery is charged directly by the control unit.
This control unit can connect a maximum of 4 sensors.
Each conforms to the 4-20 mA current loop system on this terminal block.
Connect the sensors as shown in the figure
page 8
{c} OPERATING INSTALLATION INSTRUCTIONS
WARNING!
The installation parameters modification must be performed by qualified personnel
Be sure to disconnect the controller from the power supply before making changes to
the connections

The signal terminal block for the FIRE detection (previous figure) is composed as follows:
- Terminal 1 and 2: Optional back-up battery connectione.
- Terminal 4: Positive detector power supply. The voltage is generated by the control unit.
- Terminals 5, 6, 7 and 8: Connection of fire detectors return signal
- Terminals 9 and 10: Connection of the optional manual alarm button.
WARNING! The optional battery is charged directly by the control unit.
This control unit can connect a maximum of 5 fire detectors for each zone.
Each conforms to the 4-20 mA current loop system on this terminal block.
Remember to set the end of line resistance from 1K2
12V
1 2 3 4 5 6 7 8 9 10
+
Optional
+Z1 Z2 Z3 Z4
12
3
4
12
3
4
12
3
4
12
3
4
12
3
4
12
3
4
12
3
4
12
3
4
End of line resistance 1K2End of line resistance 1K2
1 2 3 4 5 6 7 8 9 10
12V
+
Optional
+R1 R2 R3 R4
1
3
512
3
512
3
512
3
5
12
3
5
2
End of line resistance 1K2
FIRE DETECTORS SERIES "ECO"
FIRE DETECTORS SERIES "NORMAL"
page 9

SELECTION OF THE TYPE OF GAS MONITORED BY EACH PROBE
The BX449F is fitted with four micro-switches in order to select the type of gas that the connected probes should
monitor.
The LEL explosive gas reading is obtained by shifting the switch to ON.
The ppm toxic gas reading will be obtained by shifting the switch to OFF.
ACTIVATION AND DEACTIVATION OF THE SENSORS
Through Micro switches on the control unit can enable or disable the 4 Zones.
You can connect up to 4 sensors GAS (1 for each zone)
Or, you can connect up to 20 FIRE detectors (5 for each zone)
Mixed connections Gas Fire
In the configuration Mixed Gas Fire every single zone can be connected indistinctly with:
only GAS
only FIRE.
The recognition of the gas or fire detectors takes place automatically
N.B. The microswitches are also used for disabling the sensor in case of fault.
page 10
Micro-switches (1) to enable or to disable the sensors.
Position ON enabled - Position OFF disabled
Zone 1 Zone 2 Zone 3 Zone 4
Selection of the type of gas monitored by each probe
The BX449F is fitted with four micro-switches in order to select the type of gas that the connected probes should
monitor.
The LEL explosive gas reading is obtained by shifting the switch to ON.
The ppm toxic gas reading will be obtained by shifting the switch to OFF.
Zone 1 Zone 2 Zone 3 Zone 4
Micro-switches (2) to select the type of gas monitored
Position ON reading in LEL - Explosive gas
Position OFF reading in ppm - Toxic gas

Switch 1 - the main alarm relay Working Mode.
In the ON (impulse) position, the relay remains closed for 3 seconds, and then disenergizes afterwards.
In the OFF (continuous) position, the relay remains closed until the RESET button is pressed.
Switch 2 – Alarm logging maintenance, reserved for toxic gases
By setting the micro-switch to ON, the device WILL LOG the alarm, maintain the relay closed, and the main
alarm LED will blink, until the RESET button is pressed.
By setting the micro-switch to OFF, the device WILL NOT MAINTAIN the alarm memory and the relay switches
off when the connected sensor no longer detects gas.
INCOMPLIANCE WITH STANDARDS EN 60079-29-1 ITHIS FUNCTION IS ENABLED ONLY when you select the toxic gas
detection reading in "ppm"
Switch 3 – Selection of the positive safety
In the ON position, the positive safety function is ENABLED.
In the OFF position, the positive safety function is DISABLED..
Switch 1 - detection selection only for OXYGEN
ON: The detection function for oxygen is enabled; This function applies to all 4 zones
OFF: The detection function for oxygen is disabled
Switch 2 - Exclusion or disabling of the neutral range
ON: the under range reading is enabled
OFF: the under range reading is disabled
page 11
Zone 1 Zone 2 Zone 3 Zone 4
Micro-switchesi 1Working mode of the Main alarm relay
Micro-switches 2Alarm memory logging referred to co
Micro-switches 3Positive Safety
Zone 1 Zone 2 Zone 3 Zone 4
Microswitches 1only OXYGEN operating selection
Microswitches 2 Exclusion or disabling the neutral range

