ANTEK Green Energy AIR MAGNA 200 User manual

AIR MAGNA 200
INSTALLATION AND MAINTENANCE INSTRUCTIONS

2
AIR MAGNA 200
GREEN ENERGY SYSTEMS
The 6 essential points
Control the delivery: before any handling, to check the state of the heat pump after having
removed the packing of protection. Any degradation related to transport will have to be announced
on the form of transport and by Letter Registered AR under 48 hours to the conveyor.
Importance of this note: it is essential that it is given to the tter. We advise to read and follow
with attention the entirety of the instructions appearing there. Preserve this note for being able to
consult it constantly.
Standards of installation: the installation must be carried out in accordance with the standards
in force for this type of apparatus, and by respecting the instructions of the manufacturer, a person
qualied in the handling of thermodynamic machines or air-conditioning. The person must have the
lawful material and guarantee of a training of approved refrigeration technician. Any defect in the
installation can cause damage on the individuals, the animals or the objects.
On no account, the importer of this apparatus could not be made responsible for this damage.
Use of the heat pump: this heat pump is intended exclusively with use for which it was con-
ceived. Any other use non in conformity and random will be regarded as dangerous and unsuitable.
Maximum temperature of the water of swimming pool: It is essential to maintain the temperature
of water below the value recommended by the manufacturer of the swimming pool, in order not to
deteriorate its lining (liner PVC).
Breakdown: not consider any attempt at breakdown service; any even inopportune breakdown
will have to be announced to your retailer or your tter.
Wintering, maintenance: instructions appear in this note, it is essential to conform to it; before these
operations, the power supply of the heat pump must be cut.
Maintenance:
To perpetuate and guarantee the performances of the heat pump, it is necessary to make carry out a
regular maintenance; to refer for that to the instructions of maintenance.
In the event of resale with a third, it is imperative that this note is included with the material if
the new owner or the tter wishes to consult it.

3
Contents
1. Security consigny 4
2. Description of the heat pump
2-1 Outside 6
2-2 Inside 7
2-3 Dimentional and technical caracteristics 8
3. Fitting and putting into service of the heat pump
3-1 Rules of establishment 9
3-2 Hydraulic connections 10
3-3 Electric connections 12
3-4 Running of reversible heat pump 13
3-5 Description of the screen of display and control 14
4. Use in standard mode 15
5. Instruction for the tter
5-1 Devices of control and safety 17
5-2 Defrost operation 17
5-3 Instruction of the solar coil 17
5-4 The defaults messages and what to do 18
6. Instructions of maintenance 18
7. The three electric heaters 19
8. Gas ow diagram 20
9. Wiring Diagram 21
10. Problems / solutions 22

4
AIR MAGNA 200
GREEN ENERGY SYSTEMS
1-Security consigny
Attention
Any wrong handling can cause an important risk being
being able to result in death
Avertissement
Any wrong handling can cause serious damage to the
user and the machine
TO NOT DO
To follow attentively
To be sure of the electric connections
To be sure of the disconnection of the plug
Never climb, rest on or put on something on the unit
Caution DANGER: electrocution risk
Do not put hands, do not touch

5
CAUTION
Do not climb on the unit or try to move it when
installed.
Do not climb on the unit or try to move it when
installed.
Never introduce a stick, your nger or others in
the air inlet/outlet. The ventilator runs at high
speed: that would cause a very serious incident.
Important: Well clean the plug
If dirtiness adheres to the plug or if it is badly
inserted: that can cause a re or electric shocks.
If an abnormality (smell of burning…) occurs,
stop the unit, unplug or switch o the
electricity.
Do not clean the appliance with water.
Water will go into the unit and will destroy the
insulation.
Do not connect / unconnect the unit when
running ; press before all the button OFF.
Do not draw on the power supply cable. Well
have in hand the plug to disconnect it. Fire
hazard could occur due to the wrenching of the
electric cable.
Do not touch the plug with wet hands. It will
caused an electric shock.
By stormy weather, cut o the pump to avoid
the damaged caused by the lightning.
First o all the heat pump is stopped, put out
leaves or others little particles blocking the air
inlet vanes.
Verify the compatibility of the network with the data written on the heat pump before beginning
the installation.
The other disinfection systems such as electrolysis, chemical… are not recommended for a good
running of the pump. The pump must be r before these systems.
For an optimal running of the heating pump, many rules must been respected:
A. Use of free chlorine : max : 2.6mg/l
B. Total bromine : max : 5.6mg/l
C. pH : between 6.5 et 8.

