Antec controls LUME20 User manual

LUME20
Room Pressure Monitor
MANUAL v100

LUME20 - MANUAL
2 | LUME20 – Manual | AntecControls.com
TABLE OF CONTENTS
INTRODUCTION ...............................................................................................................................................................................4
General..........................................................................................................................................................................................4
Product Overview..........................................................................................................................................................................4
General Installation Information ....................................................................................................................................................4
Technical Specifications ................................................................................................................................................................5
GETTING STARTED WITH LUME20.................................................................................................................................................6
In the Box......................................................................................................................................................................................6
LUME ACCESSORIES ......................................................................................................................................................................7
Differential Pressure Sensor (SDPT) .............................................................................................................................................7
Door Contact Switch (DCS)...........................................................................................................................................................7
MECHANICAL INSTALLATION ........................................................................................................................................................8
Installation and Mounting Instructions ..........................................................................................................................................8
Pressure Sensor Installation Instructions....................................................................................................................................10
ELECTRICAL INSTALLATION.........................................................................................................................................................12
Sample Wiring Diagram...............................................................................................................................................................12
BACnet MS/TP Network .............................................................................................................................................................13
DISPLAY NAVIGATION...................................................................................................................................................................14
Initial Setup .................................................................................................................................................................................14
Home Screen ..............................................................................................................................................................................16
SETTINGS .......................................................................................................................................................................................21
Mode Override ............................................................................................................................................................................21
Room Modes ..............................................................................................................................................................................22
Monitored Rooms .......................................................................................................................................................................25
Inputs ..........................................................................................................................................................................................28
Outputs .......................................................................................................................................................................................34
BACnet........................................................................................................................................................................................37
BACnet Polling Points .................................................................................................................................................................38
User Preferences ........................................................................................................................................................................42
LUME ASSISTANT..........................................................................................................................................................................43
System Requirements ................................................................................................................................................................43
Installation Requirements............................................................................................................................................................43
How to Connect to LUME20.......................................................................................................................................................44
LUME Assistant Start-Up ............................................................................................................................................................44

LUME20 - MANUAL
3 | LUME20 – Manual | AntecControls.com
Home ..........................................................................................................................................................................................45
Diagnostics..................................................................................................................................................................................46
Adjusting Windows Defender™ Firewall Settings ......................................................................................................................47
MAINTENANCE ..............................................................................................................................................................................51
Replacement Parts......................................................................................................................................................................51
Technical Support........................................................................................................................................................................51
APPENDIX A ...................................................................................................................................................................................52
Lume™ Drywall Cut-Out .............................................................................................................................................................52

LUME20 - MANUAL
4 | LUME20 – Manual | AntecControls.com
INTRODUCTION
General
In this manual, you will find information regarding:
•LUME20 technical specifications
•LUME20 mechanical and electrical installation
•LUME20 interface navigation and configuration
•LUME Assistant software navigation and operation
Product Overview
LUME20 is designed to provide ease of use pressure
monitoring.
The Home screen provides monitoring information in a
simple format displaying information including Room Status
and Pressure Mode.
Upon swiping the screen to the left, room pressure
measurement is visually available.
Some of the key LUME20 features include:
•4.3 in. (109 mm) capacitive touchscreen display
•Password protected menus
•Configurable audible and visual alarms
•Interface with analog pressure sensor
•Native BACnet MS/TP
•Setup Wizard provides fast, intuitive start-up
•Easy to use software to copy and paste
configurations
•LED sidebars offer 180˚ viewing of current room
status
General Installation Information
1. A qualified person must perform installation and
electrical wiring in accordance with all applicable
codes and standards, including fire-rated
construction practices.
2. Do not damage electrical wiring and other hidden
utilities while installing this device.
3. Disconnect power at the service panel before
performing wiring or maintenance on this device.
4. Intended for indoor installation only, in areas with
Pollution Degree 2.
5. Not designed for use in industrial, farming or
humid environments.
6. Not designed for use in residential environments
and may not have adequate protection to radio
interference.
7. Not designed to operate in a construction
environment. Use in these environments may lead
to excess or unintended wear, reducing product
life and/or performance.
8. The manufacturer assumes no responsibility for
personal injury or property damage resulting from
improper handling, installation, service or operation
of the product.
CAUTION
This mark indicates an important point for the proper
function of LUME20 and its accessories. Pay close attention
to all caution points throughout this manual.
For local area support, please contact your local Antec
Controls Representative.
For more information visit
www.AntecControls.com