{f} TEST
Once activated, the control unit starts warm up for 100 seconds.
In this phase all the LEDs flash, waiting for the connected probes to go into full speed.
The power LED flashes until the warmup done.
Once started, the control unit enters detection mode: the power LED is on, even with the LEDs of the type
of gas selected on the zones enabled, based on the configuration of the DIP-SWITCHES.
It is therefore possible to carry out a first check of the system by pressing the test button: keeping this
button pressed, the control unit simulates a concentration of gas gradually increasing from the enabled sensors,
and it is therefore possible to control the switching on and off of the LEDs and that all switch relay, enabling
the loads connected to them.
page 12
After making all the connections and configurations, the system can be powered
WARNING!
> This control unit is NOT built for installation in ATEX classified areas
> To meet the requirements as a control unit according to the standard EN 60079-29-1: 2016, the
DIP switches on the control unit must be set to: SW2.1: ON, SW2.2: OFF, SW3.2: ON, SW4.2: ON.
> All the wiring of the remote sensors must be made using wires with a minimum section of 1.5
mm2 and no longer than 25 m. Do not use the same conduit for signal and power cables.
> In case of installation in the presence of strong EMC disturbances, the shielded cables use is
strongly recommended. The screen must be connected to the 'Gnd' terminal of the interested
area only on the side of the control unit.
> The appliance must be connected to the power supply by means of a switch capable of
disconnecting the poles in compliance with current safety standards and with a contact
separation of at least 3 mm in all poles.
> The installation and electrical connections of this appliance must be carried out by qualified
technicians and in compliance with the current technical and safety standards.
> Be sure to turn off the power before wiring the device.
> Safety depends on the installer (whose responsibility is to set up a detection system in
compliance with existing standards, both European and national) to choose the correct type of
loads to be connected to the control unit and the correct configuration of the system parameters.
In case of doubt, please contact the distributor.
{d} OPERATIONAL LIMITATION
* The response time of the entire system is determined by the response time of all parts of the
equipment within the gas detection system.
The maximum delay time of a special status in case of transmission errors until insertion.
01. This device can be set for explosive, toxic gases and fire
02. For transverse sensitivities refer to the remote sensor user manual.
03. Response time T90: 1 second *
04. Temperature operating range: -10° C ÷ + 60° C
05. Humidity operating range: 0 ÷ 90% RH not condensed
06. Pressure operating range: 800 ÷ 1100 hPa
07. Power supply: 110/230VAC 50/60Hz
08. Absorption: 11W
09. Electrical wiring: see paragraph (c)
10. Batteries: max 2,2 Ah
11. Sample scope: Not applicable
12. Warm-up time: 100 seconds
13. Stabilisation time: not applicable
14. Contact rating: 10A 250V
15. Pre-alarm range 1st interval: for explosive gases set at 8% of LEL for toxic gases set at 120 ppm
16. Pre-alarm range 2nd interval: for explosive gases set at 13% of LEL for toxic gases set at 200 ppm
17. Alarm range 1s threshold: for explosive gases set at 20% LEL for toxic gases set at 300 ppm
18. Protective rating: IP20
19. Weight: 260 g
20. ATEX protection: this device must be installed in NON-CLASSIFIED ATEX areas.