6
AIR MAGNA 200
GREEN ENERGY SYSTEMS
2- Description of the heat pump
2-1 Outside
1 Power Plug
2 Control pannel
3 Air lnIet
4 Air Outlet
5 Temperature Sensor
6 Drainage hole
7 Cold Water Inlet
8 Hot Water Outlet
9 Service valve
10 solar coil inlet *
11 solar coil outlet *
12 Electrical heater *
4 3
9
8
5
11
12
6
7
6
10
1
2

7
2-2 Inside
1 Control panel cover 15 Gas returning pipe 29 Drainage Pipe
2 Power plug 16 Exhaust pipe 30 Rubber Cover
3 Clip of Power Cable 17 Filter 31
4 Electrical heater * 18 Auxilliary capillary 32
5 Plastic Base 19 Capillary 33
6 Water tank 20 Defrost sensor 34
7 Motor Capacitor 21 Assistant unit of air outlet 35
8 Compressor capacitor 22 Fan motor 36
9 Compressor 23 Electrical Box 37
10 Circuit Board 24 Circuit board base 38
11 Condenser 25 Barrier board 39
12 Condenser top polyfoam 26 Condenser heater 40
13 Four way valve 1 27 Control panel 41
14 Four way valve 2 28 Plastic shell 42
1 2 3 4 5 6 7
8
9
11
12
10
13
14
15
16
17
18
19
20
212223
24
25
26
27
28
29
30

8
AIR MAGNA 200
GREEN ENERGY SYSTEMS
2-3 Dimentional and technical caracteristics
ArtNo AM200-1,AM200-2 AM200-3
Model Code 120/150/200 300
Ratin Healing Capacity (kW) 2.68 3.40
Ratin Heating Power Input (kW) 0.85 1.09
Heating Current (A) 4.0 5.0
Refrigerant (g) ( R410A) 550 900
Compressor Quantity 1 1
Fan Quantity 1 1
Noise dB(A) 47 47
Temperature of output water 10-60 10-60
Unit Net Dimension (D X H) Φ570X 1415/(1515)/(1745) Φ 680X 1775
Unit Shipping Dimension (L/W/H) 640/620/1430(1530)(1760) 695/695/1825
Air ducts Dimension ( mm ) Φ150 Φ150
Net weight / Gross weight (kg) 55/64 66/75 73/82 81/90
Water Connection (Inch) 1 1
Capacity of the water tank (L) 120/150/200 300
Power Suppy (V/Ph/Hz) 220-240/1/50 220-240/1/50
Ambient Temperature (°C) -10 - 35 -10 - 35
Electricity Control Way Mini-computer intelligent control
Controller LED Display
Wire Control Yes
* according to climatic conditions; noncontractual document.
N.B. :
Sound measurement is made in laboratory before leaving the factory.
In the event of dierence between the table of the technical data and the descriptive plate of the
machine, it is necessary to refer to the data posted on this plate.