LUME20 - MANUAL
5 | LUME20 – Manual | AntecControls.com
Technical Specifications
Environmental (Operating) 32°F to 130°F (0°C to 55°C), 5% to 95% R.H. (Non-Condensing)
Environmental (Storage) -22°F to 158°F (-30°C to 70°C), 0% to 95% R.H. (Non-Condensing)
Input Power 24 VAC ±10%, 50/60 Hz, 21 VA Max (excluding external loads), Class 2
Inputs
4 Universal Inputs
Binary Input (Contact Closure)
Analog Input (0 – 10 VDC)
Thermistor Input (10k Type 2)
3 RJ45 Network Ports
Outputs
1 Analog Output (0 – 10 VDC, Max: 10 mA)
2 Binary Outputs, Non-Isolated Contact Closure (Max: 24 VAC, 500 mA)
Indicators Touchscreen Display, 4.3 in. (109 mm) TFT, Speaker
Housing UL 94V-0, PC-ABS Plastic
BACnet
Device Type B-AAC
Communication Type MS/TP (RS-485)
Communication Speed 9600, 19200, 38400, 76800
Certification BTL
Control Priority Order 1. BACnet
2. Normal operation

LUME20 - MANUAL
6 | LUME20 – Manual | AntecControls.com
GETTING STARTED WITH LUME20
In the Box
Room Pressure Monitor (LUME20)
Component
Quantity
Description
Room Pressure Monitor
(LUME20)
1
Single LUME20
[Optional] Differential Pressure Sensor (SDPT)
Component
Quantity
Description
Differential Pressure
Sensor
1 (single room monitoring)
2 (dual room monitoring)
3 (triple room monitoring)
Single SDPT
[Optional] Stainless Steel Sensor Plate
Component
Quantity
Description
Stainless Steel Sensor
Plate
2 (single room monitoring)
4 (dual room monitoring)
6 (triple room monitoring)
Stainless Steel Plate used as a
pressure sensor inlet
Mounting Hardware
Packet
2 (single room monitoring)
4 (dual room monitoring)
6 (triple room monitoring)
Packet containing two screws
for J-Box mounting of Sensor
Plate
Kink Resistant Air Tubing -
96 in. (2.44 m)
1 (single room monitoring)
2 (dual room monitoring)
3 (triple room monitoring)
Air pressure tubing to connect
between Sensor Plate and
Room Pressure Sensor
OR
[Optional] ABS Sensor Plate
Component
Quantity
Description
ABS Sensor Plate
2 (single room monitoring)
4 (dual room monitoring)
6 (triple room monitoring)
ABS plate used as pressure
sensor inlet
Mounting Hardware
Packet
2 (single room monitoring)
4 (dual room monitoring)
6 (triple room monitoring)
Packet containing two screws
and two drywall anchors for wall
mounting of Sensor Plate
Kink Resistant Air Tubing -
96 in. (2.44 m)
1 (single room monitoring)
2 (dual room monitoring)
3 (triple room monitoring)
Air pressure tubing to connect
between Sensor Plate and
Room Pressure Sensor
CAUTION
Please ensure you have all the components before proceeding. Inspect all components for shipping damage. Do not install any components that appear
damaged. Contact your local Antec Controls Representative for replacements.
For the latest information and videos please visit www.AntecControls.com.

