Aqua Cooler VERSAFILLER Series User manual

Your Partner in Cool.
Usage and Care
Manual
Models: AC-P8EBFSLTTY-ASM & AC-PV8EBFSLY-ASM
VERSAFILLER
SERIES

32 Your Partner in Cool.
PRODUCT DIAGRAM PRODUCT DIAGRAM

54 Your Partner in Cool.
IMPORTANT INFORMATION ABOUT GROUNDING
• To provide additional protection from the risk of shock, this unit must always be connected to
a residual-current device (RCD) or a breaker. Use of joint cable should be avoid.
• This appliance must be grounded. Improper use of the grounding plug can result in a risk of
electric shock, causing serious injury and possibly death.
• This appliance is equipped with the power terminal or power cord. A ground connection
must be connected into a properly grounded, polarised outlet.
• Consult a qualied electrician if the grounding instructions are not completely understood, or
if doubt exists as to whether the appliance is properly grounded.
• Do not under any circumstances cut or remove the third (ground) prong from the power cord
plug (if provided). Do not use an adapter plug with this appliance.
INSPECTION
Inspect the cartons and various components for evidence of rough handling and concealed
damage. Damage claims should be led with the carrier.
INSTALLATION
The installation must be in accordance with AS/NZS 3500.1 and AS/NZS 3500.2, as well as the
instructions below. Pipe jointing and installation is a trade skill and Aqua Cooler recommended
this process is performed by qualied personnel only.
The water cooler contains the refrigeration system and is always mounted on the right side. This
unit can be congured with the water cooler high or low. Refer to proper roughing in drawing for
location of plumbing and electrical service. Filter units have additional instructions on a label
inside fountain side access panel. Read these before installing unit. This drinking water cooler is
designed to be operated at a water supply line pressure of up to 100 psi (690 kPa). A pressure
regulator must be installed in front of the unit’s water inlet if the water pressure (including any
possible pressure spikes) could exceed 100 psi (690 kPa).
FLUSH BUILDING WATER SUPPLY BEFORE INSTALLING UNIT.
Install wall hangers as shown on the desired roughing in drawing. Wall hangers are shipped
fastened to the backs of each unit.
To congure this cooler for right side high or right side low installation, refer to details below.
Bottom screws of the appropriate side panel may be temporarily removed to install patch plate.
Assemble drains as shown below, matching the position of the gaskets to the contour of the
cooler tops.
Mount the water cooler on the right hanger.
Mount water fountain on left side hanger while routing “Water In” tube through access hole to
stop valve as required. Remove cap from “Drain/Remote Cold Water” connection and insert
“Water In” tube.
All provided waste drain parts for eld installation are packed in the water fountain. Assemble
drain per appropriate roughing in drawing. The short leg of the crossover piece will be on the
water cooler side. When unit has an internal waste trap, it should be wrapped with insulating
tape to prevent sweating. Use of 1-3/4” knockout for a waste line is not recommended because
of potential conict with ADA* toe space requirements. Check with your local building code
inspector for approval.
Install a shut off valve in water supply line. An in-line strainer is furnished in “Water Supply” tube.
Connect “Water Supply” tube to shut off valve. This connection should not be a solder joint or
are connection to allow access to the strainer service. To ease removal of the strainer, a sheet
metal screw may be lightly threaded into the open end.
Rotate fan blade by hand to see that it is free of obstructions.
Check available power supply against water cooler data plate to assure correct electrical service.
This drinking water cooler is intended to be connected to a 20A minimum ground fault circuit
interrupting (GFCI) device to meet UL requirements. Plug power supply cord into wall outlet. The
rear most 1-3/8 diameter knockout in frame bottom is for an externally located electrical supply.
Make sure knockout hole edge is smooth and free of any burrs. Use of Heyco bushing #2184 in
knocked out hole is recommended to prevent damage to service cord and to close up excess
opening around cord. Route cord so it does not interfere with ADA* space requirements.
IMPORTANT SAFETY INSTRUCTION
When using electrical appliances, basic safety precautions should be followed to reduce the risk
of re, electric shock and injury to persons or property. Read all instructions before using any
appliance.
• Keep combustible material such as furniture, bedding, pillows, clothes and/or papers away from
the unit.
• Do not operate this, or any other appliance, with a damaged power cable.
• No other appliance should be connected into the same power supply.
• Do not run the power cable over carpeting or other heat insulators.
• Keep the power cable away from high trafc areas.
• Do not submerge the power cable in water.
• We do not recommend the use of joint cables as they may overheat and increase the risk of re.
• Exercise caution and use reasonable supervision when the appliance is used by or near children.
• Keep a minimum distance on each air-louvre side free.
• Do not use this product to dispense anything other than water.
• Do not use this product to dispense anything other than water.
• This appliance must be installed on an even and at surface or wall.
• If the power cable or terminal is damaged, one of its service agents or a similarly qualied person
must replace it to avoid hazard.
• Switch off the main power source before servicing the appliance.
• Warranty will be voided if installation is not carried out as detailed in this instruction manual.
• The compressor motor is equipped with an automatic reset protector which will disconnect the
motor from the line in case of an overload.