9
3- Fitting and putting into service of the heat pump
3-1 Rules of establishment
Ma measures dene the place of the appliance. it is essential to respect them:
Electric and hydraulic connections must be carried out according to national wiring regulation.
• The appliance must be installed outside
• The appliance must be put on its antivibratory studs, regulated with horizontal and on a massive
base (concrete stone or steel frame); this base must have a sucient height to prevent entering
of water by the bottom of the appliance; to regulate the height with the studs so as to be able to
connect the connection collecting the condensates.
• The obstacles such as wall and vegetation must be separated from the apparatus as indicated on
the diagram below.
• The ventilator should not blow towards the windows or crossing place.
• There must be more than 1.5M space on the top of the unit.
• The xing board of the unit must be xed by bracket.
• Connect drainpipe to the outlet of condensate water, then draw the drainpipe into blowo pipe.
Other precautions of establishment:
• Do not install the appliance near a way with circulation of cars in order to avoid mud projections.
• Avoid directing blowing counters the dominant winds.
• If the appliance is intended to be used in period winter, put it at the shelter of the falls of snow.
• The appliance must be able to be watch on especially so that children do not play around.
Attention:
When install pipeline for heat pump, user need to install an additional pressure reducing valve
(working pressure is less or equal to 3bar) in the water inlet pipe, for pressure reduction
and pressure stabilizing in the water supply system.
UNIT
0.5 m 0.5 m
0.5 m
0.5 m

10
AIR MAGNA 200
GREEN ENERGY SYSTEMS
3-2 Hydraulic connections
Refer the diagram below:
1. Connect the mouth for hot- water- in to the water tank with PP-R pipe, with other metal pipe. Pay
attention to heat preservation if use metal pipe.
2. Install water lter and one-way valve in the Tap water pipe, then connect the tap water pipe to
the tank mouth of tap water inlet.
3. Fill water into the tank: Open the tap- water-in valve to ll water; Meanwhile, open the hot
water-out valve, till water spill over from the hot-water-out valve. It means the tank is full of
water. Close the tap -water-in valve, check leakage by storing full water, Ensure there is no water
leakage in the all system.
Attention: be sure the tank is full of water before it is switched on to run.
Water lter
Hot water in
One-way valve
Water faucet
Tap water in
Tap water in
Water faucet
Water faucet
Water faucet
TECHNICAL ROOM
W
A
L
L
50 cm
150 cm
The exible pipe´s diameter is Ø 150 mm,
you can x it according to your system
design (details in next page)

11
Many system-design options for architects
Option A:
• Installation in the heating room.
• Hot water heating from room air.
• Optional use:
cooling of the food storage or wire cellar.
cooling of the room of your choice.
Option B:
• Installation in the laundry washing room.
• Hot water heating from room air.
• Optional use:
laundry-drying, decalcied water for steam-iron.
Dehumidication.
Option C:
• Installation in the same room as heating
heat pump.
• Heat recovery from return air; sanitary
hot water production.
• Optional use:
Removal of used, humid, charged air from
bath, toilet, kitchen;
Fresh ambient air enter home by slots.

12
AIR MAGNA 200
GREEN ENERGY SYSTEMS
3-3 Electric connections
CAUTION: before connecting the appliance, make sure that the supply power line in
disconnected from the network.
Characteristies of the general power supply:
• mode of neutral TT and TN.S; the circuit of heat pump must be connected to an earthing circuit
Connections:
• The electric Installation must be carried out by a professional qualied (like an electrician)
according to the rules und standards in force in the country of installation.
• The power supply of the heat pump must come preferably from an exclusive circuit und having
the bodies of lawful protection.
• Controller must be installed or indoor wall and the plane is easy for use.
Electric protection of which must lay out the heat pump:
• circuit breaker curves D or standard fuse of protection Am, gauged with 16A
• dierential protection of 30 mA
In the event of connection to an electrical plug by the user:
• The heat pump is being provided with an electric cable, set possible to connect it with a plug.
• The plug must be checked in conformity with the power of the appliance by a qualied
technician.
• The plug must be safe from the rain, of easy access to be cleaned and one will have to regularly
check the good condition of this plug.
BEFORE THE STARTUP OF HEAT PUMP, IT IS SIGNIFICANT TO
INCLUDE/UNDERSTAND THE OPERATING AND THE SETTINGS OF WHICH YOU WILL
TAKE NOTE IN THE FOLLOWING PARAGRAPHS