LUME20 - MANUAL
7 | LUME20 – Manual | AntecControls.com
LUME ACCESSORIES
Differential Pressure Sensor (SDPT)
The SDPT is a room pressure sensor that is used to measure pressure.
Overview
See the SDPT product submittal on AntecControls.com for Specifications, Dimensions and Configurations.
Options
1. Differential Pressure Sensor
Model:
Features:
SDPT
•2 – 10 VDC outputs for pressure reading.
•-0.25 to +0.25 in.w.c. (-60 to 60 Pa)
•LED light used to display status
•Accurate to 3% of reading
Door Contact Switch (DCS)
Door Contact Switches can be wired into the binary input(s) to detect when the door(s) are open.
Overview
See the DCS product submittal on AntecControls.com for Specifications, Dimensions and Configurations.
Options
1. Surface Mount 2. Flush Mount

LUME20 - MANUAL
8 | LUME20 – Manual | AntecControls.com
MECHANICAL INSTALLATION
It is recommended to mount LUME20 at approximately 5 feet (1. 5 m) from the floor. This will allow the interface to be at an
appropriate height for use during setup and during normal operation.
Installation and Mounting Instructions
Touchscreen Installation Instructions
Option A
Mount LUME20 directly on dry wall.
STEP 1
Mark an appropriate mounting location for the monitor.
STEP 2
Using a jigsaw, cut four lines to cut-out a rectangle (minimum 2.0 in. W X 2.5 in. H,
50.8 mm W X 63.5 mm H).
NOTE: Ensure the cut-out sizes are not bigger than the size of the back plate (3.4
in. W x 4.9 in. H, 86.4 mm W X 124.5 mm H ).
STEP 3
Drill 4 mounting holes according to the provided template in Appendix A.
STEP 4
Make sure that the anchors are flush to the wall and then mount the backplate on
the drywall using four #6 drywall screws with anchors.
STEP 5
Attach LUME20 on the backplate installed on the dry wall.
Option B
Mount LUME20 using an EU Wall box.
STEP 1
Using the provided instructions, mount the EU Wall box at the suggested height from
the floor.
STEP 2
Remove the two unused screws from both sides.
STEP 3
Mount the back plate on the wall box using the two screws removed from the wall
box in Step 2.
STEP 4
Attach LUME20 on the backplate that was installed in Step 3.

LUME20 - MANUAL
9 | LUME20 – Manual | AntecControls.com
Option C
Mount LUME20 using a standard single-gang electrical box.
STEP 1
Using the provided instructions, mount the standard single-gang electrical box at the
suggested height from the floor.
STEP 2
Mount the back plate to the box using two #8-32 screws.
STEP 3
Attach LUME20 on the backplate that was installed in Step 2.

LUME20 - MANUAL
10 | LUME20 – Manual | AntecControls.com
Pressure Sensor Installation Instructions
Selecting a Location for Installation
There are three components that are to be installed for each
space that requires pressure monitoring:
1.
A sensor plate inside the room
2.
A sensor plate outside the room
3.
An SDPT differential pressure sensor
Begin by determining installation locations for each of these
components.
1.
The best installation location for the sensor plates is
typically above a doorway. When determining the
location for the sensor plates:
a.
Ensure that nothing can be placed in front of the
pressure sensor, blocking its ability to measure
the room pressure accurately.
b.
Be wary of diffuser placement in relation to the
sensor. Turbulent airflow passing over the sensor
plate can cause unstable pressure readings.
2.
The Differential Pressure Sensor (SDPT) can be
mounted in the plenum space either in the room or in
the reference space. Important notes:
a.
The sensor must be placed in a location where
the ninety-six inches (96 in., 2.44 m) of total
pressure tubing provided with the SDPT can
reach both pressure plates.
b.
The sensor should be easily accessible for wiring
and setup.
CAUTION
Incorrect placement can affect the sensor’s readings.