76 Your Partner in Cool.
INSTALLATION CONT.
To ll cold water tank on water cooler, open water supply line shut-off and push any one of front
push pads to allow water to ow to bubbler. On TM and TT models, actuate solenoid by holding
one hand approximately 1” from infrared sensor (under front edge of shelf). Run water until stream
is free of bubbles. After approximately 30 seconds run time, solenoid valve will automatically shut
off. To reactivate, move hand away for an instant and then again place it in front of sensor.
To Adjust Bubbler stream:
All models are equipped with a cartridge regulator. The standard push pad and electric eye
models have a slot at back of underside of shelf. Insert a screwdriver in this slot to adjust regulator.
Turn adjustment clockwise to increase stream height. To access PGV8ACSL and PGVF8ACSL
adjustment, remove the Bezel and Button from front of cooler.
To adjust beam range of sensor (TM and TT models only):
1. Shut off water. Actuate sensor to relieve water pressure. NOTE: Unplug cooler or avoid
touching fan blade and electrically live components when adjusting sensor.
2. Remove six screws holding top on. Lift up front to access sensor.
3. To adjust sensing distance, use a mini-screwdriver (2.5mm at tip or smaller) and rotate
adjustment potentiometer screw on side of sensor. Turn clockwise to sense objects further
away. This is represented by thicker end of curve on sensor label. The screw can be turned a
maximum of ¾ turns. Sensor has a maximum range of approximately 14”, it is factory set at
4”.
4. NOTE: Do not turn adjustment as high as it can go. If you do, sensor will lock on until you
turn sensing distance back down.
5. There is an adjustable on-time delay if desired. It is factory set for immediate response upon
activation. To adjust on-time delay, rotate blue knob on timer clockwise. The maximum on-
time delay is 1 second. Water will shut off immediately once object is removed from under
shelf. Maximum on-time is 30 seconds should someone tamper with sensor. NOTE: Floors
with a reective nish, i.e., ceramic tile, may cause false actuation no matter what sensor
adjustment is for distance. Therefore, do not install unit in such an area or dull surface of oor
so it will not reect light.
6. Replace top, starting at back of unit, snug up screws, but do not overtighten.
MAINTENANCE
The only maintenance operation required is the removal of dirt and lint from the condenser of
the water cooler. Inspection should be made at 3-month intervals. Disconnect the power supply
cord, then clean the condenser with a small stiff non-wire brush when required. Observance
of this procedure will ensure adequate air circulation through the condenser so operation is
efcient and economical.
TROUBLESHOOTING
PROBLEM POSSIBLE CAUSE REMEDY
Controller is faulty Temperature sensor is faulty Check sensor connections.
Controller display is faulty Contact Aqua Cooler service team.
No water owing out of
the unit Water source has been suspended Restore water supply
The system is clogged Check the pipes
Solenoid valve is faulty Check controller and cable connections
Unit does not dispense cold
water The cooling controller is turned off Check the position of the mechanical thermostat
and set to desired temperature
Power failure Check the power cord is properly plugged in or if
there is a power outage
The ventilation around the unit is
insufcient Ensure sufcient ventilation space around the unit
System malfunction Contact Aqua Cooler service team.
The temperature of the incoming water
it too high Ensure the unit is not placed in direct sunlight or
close to other heat sources
Unit is noisy during operation Chiller unit in the machine is not level Place the chiller unit on a level at surface.
Chiller unit is touching other objects Ensure the chiller is standing free of any surrounding
objects.
The water being dispensed
has a strange taste. This is not uncommon with new
water oolers. Do not worry, this is not
dangerous to your health.
Flush as per installation instructions. Perform
cleaning procedure.
OVERLOAD PROTECTION
The compressor motor, where used, is equipped with an automatic reset protector which will
disconnect the motor from the line in case of an
overload.
DISCONTINUED USE
TO DISCONTINUE USE OF WATER COOLER AND WATER FOUNTAIN
1. Close water shut off valve.
2. Provide container to catch water to be drained.
3. On push button model, disconnect power supply cord then disconnect water supply line at
shut off valve. Route water supply line to container and actuate push button. If this drains
too slowly for you, prepare 3/8” ID tube or 3/8” OD tube with quick-connect tting and
remove screw plug in tank drain. Slide tube over drain and route to container. Replace
screw plug when draining is complete. Do not overtighten. O-ring only needs to be snug to
seal.
4. On TM and TT models, disconnect water supply line at shut off valve. Place water supply line
in container and actuate solenoid as explained in Step B12. If this drains too slowly for you,
disconnect power supply cord and prepare 3/8” ID tube or 3/8” OD tube with quickconnect
tting and remove screw plug in tank drain. Slide tube over drain and route to container.
Replace screw plug when draining is complete. Do not over-tighten. O-ring only needs to
be snug to seal.
5. ALWAYS DRAIN ALL WATER WHEN FREEZING TEMPERATURES ARE ANTICIPATED AND
BEFORE SHIPPING THE WATER COOLER