{g} WORKING CONDITIONS
page 13
Depending on the input signal of the remote sensors, the control units can be found in the following working condition:
NORMAL MODE: the control unit receives a signal from the sensors corresponding to a gas level between 0% and 8%
of LEL for explosive gases and between 0 ppm and 120 ppm for toxic gases.
The relays are off and no alarm or fault LED lights up. The buzzer is off.
1st PRE-ALARM: the control unit receives a signal from the sensors corresponding to a gas level between 8% and 13%
of LEL for explosive gases and between 120 ppm and 200 ppm for toxic gases.
The relays are off and the red "8/120" LED lights up. The buzzer is off.
2nd PRE-ALARM: the control unit receives a signal from the sensors corresponding to a gas level between
13% and 20% of LEL for explosive gases and between 200 ppm and 300 ppm for toxic gases.
The pre-alarm relay changes state and the red LED "13/200" and "pre-alarm" also lights up
The pre-alarm relay is energized. The buzzer is on (low frequency).
MAIN ALARM: the control unit receives a signal from the sensors corresponding to a gas level higher than 20%
of LEL for explosive gases and greater than 300 ppm for toxic gases.
The main alarm relay changes state and the red "20/300" LED also lights up, the "Main alarm" LED flashes. The
main alarm relay is energized. The buzzer is on (high frequency).
OVER/UNDER RANGE: the control unit receives an under/over range signal. This condition is signaled through
two different flashing frequencies of the explosive gas LEDs.
The relays are off and no alarm or fault LED lights up. The buzzer is off.
FAULT: the control unit receives a "short circuit" or "open circuit" signal.
The yellow fault LEDs are on. The fault relay is energized. The buzzer is on (fixed sound).
SYSTEM ERROR: the control unit is blocked due to an internal fatal error.
The yellow error LEDs flash. Relays are OFF. The buzzer is on (LED frequency).
{i} PERIODIC CONTROL
{h} TROUBLESHOOTING
Problem.
If the error LED lights up, the system reports an error status.
Possible cause: The input current loop is broken or the transmitter is not powered.
Solution:
Check the connections between the transmitter and the control unit for interruptions. Check with a multimeter
the presence of a voltage around 12 VDC between the "+ V" and "GND" terminals of the reference input.
MAINTENANCE
A periodic service must include the following operations:
a) (every 6 months): Check the correct operation of the detection system by applying calibrated gas to each
remote sensor and checking the value.
Refer to the user manual of the sensors for more information.
b) (every 12 months): revision of the control unit transfer function and correct detection of anomalous
situations.
This can be done by disconnecting the sensors and forcing through a suitable calibrator the input current of
each zone to the significant values for example:
0 mA: open circuit,
3,7 mA: under range,
4-20mA: normal operation,
21 mA: Over range
23 mA: fault.
The following figure shows the conversion between mA and the corresponding gas concentration.

The simultaneous and prolonged pressing for 5 seconds of the "TEST" and
"RESET" keys enables the test-on mode in which the control unit does not switch
the general alarm relay for a period of 15 minutes; Not even by pressing the
external manual button.A further press of the keys in the same mode extends
the time by 15 minutes up to a maximum of 60 minutes.
In this mode, the string "tESt-On" (scrolling) is displayed before each passage
from the current channel to the next, followed by the minutes of the general
alarm relay being decommissioned.
N.B. Once the pre-set minutes are reached, the control unit automatically returns
to the control service mode.
You can terminate this mode before resetting the control unit by pressing 3
consecutive times and within 5 seconds the RESET button
NOTE. The alarm is activated only with the external manual button.
RESET TEST
test- on 15
Programma di Manutenzione
Functional test with GAS Pre-Calibrated and control tester
The user periodically at least every 6 months, must carry out a verification of the
functioning of the system by spraying a special test gas at the base of the
connected probes until obtaining the alarm status.
At least once a year
A more accurate check must be carried out by a specialized technician who must
issue the verification certificate with the Beinat TS1008 tester.
The decommissioning of the system must be carried out by a specialized
technician.
page 14
0 60 120 200 240 300 337
mA
Fault zone
Over range area
Under range area
Fault zone
7,2
0
10,4
16,8
20
14,7
4
3,6
22
ppm
Linear +/-5%
0 4% 8% 13% 16% 20% 22%
mA
Fault zone
Over range area
Under range area
Fault zone
7,2
0
10,4
16,8
20
14,4
4
3,6
22
LEL
Linear +/-5%
3,8 3,8
Explosive gas detection diagram Toxic gas detection diagram