LUME20 - MANUAL
11 | LUME20 – Manual | AntecControls.com
Once the installation locations have been selected, the sensor plates can be mounted using the following steps.
Prior to mounting the sensor plates, cut the ninety-six inches (96 in.,
2.44 m) clear tubing to the required length for the distance from each
plate to the sensor. E.g., if the plate for the isolation room is five feet
(5 ft, 1.52 m) from the SDPT and the plate for the corridor is three feet
(3 ft, 0.91 m), cut the provided tubing into one five-foot (5 ft, 1.52 m)
and one three-foot (3 ft, 0.91 m) length.
To mount the ABS sensor plate directly to the wall:
1. Cut a one-inch (1 in., 25.4 mm) hole for the tubing to pass
through.
2. Use the sensor plate to mark the holes for the anchors
(anchors require 3/16 in., 4.8 mm drill). Drill hole and install
the provided anchors.
3. Push the clear tubing onto the pickup on the back of the
sensor plate.
4. Run the tubing through the one-inch (1 in., 25.4 mm) hole in
the wall and mount the sensor plate to the surface using the
provided screws.
5. Connect the tubing to the SDPT.
a. Monitored space to high pressure port.
b. Reference space to low pressure port.
To mount the stainless steel sensor plate directly to a single gang
electrical box:
1. Knockout a hole for the tubing to pass through.
2. Push the clear tubing onto the pickup on the back of the
sensor plate.
3. Connect the tubing to the SDPT.
a. Monitored space to high pressure port.
b. Reference space to low pressure port.
CAUTION
Make note if the tubing is reversed when installed. If the corridor is connected to
the high pressure port on the SDPT, the reading can be reversed during setup.
Do not extend the pressure tubing past the provided length of ninety-six inches (96
in., 2.44 mm). Extending the tubing past this length can result in degradation
of the pressure reading.
Do not connect tubing from the SPDT to any other pressure measurement devices
or other SDPT sensors.
Do not tee off the tubing to connect to any additional devices.

LUME20 - MANUAL
12 | LUME20 – Manual | AntecControls.com
ELECTRICAL INSTALLATION
Sample Wiring Diagram
NOTES:
1. For Typical Network Wiring Diagrams, see BACnet MS/TP Network section.
2. All wire connections to the LUME20 screw connection terminals must be between 16-26 AWG wire.
3. Current and voltage drop should be taken into consideration when selecting wire gauge.
4. Wiring above may not reflect those required for your project. Refer to your Antec Controls Wiring Diagram Package for
typical wiring recommendations.

LUME20 - MANUAL
13 | LUME20 – Manual | AntecControls.com
BACnet MS/TP Network
What is BACnet?
BACnet MS/TP is a communication protocol for
communication between LUME20 and the building
automation network. BACnet communication allows the
end user to verify rooms are operating as expected and set
up trends to monitor safetyand any alarms that occur.
LUME20 requires a connection to BACnet to transmit its
information to the Building Management System (BMS).
Network Addressing
When configuring LUME20, the user needs to assign the
unique addressing for the device.
On any BACnet MS/TP network:
•MAC Address can be between 0 and 127 and
must be unique to the MS/TP segment.
•Device Instance can be between 0 and 4,194,303
and must be unique to the facility.
•Baud Rate can be 9,600, 19,200, 38,400 or 76,800
and must match that of the Router/System
Controller for the MS/TP segment.
Typical BACnet Wiring
BACnet Points
See LUME20 Product Submittal at AntecControls.com for
BACnet Points List.
Physical Connection
BACnet consists of a three-wire network architecture.
Daisy chain the +, - and COM connections of all devices on
the network segment. A BACnet MS/TP segment has a
limit of:
•Maximum of 32 devices
•Maximum length of 1050 ft. (320 m) for the whole
segment
When using shielded cable, ground the shield at one end of
the network segment only. Connect the shield of the cable
entering a device to that of the cable exiting the device.
Terminate the MS/TP network segment at each end of the
network segment by connecting a 120-ohm resistor
between the + and – terminals. Remove the termination
resistor or disable any network terminations on all devices
when adding devices to an existing network segment.
Wiring Requirements
Refer to your Antec Controls Wiring Diagram Package for
typical wiring requirements and recommendations.
CAUTION
When using non-isolated power supplies (i.e. A transformer
with the secondary common connected to ground), do not
reverse 24VAC polarity on any device, as it is critical to the
network health.