13
3-4 Running of reversible heat pump
By using the free energy contained in the ambient air, the heat pump enables to heat the water of
the water in a very economic way.
Your heat pump is a heat machine that can transfer the heat from a low temperature place (ambient
air) to a higher temperature place.
Running in heating mode
The heat of the air is absorbed by die cold, liquid refrigerant, through the evaporator (radiator with
wings), in which it‘s vaporized, then die compressor increases the pressure and the temperature,
and sends it into the condenser (exchanger) where it loses its heat by transmitting it to the water
und it comes in the liquid state, it loses its pressure und cools again into the pressure reducer before
returning to the evaporator for new cycle.
* Running in cooling mode or defrosting mode
4 way valve enables to reverse die cycle of the refrigerant; the liquid uid is vaporized into the ex-
changer (that becomes the evaporator) by taking the heat of the water of die water, passes into the
compressor which heats it then into the radiator (which becomes the condenser) where it comes
back at the liquid state.
Note: Single water heater without cooling water mode; Single water chiller without heating
water mode and defrosting mode.

14
AIR MAGNA 200
GREEN ENERGY SYSTEMS
3-5 Description of the screen of display and control
1. With water tank assistant electical heater
2. Without water tank assistant electical heater
Two gures on the left: current temperature of the water tank
Or two gures on the right: desired temperature
Light of heat pump running
Light of electric heater running
Button for coercive defrosting
It is used to ser up the function
of coercive defrosting.
On/o
To adjust the hour
To adjust the current hour and
functionning timetable
Button for Temperature
up and down
It sets the temperature of
water and time of dose
the heater.
Defrost Setting and
Electric heater Forced
Or two gures on the right: desired temperature
Two gures on the left: current temperature of the water tank
Light of heat pump running
Button for coercive defrosting
It is used to ser up the function
of coercive defrosting.
On/o
To adjust the hour
To adjust the current hour and
functionning timetable
Button for Temperature
up and down
It sets the temperature of
water and time of dose
the heater.
Defrost Setting

15
4- Us in standard mode
Starting Operation
Press “ “ button, and when the unit receives the signal, it gives out two“ beep“tones, the
operation is on and the heat pump water heater stars operation.
lf the interval shorter than 3 minutes from last shut down to the present switch-on, the compressor
only restarts after 3 minutes to protect the system.
Temperature Setting Selection
Press “ “ to set temperature 1 degree higher.
Press “ “to set temperature 1 degree lower
Temperature range set in heating mode: 10°C – 60°C. (Single water chlller without this function)
Setting right the hour of the Heat pump
The Heat pump must not run. If it is running. press on “ “ for stopping it.
Press 5 seconds on“ “, the left display ( = the hour) lights
Press the button‘‘ “ or“ “ for increasing or decreasing the hour.
Press again on “ “, the left display ( = the minutes ) lights
Press the button“ “ or“ “ for increasing or decreasing the minutes.
Validate in pressing on “ “ ( or wait 10 seconds; the display will leave this setting mode by it self)
Setting of running selected periods (TIMER)
Press on “ “ , the left display (= the hour ) lights
Press the button“ “ or“ “ for increasing or decreasing the hour.
Press again on “ “. the left display ( =the minutes ) lights
Press the button“ “ or“ “for increasing or decreasing the minutes.
Validate in pressing on “ ‘‘; The light“ “switches on.
For setting the hour of stopping running (TIMER)
Press on “ “ and set the hour &he minutes as done before...
The light“ ‘‘ switches an.
Cancelling this programming
Press on “ “ The light“ “ light. Press on“ “
Press on “ “ The light“ “ light. Press on“ “
Coercive Defrosting
1. press“ “‚ Button, the heater go to defrost state.
2. After 3 minutes‚when coil temperature up to 10°C or the time of defrost reaches 8 minutes, defrost
is stopped.
3. After exiting the state of defrost, ther heater will stop operation for 3 minutes, then it will run as
the state before defrost.
Or two gures on the right: desired temperature
Light of electric heater running
Button for coercive defrosting
It is used to ser up the function
of coercive defrosting.
Or two gures on the right: desired temperature
Button for coercive defrosting
It is used to ser up the function
of coercive defrosting.