{q} MARKING
Example of a label
page 15
{m} BATTERY MAINTENANCE
{n} SPARE PARTS
This control unit has not user serviceable parts.
{l} AUTOMATIC RESET
{k} CONTAMINANTS
Not applicable to the control unit. For the remote sensor, refer to the remote sensor user manual
{j} STORAGE
This control unit has not compatible accessories.
{p} WARRANTY
{o} ACCESSORIES
Temperature operating range: -10° C to + 60° C
Humidity operating range: 0 ÷ 90% RH not condensed
Pressure operating range: 800 ÷ 1100 hPa
The pre-alarm relay state is automatically reset when the concentration drops below the pre-alarm threshold.
On the contrary, the alarm relay state CANNOT be automatically reset and remains in memory until the control
unit is reset by the user. Refer to the section for details.
This control unit is equipped with input terminals (1 and 2) for backup of the external 12 VDC power supply.
The control unit charges the battery up to 1.2 Ah.
Battery maintenance operations must be based on the manufacturer's technical information.
With a view to the constant development of its products, the manufacturer reserves the right to modify technical
data and functions without prior notice.
The consumer is guaranteed for any lack of conformity pursuant to European Directive 1999/44 / EC, as well
as to the manufacturer's document about the warranty policy.
The full text of guarantee is available on request from the seller.

CNC
NO
CNC
NO
CNC
NO
Ph
N
1 2 3 4 5 6 7 8
1°Gas Threshold Gas Alarm phone prog. Electromagnet
NC
C
NC
NO
PH N 4 5
Ph
N
CNC
NO
CNC
NO
CNC
NO
1 2 3 4 5 6 7 8
Electromagnet
NC NA
°GasThreshold GasAlarm Solenoidvalves phone prog.
Fault
NOTE!
All relays are voltage free
Fire Relay
Fire Relay
Connections of a solenoid valve Normally
Closed without Positive Safety
ELECTRICAL CONNECTIONS
{r} INSTALLATION EXAMPLES
WARNING.
Before connecting to the mains power,
ensure the voltage is correct.
Carefully follow the instructions and the
connections according to Regulations in
force, keeping in mind that the signal
cables should be laid separate from the
power cables.
An automatic cut-off switch appropriately
identified should be incorporated in the
electrical system, adequatelylocated and
easily accessible.
page 16
Connections of a solenoid valve Normally Closed with Positive Safety
Power supply
110/240 VAC
Power supply
110/240 VAC
Power supply
110/240 VAC
FaultMain Alarm
Pre Alarm BX449F probes battery
RESET TEST
Explosive Toxic
000LEL
ppm
1 2 3 4
OVER LOAD
1
2
3
4
Open Line
Close Line
FIRE
Alarm

Connections of a solenoid valve normally closed without Positive Safety and auxiliary
to 12VDC through a power Switching
page 17
Sensors terminal block for GAS detection
In this diagram they are connected three probes GAS and one of fire.
N.B. at each input you can connect: 1 GAS sensor,1 Group sensors fire from 1 to 5 max
FaultMain AlarmPre Alarm BX449F probes battery
RESET TEST
Explosive Toxic
000LEL
ppm
1 2 3 4
OVER LOAD
1
2
3
4
Open Line
Close Line
FIRE
Alarm
1 2 3 4 5 6 7 8 9 10
12
3
4
12V
+
Optional
3 2 1
Sensor 1 3 2 1
Sensor 2 3 2 1
Sensor 3
End of line resistance 1K2
Fire Sensor
+R1 R2 R3 R4
Diode
1N5406
CN C
N O
CN C
N O
C
N O
N C
1 2 3 4 5 6 7 8
GASalarm FIREalarm
Pre
alarm
1 2 3 4 5 6 7 8 9 10
Switching power supply
12 V
3 2 1
Sensor 1 3 2 1
Sensor 2 3 2 1
Sensor 3
R1 R2 R3 R4
End of line resistance 1K2
230 VAC
Ph
N
12 VDc
12
3
4
12
3
4

