
21 3
OPERATING INSTRUCTIONS
AUTOMATIC MODE (MANUAL MODE – SEE PAGE 4)
Your Humidier Control is installed in the return air duct of your air
conditioning and heating system. During the rst heating season,
your Humidier Control needs to be set initially
to match your home’s condition. Please follow
these steps when adjusting your control.
1. Turn the dial setting knob to 5, which is
within the normal range. During the next
24-48 hours, it may be necessary to
adjust the dial for more or less humidity,
depending on your personal comfort and
home’s requirements. Refer to TABLE 1.
2. During the coldest portion of the rst heating season, minor
adjustments may be necessary. This is dependent upon your
individual home construction. Refer to TABLE 1.
TABLE 1 – OPERATION GUIDE
Condition Solution
Condensation on
windows.
Reduce the setting on the control dial
by 1 increment.
Humidity too low. Increase the setting on the control dial
by 1 increment.
Humidier does not
operate. (Solenoid
does not “click” when
control is moved to
TEST/RESET position.)
Turn dial to TEST/RESET. Make certain
furnace blower is operating and
furnace is calling for heat. If unit still
doesn’t operate, consult a heating
contractor.
Humidier won’t
shut off.
Turn dial to OFF. If unit continues to
operate, consult a heating contractor.
Test mode.
System operation is checked by
setting the knob to TEST/RESET. Make
certain furnace blower is operating
and furnace is calling for heat.
Humidier will operate for one minute.
The relative humidity in your home will now be controlled to meet
your needs and should not need further adjustment during future
heating seasons. Make note of the dial setting in the event you
temporarily move the knob when performing annual maintenance
of the humidier.
ADDITIONAL INFORMATION
Your humidier is a high precision system that will accurately
maintain the relative humidity in your home. For every 1°F change
in outdoor temperature, the Automatic Humidier Control will
automatically adjust the indoor relative humidity (RH) by 1/2%. If
you would like to determine the relative humidity in your home,
follow these steps:
1. Determine the outdoor temperature.
2. Activate the furnace blower by setting your thermostat to a
higher temperature.
3. Turn the Humidier Control dial setting to the OFF position.
Then, slowly turn the dial clockwise until you hear the solenoid
valve “click on”. Next, slowly turn the dial counterclockwise until
you hear the solenoid valve “click off”. At this point, make note
of the dial setting.
4. Locate your dial setting on TABLE 2. Follow the dial setting
to the right until it intersects with the current outdoor
temperature. This is the relative humidity in your home under
existing conditions.
TABLE 2 – % RELATIVE HUMIDITY GUIDE
Outdoor Temperature (°F)
-10°F 0°F 10°F 20°F 30°F 40°F
Dial Setting
110% 10% 10% 15% 20% 25%
Relative Humidity (%)
210% 10% 15% 20% 25% 30%
310% 15% 20% 25% 30% 35%
415% 20% 25% 30% 35% 40%
520% 25% 30% 35% 40% 45%
625% 30% 35% 40% 45% 45%
730% 35% 40% 45% 45% 45%
As an example, if the outdoor temperature is 20°F and, following
step 3, the humidier turns off at 5on the dial range, then the
relative humidity in your home is 35%.
5. Return the thermostat and control to their original settings.
The healthy humidity range is 40-60%, but on cold days that can
result in condensation forming on cold surfaces which can cause
damage to your home. The Humidier Control will automatically
adjust the humidity setting lower to compensate. The Humidier
Control will accurately control the humidity in your home to a
maximum of 45% RH and a minimum of 10% RH. The values of
outdoor temperature and dial settings may fall in between or
outside of the listed values in TABLE 2. In these cases, you can only
approximate your home’s actual indoor relative humidity.
MANUAL MODE (AUTOMATIC MODE – SEE PAGE 1)
Your Humidier Control is installed in the
return air duct of your air conditioning
and heating system. When installed
in the manual mode, it is important to
anticipate a drop in outdoor temperature
and reduce the setting accordingly to
avoid excess condensation. For example,
with an outdoor temperature of 20°F,
the correct setting will be 35%. If the
temperature is expected to fall to 0°F,
reduce the setting to 25% several hours
prior to the temperature change.
See TABLE 3 for the
recommended settings.
These settings represent a
compromise between healthy
humidity levels (40-60% RH)
and protection from window
condensation. For example,
a range of 40-60% indoor
humidity in wintertime may
be ideal for comfort, but
would result in damaging
condensation. Thus, observing
recommended humidity levels
on the Humidier Control is
important. Condensation on
the inside surface of windows
in the form of fogging or
frost is indicative of over-
humidication. This same
condensation can occur in
other areas of the home,
resulting in damage.
90-1054
90-1055
TABLE 3 – OUTDOOR
TEMPERATURE / INDOOR
RELATIVE HUMIDITY
Outside
Temperature
Recommended
RH
+40°F 45%
+30°F 40%
+20°F 35%
+10°F 30%
0°F 25%
-10°F 20%
-20°F 15%