16
AIR MAGNA 200
GREEN ENERGY SYSTEMS
Adjustment of the defrosting
1-Press on “ “ or ” “ for 3 seconds , you can see (for example)
The rst number is the symbol of the item; and the second value is the setting value of the current
item.
Press the button“ ”or “ ”for increasing or decreasing the value.
2-Press on “ “ or ” “ again to enter next item, just like:
The content of each item :
Number 0 stand for << Flow switch detection >>: (0,1) adjustable ( invalidation in this system )
Number 1 stand for <<Defrost starts temperature>>: (-30°C to 0°C) adjustable Number 2 stand
for <<Defrost stops temperature>>: (0°C to 30°C) adjustable Number 3 stand for <<Interval of de-
frost>>: (30 min to 90 min) adjustable Number 4 stand for <<Time of defrost>>: (1 min to 20 min)
adjustable
Number 5 stand for <<The time of water temperature up 1 °C >>: (1 min to 10 min) adjustable
Number 6 stand for <<The minimum temperature dierence of compressor star>>:
3 ° C to 15°C) adjustable
3-After setting the value, the defrosting setting will exit automatically after several seconds.
And the system will memorize the last value of each setting.
Temperature Display
You can check the correlative temperature by following step:
1-Press on “ ” for 4 seconds , you can see (for example)
The rst letter is the symbol of the item; and the second value is the temperature of the current item.
2-Press on “ ” again to enter next item.
A stand for << Temperature of the water>>
B stand for <<Temperature of the ambient>>
C stand for <<Coil temperature in outdoor heat exchanger>>
D stand for <<Exhaust temperature from compressor>>
Reset button
when press the button“ “ for 4 seconds, and the following points will return to initial state
(Windows default):
0. Flow switch detection: 0
1. Enter defrost temperature: -7°C
2. Exit defrost temperature: 10°C
3. Defrost interval: 45 minutes
4. Defrost time: 8 minutes
5. The time of water temperature up 1°C : 3 minutes
6. The minimum temperature dierence of compressor star : 5°C
1 . -7
2 . 10
A . 45

17
5- Instruction for the tter
The tter has to read the following notice and explain the instructions to the user.
5-1 Devices of control and safety
The beet pump is equipped with:
2 control devices:
• A defrost temperature probe located on the evaporator, starts the defrost sequence.
• A thermal probe located on the exchanger, ensures the cut of the heat pump when the
temperature of the water reaches the temperature instructed
The meaning of code name:
T1: water temperature
T2: ambient temperature
T3: exhaust temperature from compressor
T4: coil temperature in outdoor beet exchanger
TC: water temperature setting
Control function:
1. TC can be set between 10°C-60°C in heating mode. Original TC is 45°C. When T1 TC-1°C,
Compressor and fan motor start; When T1 TC+1°C, Compressor and fan motor stop.
When compressor is running, if T2 14°C, the four way valve2 on; if T2 16°C, the four way valve2 o.
5-2 Defrost operation
1. Defrost:
The System begins to defrost if the following three terms are met in the same time:
a. T4 -7°C lasts for a while;
b compressor runs continuously for more than 5 minutes
c. compressor runs accumulative total for 45 minutes (the interval between two defrost is a cycle,
time accumulates)
While the system begin to defrost, compressor and fan motor stop at rst and four way valve1 is on
after 1 minutes and begins to work, compressor restarts after it stop for 3 minutes. lf the sensor for T4
is damaged, the system begins defrosting after compressor runs continuously for 45 minutes.
2. Terms of defrost exiting:
When defrosting time reach 3 minutes and T4 reaches 10°C or defrosting time reaches 8 minutes,
defrost exits and enter heating water mode. While defrost exiting, after compressor and fan motor
stop for 1 minute, four way valve is o. Compressor restart after it stops for 3 minutes, the system will
run the mode the same as before defrost.
5-3 Instruction of the solar coil
Type
Data
150L 200L 300L
Thickness (mm) 1.0 1.0 1.0
Length (m) 19 19 19
Diameter (mm) 15.88 15.88 15.88
Connecting Size (inch) 1/2´ male thread 1/2´ male thread 1/2´ male thread