Page 18
GAS PROBE INSTALLATION FIRE PROBE INSTALLATION
Smoke detectors
Temperature detectors
30 cm Light Gas
30 cm Heavy gas
160 cm Volatile gas
The BX449F control unit belongs to group II and must be installed in a safe area;
Outside the ATEX zone, however, not in boiler rooms or engine room.
The control unit must be accessible and visible to the user.
The BX449F control unit is a device suitable for being installed on the wall, or on an electrical panel using the
special bracket, optional, on request.
When installing, it is good to use the normal care that an electronic equipment requires:
- Install the equipment away from excessive heat sources.
- Avoid liquids coming into contact with the control unit, remembering that its external structure has IP20 degree
of protection if installed on the Boxed version (cabinet) supplied to the source is IP....
The sensors must be selected with an IP degree depending on the area to be controlled (Kitchens,
Boiler Rooms, Laboratory, etc.) by selecting one of the probes from Beinat from IP30 to ATEX. see
page 3
The GAS connected sensors to this equipment are of multiple types and must be positioned at different
heights according to the type of gas to be detected.
These heights are:
- 30 cm from the lowest point of the floor in order to detect: Heavy gases (L.P.G. etc.)
- 30 cm from the highest point of the ceiling in order to detect: light gases (Methane, etc.)
- 160 cm from the lowest point of the floor in order to detect: volatile gases (CO, etc.)
It is important to note that the remote probes should be installed according to the following
restrictions:
1) The sensors should not be placed near the appliances to be controlled (boilers, burners, industrial
kitchens, etc.) but on the opposite side.
2) The sensors should not be affected by smoke, vapour, and moving air, as they could distort their
measurement.
3) The sensors should not be placed near sources of heat, ventilators or fans.
It should be noted that the internal GAS sensors of the probe are perishable components with a variable
average life span from 5 to 6 years (you can request the relative table). Therefore, after this period of time
has elapsed it is advisable to replace them.
Maintenance
The user periodically (every 6 months) must carry out a check of the functioning of the detection system
by spraying a special test gas pouring the sensors connected to the BX449F until obtaining the alarm status
of the control unit.
a) At least once a year have a more accurate check performed by a specialized technician.
b) The disposal of the sensors after 5 years from installation must be carried out by qualified personnel.
Installing and positioning the control unit
Installingandpositioningthesensors

Page 19
1) Apply power using the proper external switch. This switch should be fitted with protection fuses.
2) You will notice that some LEDs will light up in turn for about 20”. N.B. Make sure all leds are working.
3) The display will start the COUNT DOWN of about 90 seconds (warm up). At the end the control unit is ready
for detection.
4) Pressing and holding down the TEST button, you can obtain a gas leakage simulation. The control unit will
carry out the following:
a) It will light up the prealarm led set to 13% LEL or the 200ppm (with reference to CO) and switching the
1st threshold relay. The buzzer will issue a low frequency sound.
b) It will light up the main alarm led set to 20% LEL or the 300ppm (with reference to CO). In addition to
maintaining the PRE ALARM relay switched, it will also switch the MAIN ALARM relay. The MAIN ALARM LED will
start blinking and the buzzer will issue a higher frequency sound.
5) To complete the test, carefully read the probe instruction manual and perform the sensor test by issuing
gas from a pre-calibrated aerosol.
6) If you want to simulate a zone FAULT, you only need to disconnect the signal cable of one or all the four
sensors. The control unit will carry out the following:
- The FAULT and MAIN ALARM LEDs will light up and blink;
- The buzzer will issue a continuous sound;
- The FAULT and MAIN ALARM relays will switch.
Reconnect the signal cable and press RESET to restore the control unit functioning.
If other problems arise, a specialised and/or authorised technician and/or the Distributor of
BEINAT S.r.l. should be contacted directly.
If the device does not start up.
Check that the 230VAC mains power is correctly connected. If powered by the battery, check that the 12VDC
power is correctly connected.
-If the Fault LED lights up.
Check that the probe cables are connected as in the drawing, they have not pinched the insulating sheath
Check that the voltage at the terminals 3-4, is greater than 11 VDC and less than 25 VDC
Check that at the terminals 3 and 5 (6-7-8) is present a voltage from a minimum of 0,8 VDC at a maximum
of 1,1 VDC
If the Over Load Probe LED lights up.
Check: that the power polarity has not been inverted, that no short-circuit is present,
that the probes were not damaged during installation, that no excessive current absorption is present.
If the Over Load Battery LED lights up.
Check that the connection cables are not short-circuited, that the polarity has not been inverted, or that the
battery is not damaged
- If the Open Line LED lights up.
Check that the connection cables, which connect the sensors are intact and that the signal wire is well
connected. That the sensors are perfectly housed in their plinth, and that the end-of-line resistor is inserted
and of the right Ohmic value.
- If the Closed Line LED lights up.
Check that the connection cables, which connect the sensors are intact and that the signal wire is well
connected. That the sensors are perfectly housed in their plinth, and that the end-of-line resistor is inserted
and of the right Ohmic value.
If the Control Unit is repeatedly issuing an alarm.
Check that there are no gas leaks. If the alarm signal and the FAULT indicator light turn on together, check
the probes.
If the Control Unit is issuing an alarm and does not shut off the devices connected to it.
Check that the wiring is correct and that the jumper that carries power to the relay has been set properly. All
relays are free from electrical power.Check the drawing of the connections.
If a 12Vdc solenoid for valve, which does not work well, is connected to the BX449F.
Direct connection of 12Vdc solenoid valves or sirens to the BX449F is not permitted.
An external power unit must always be used.
The BX449F gives a max current of 100mA.
Turn On
Troubleshooting and solutions before calling a technician
013
2
1,1
V.
Voltmeter
1 2 3 4 5 6 7 8
+ +
3 2 1
Sensor 1 3 2 1
Sensor 2 3 2 1
Sensor 3 3 2 1
Sensor 4
WARNING.
This measurement should
be performed in clean air.