LUME20 - MANUAL
14 | LUME20 – Manual | AntecControls.com
DISPLAY NAVIGATION
Initial Setup
When LUME20 is first powered on, it will prompt the user to step through a Setup Wizard to help configure the device. At any
point in the device setup, the user can return to previous selections in the menu via the Next/Previous buttons. Any value not
initially configured in the Setup Wizard can be configured through the Settings menu during normal operation. To begin the
Setup Wizard, enter the password 1-6-6-4. The following menus will be displayed:

LUME20 - MANUAL
16 | LUME20 – Manual | AntecControls.com
Home Screen
The Home Screen displays once the Setup Wizard has been completed or after a configuration file has been loaded using
LUME Assistant.
The Home Screen provides the user with a clear indication of the pressure mode, room status and pressure reading.
Normal Operation
Display Component
Description
1
Room Name
The current name of the room is displayed. This is
configurable through the Monitored Room menu.
2
Settings Button
Allows access to settings. This is password
protected.
3
Room Status
Displays the name of the current room mode. Room
modes are named Normal or Setback by default and
are configurable through the Room Modes menu.
4
Pressure Mode
Indicates whether the room is in Negative or
Positive pressure mode.
5
Room Mode
Allows the user to override the room mode. This is
password protected. Default Password: 1-2-3-4.
NOTE: Any overrides done locally through the
touchscreen will follow mode priority.

LUME20 - MANUAL
17 | LUME20 – Manual | AntecControls.com
Screen Saver
After a configurable inactivity timeout, the home screen will dim and display a screen saver. The screen saver displays a
checkmark with the color of the current room mode to indicate that the room is operating normally. The LED sidebars will
continue to display the light color of the current room mode for 180˚ viewing of the current room status while the screen saver
is active. Tapping on the touchscreen will reset the inactivity timeout and display the Home Screen in normal operation. The
screen saver and screen dimming can be disabled in the User Preferences menu.
NOTE: The screen saver will never display when there is an alarm or caution active.

LUME20 - MANUAL
18 | LUME20 – Manual | AntecControls.com
Caution Active
Display Component
Description
1
Room Name
The current name of the room is displayed. This is
configurable through the Monitored Roomsmenu.
2
Settings Button
Allows access to settings. This is password
protected.
3
Room Status
Displays Caution to indicate there is a caution active.
4
Caution Reason
Displays the type of caution that is active. Options:
1. Door Open
2. Low Pressure
3. High Pressure
4. Binary Input (Configurable display message,
see Binary Inputs)
5
Room Mode
Allows the user to override the room mode. This is
password protected. Default Password: 1-2-3-4.
NOTE: Any overrides done locally through the
touchscreen will follow mode priority.

LUME20 - MANUAL
19 | LUME20 – Manual | AntecControls.com
Alarm Active
Display Component
Description
1
Room Name
The current name of the room is displayed. This is
configurable through the Monitored Room menu.
2
Settings Button
Allows access to settings. This is password
protected.
3
Room Status
Displays Alarm to indicate there is an alarm active.
4
Alarm Reason
Displays the type of alarm that is active. Options:
1. Door Open
2. Low Pressure
3. High Pressure
4. Binary Input (Configurable display message,
see Binary Inputs)
5
Room Mode
Allows the user to override the room mode. This is
password protected. Default Password: 1-2-3-4.
NOTE: Any overrides done locally through the
touchscreen will follow mode priority.

LUME20 - MANUAL
20 | LUME20 – Manual | AntecControls.com
Alarm Silence
Silence Screen
If an alarm activates, the display will turn red and the audible alarm will
activate. The Silence Screen allows users to temporarily mute the audible
alarm for a configurable number of minutes. The mute duration defaults to
a five-minute delay and can be adjusted in the User Preferences menu.