18
AIR MAGNA 200
GREEN ENERGY SYSTEMS
5-4 The defaults messages and what to do
Failure code:
E1: sensor for T1 (water temperature) failure
F2: sensor for T2 (ambient temperature) failure
E3: sensor for T3 (exhaust temperature from compressor) failure
E4: sensor for T4 (coil temperature in condenser) failure
E5: Compressor stops three times in 24 hours because the
current is too high.
E6: While heating water, there is three times of T3 ≥ 100°C in 24 hours.
E7: There is electric leakage in Compress or outdoor motor, four way valve.
Recommendation: Call your tter to check or change the controller of ow.
6- Instructions of maintenance
This operation must be done by a professional, qualied person, each year.
• Clean the beck evaporator with a delicate brush and a water jet without any pressure (karcher
prohibited).
• Check the instructions and working points of the apparatus
• Check the safety measures
• Check the pressure of the refrigerating gas
• Clean the electic box and control die connections
• Check the connections of the masses to the earth

19
7 - The three electric heaters
1. Condenser electric heater *
Working conditions: During the compressor running:
A . the heater start in defrosting period, to Speed up defrosting, to reduce defrosting time;
B .When ambient temperature is less than 2°C, the heater start, and it stop when ambient
temperature is more than 4°C.
2. Compressor electric heater *
Working conditions:
A When the compressor is not working and ambient temperature is less than 0°C, electric
master will start;
B When ambient temperature is more than 2°C or compressor is working, electric heater will
stop.
3. Water tank electrical heater (only for heat pump with assistant electrical heater)
The electrical heater of water tank has two mode: manual or automatic
(1) Automatic: precondition is under compressor running: if the water temperature does not up 1°C
or temperature remain or down in a certain time (the certain time 15 adjustable from 1 to 10
minutes, windows default is 3 minutes), then the heater will start, until reach the setting
temperature. The heater can not be stop forcedly when the electric heater in the automatic mode.
The heater will be start forcedly during defrosting.
(2) Manual: press the button“ “ once to start the heater forcedly, until reach the setting
temperature it closes.
Or press “ “ again to stop the heater forcedly.
lt the water temperature has already reached the setting temperature, then it wills no eect to press
the button.
Also the heater will restore to automatic state after the water temperature reach Its desire.
when reach the setting temperature, the heater close and the light oft.
NOTICE!
The machine would give an alarm if the water tank`s sensor nds water temperature is 2°C or
less, User need to drain all inside water out to prevent unit damage from ice, also do it if
machine not be used a long time in winter.

20
AIR MAGNA 200
GREEN ENERGY SYSTEMS
8- Gas FIow Diagram
HEATING:
COOLING:
Exchanger
Exchanger
Compressor
Compressor
Water Outlet
Water
tank
Water
tank
Water Outlet
Water Inlet
Water Inlet
Four way
valve 2
Four way valve 1
Four way valve 1
Four way
valve 2
Capillary 1
Capillary 1Capillary 2
Capillary 2
Table of contents
Popular Heat Pump manuals by other brands

Trane
Trane CXAU Installation, operation and maintenance

Wolf
Wolf FERTIGFUNDAMENT CHA-07 Installation & Operating Instructions For Contractors

Vaillant
Vaillant geoTHERM SERIES installation instructions

Panasonic
Panasonic CS-E18NKUA Information

Fairland
Fairland TurboSilence InverX IXCR36 manual

STIEBEL ELTRON
STIEBEL ELTRON WWK 220 electronic Operation and installation