BX449F Rev3 29 19
Control Unit BX449F Lo styling è della b & b design
Dealer stamp
Purchase date:
Serial number:
Beinat S.r.l. following the purpose of improving its products, it reserves the right to modify the technical, aesthetic and functional characteristics
at any time and without giving any notice.
INSURANCE. This device is insured by the SOCIETÀ REALE MUTUA for the PRODUCT'S GENERAL LIABILITY
up to a maximum of 1,500,000.00 EURO against damages caused by the device in case of failures in functioning.
WARRANTY. The warranty term is 3 years from manufacturing date, in agreement with the following
conditions. The components acknowledged as faulty will be replaced free of charge, excluding the replacement
of plastic or aluminium cases, bags, packing, batteries and technical reports.
The device must arrive free of shipment charges to BEINAT S.r.l.
Defects caused by unauthorized personnel tampering, incorrect installation and negligence resulting from
phenomena outside normal functioning shall be excluded from the warranty.
BEINAT S.r.l. is not liable for possible damage, direct or indirect, to people, animals, or things; from product
faults and from its enforced suspension of use.
DISPOSAL OF OLD ELECTRICAL & ELECTRONIC EQUIPMENT.
This symbol on the product or its packaging to indicates that this product shall not be treated as household waste. Instead, it shall be handed over to
the applicable collection point for the recycling of electrical and electronic equipment, such as for example:
- sales points, in case you buy a new and similar product
- local collection points (waste collection center, local recycling center, etc...).
By ensuring this product is disposed of correctly, you willhelp prevent potential negative consequence for the environment and human health, which could
otherwise be caused by inappropriate waste handing of this product. The recycling of materials will help to conserve natural resources. For more detailed
information about recycling of this product, please contact your local city office, your household waste disposal service or the shop where you purchased
the product.
Attention: in some countries of the European Union, the product is not included in the field of application of the National Law that applies the European
Directive 2002/96/EC and therefore these countries have no obligation to carry out a separate collection at the “end of life” of the product.
Madein Italy
IP20
Technical support - laboratorio@beinat.com
BEINAT S.r.l.
Via Fatebenefratelli 122/C 10077, S. Maurizio C/se (TO) - ITALY
Tel. 011.921.04.84 - Fax 011.921.14.77
http:// www.beinat.com
Table of contents
Popular Control Unit manuals by other brands

Danfoss
Danfoss BVTS installation guide

Roger
Roger R70/1AC INSTRUCTIONS AND RECOMMENDATIONS FOR THE INSTALLER

M-system
M-system R30TS4 instruction manual

Texas Instruments
Texas Instruments DLPDLCR660TEVM user guide

Murphy
Murphy EMS-GC10 Operator's manual

Miele
Miele DSM 408 Operating and installation instructions

MG
MG JFK instruction manual

Metso
Metso Neles PZ Series Installation maintenance and operating instructions

Honeywell
Honeywell VR8215S installation instructions

Warren rupp
Warren rupp Sandpiper HD20F Service & operating manual

KUGELHAHN MÜLLER
KUGELHAHN MÜLLER KM-O Series Operating and maintenance instructions

Telit Wireless Solutions
Telit Wireless Solutions BlueMod+S50/AI Hardware user's guide