Your Partner in Cool.
WARRANTY & SERVICE REGISTRATION
For All Aqua Cooler Water Cooler and Fountain Products
Effective July 2017
Aqua Cooler Pty Ltd warrants this appliance to the rst purchaser as follows and subject to the
stated conditions.
12 Month Comprehensive Warranty - Any defect in the appliance occuring within the rst
twelve months from the date of purchase will be rectied free of change by Aqua Cooler Pty Ltd
or by any authorised independent Service Agent.
24 Month Extended Warranty - Aqua Cooler Pty Ltd agrees to replace any part of the
hermetically sealed refrigeration system which becomes inoperative in the two years following
the rst years comprehensive warranty. This extended warranty covers the compressor,
condensor, and interconnecting refrigeration pipework. It excludes compressor relays, overloads
and all other components of this appliance. This extended warranty does not include service,
repair or labour costs or any pickup and/or freight charges. Aqua Cooler at its sole discretion
may replace the cooler with a new or refurbished cooler of a similar age.
Warranty Exclusions
1. Any costs associated with the removal and reinstallation of repaired or replaced units.
2. Travel expenses to locations further than 100km from any Australian Capital City CBD or
further than 100km of a registered Service Agent.
3. Damage to units where mains connected pressure is higher than 700kPa and a pressure
limiting valve is not installed.
4. Where the unit is not installed as per installation instructions found within the supplied user
manual.
5. The warranty does not cover defects occasioned by misuse, alterations, accident or where the
water cooler has been stored on its side.
FOR ANY CLAIMS UNDER THIS WARRANTY PLEASE CONTACT AQUA COOLER PTY LTD
PHONE: +61 (02) 9721 9300 OR EMAIL: support@aquacooler.com.au
Thank you for your custom and we hope our product provides many years of fault free
operation. To enable us to register your warranty and provide the best possible service should a
problem occur, we recommend you ll out the section below and return it to us immediately.
This warranty is provided in addition to other rights and remedies you have under law: Our
goods come with guarentees which cannot be excluded under the Australian Consumer Law.
You are entitled to replacement or refund for a major failure and to compensation for other
reasonably foresseable loss or damage. You are also entitled to have the good repaired or
replaced if the goods fail to be of acceptable quality and the failure does not amount to a major
failure.
Warranty & Service Registration Form
Please ll in this form and mail to us or send via email to support@aquacooler.com.au. If this form is not completed and
returned the warranty period will be deemed to have commenced from date of manufacture.
COMPANY NAME (if applicable):
CONTACT NAME: PHONE NUMBER:
ADDRESS:
SUBURB: POSTCODE:
MODEL NUMBER: SERIAL NUMBER:
PURCHASED FROM:
DATE OF PURCHASE:

Your Partner in Cool.
Phone Numbers
Sales: 1300 278 226
Service: 1800 278 226
Address
U14, 2-12 Knobel Court
Shailer Park QLD 4128
Internet
www.aquacooler.com.au
info@aquacooler.com.au
Other manuals for VERSAFILLER Series
1
This manual suits for next models
2
Table of contents
Other Aqua Cooler Outdoor Fountain manuals
Popular Outdoor Fountain manuals by other brands

Campania International
Campania International Dragonfly FT-196 instructions

Serenity
Serenity Cascading Rock Pool Water Feature instruction manual

LuxenHome
LuxenHome WHF1741 instruction manual

LuxenHome
LuxenHome WHF925 instruction manual

LuxenHome
LuxenHome Polyresin WHF813 instruction manual

LuxenHome
LuxenHome WHF723 instruction manual