SETUP & TESTING
System setting Setting range, default in bold
09 1st stage differential 1°F (0.5°C)
1°F to 4°F (0.5°C to 2°C)
10 2nd stage differential (8448, 8466) 1°F (0.5°C)
1°F to 4°F (0.5°C to 2°C)
11 3rd and 4th stage differential (8448HP, 8466HP) 1°F (0.5°C)
1°F to 4°F (0.5°C to 2°C)
12 Reverse valve (8446, 8448HP, 8465, 8466HP) 0 – O/B energized in cooling (O)
1 – O/B energized in heating (B)
13 Stage rate* 2
1 to 5 or “OFF” to disable
14 Deadband (auto mode) 3°F (2°C)
2°F to 5°F (1°C to 3°C)
15 Progressive recovery (8463, 8465, 8466) 0 : Progressive recovery is disabled
1 : Progressive recovery is enabled
16 Low Balance Pt. (8446, 8448HP, 8465, 8466HP)
System setting 05 must be enabled
20°F (-7°C)
0°F to 60°F (-18°C to 16°C) or “OFF” to disable
*Accumulation of equipment run time in equipment staging determination.
1 = more rapid staging of equipment (comfort).
5 = slower staging of equipment (economy).
SYSTEM SETUP INSTRUCTIONS (CONTINUED)
SETUP & TESTING
System setting Setting range, default in bold
17 High Balance Pt. (8446, 8448HP, 8465, 8466HP)
System setting 05 must be enabled
65°F (18°C)
0°F to 80°F (-18°C to 27°C) or “OFF “ to disable
19 Program format (8463, 8465, 8466) 0 – 5/2 program (Weekdays and Weekends)
1 – 5/1/1 program (Weekdays, Sat. and Sun.)
20 Change air filter OFF
1, 3, 6, 12 months or “OFF” to disable
21 Change water panel**
Set number of months until reminder is required
OFF
1 to 12 months or “OFF” to disable
22 Humidifier type** 0 : Flow through type humidifier (1 reminder per season)
1 : Drain-less type humidifier (2 reminders per season)
23 Service dehumidifier OFF
1 to 12 months or “OFF” to disable
24 Service HVAC OFF
1 to 12 months or “OFF” to disable
25 2 or 4 Program Events 0 = WAKE and SLEEP
1 = WAKE, LEAVE, RETURN, SLEEP
**If humidifier type is set to Drain-less, then the first reminder is based on the system setting 21, second
reminder will activate 3 months later. If humidifier type is set to Flow through, then the first reminder is based
on system setting 21, second reminder will activate 12 months later.
SYSTEM SETUP INSTRUCTIONS (CONTINUED)