
5
Installation of Disc Diffusers
The Aquaflex Disc Diffuser units are furnished completely factory assembled. The only work required by the Contractor is
the installation and placement of the diffuser units on the laterals piping. Aquaflex diffusers utilize EPDM rubber membranes
specially
formulated for water and wastewater aeration facilities, as the air diffusion media. Alternate membrane materials are
available for special applications. Aquaflex Technical Department recommends care in handling and storage to prevent tearing,
puncturing or fouling of the rubber membranes. If units are to be stored before installation, store in a clean, well ventilated, cool
location that avoids potential mechanical damage. Air distribution through the Aquaflex diffuser is a function of the individual
diffuser elevation.
For proper system operation, Aquaflex Technical Department recommends a leveling tolerance of ±3/8" for
the diffuser unit. If the diffusers are mounted with excessive elevation tolerances, the airflow distribution in the system will be
adversely impacted.
The Aquaflex aeration system employs individual diffuser assemblies attached directly to the lateral piping. Aquaflex
normally
designs the aeration piping system to provide uniform distribution of air without requiring adjustment of the
isolation/throttling
valves on the laterals with the exception in situations where water level variation exists. However, these
valves are typically
provided for direct control of airflow distribution on large aeration systems or for process control.
Aquaflex Technical Department has designed the Aquaflex Disc diffuser for easy on field installations. Place the threaded
end of t h e diffuser into the threaded outlet hole in the lateral pipe. Tighten the diffuser unit by hand rotating clockwise. DO
NOT OVER
TIGHTEN. Over tightening the unit will cause failure to lateral piping, diffuser unit or both. When blower assemblies,
header piping,
air laterals, and all units are properly installed, system is ready for startup. During all of the installation
procedure, please do not grab around the membranes.
Refer to Aquaflex Startup Instructions for details.
3.STARTUP
Startup Instructions
These instructions cover the general startup requirements for the Aquaflex diffuser system. Special startup
requirements outlined
in the Engineer’s specifications, contract documents, or instructions offered by Aquaflex Technical
Department shall be supplementary to or take precedent over these general instructions.
No work may be done in the basin area after the diffusers have been placed. All works in or at the basin could cause
damage to
the diffusers (e.g. painting or welding, finishing concrete works and more). Remove all tools and loose objects (even
small stones)
from the basin floor before filling up the basin with water.
A trial run in the basin using clean water is to be carried out directly after installation. Performance and sealing of each
diffuser unit is tested on after the other, using a maximum 20 cm water level over the membrane disc diffusers. The
presence of
leaks becomes visible after shutting off the air supply. Due to the lower pressure loss of leaks air bubbles will rise at the leaky
places, while the membranes close up.
An overview of startup procedures is related below:
Confirm that piping and diffusers are level by filling the basin with water. Adjust supports for diffusers as required
Continue filling the basin with water until the diffusers are 2, 5 cm (1”) to 5, 0 cm (2”) under water. In the event of air leaks
the diffusers are accessible
Activate the blower and introduce air to the aeration system. Check piping and diffusers for leaks, and repair if required.
For blower components refer to the blower installation and start up to ensure that all blower components are mounted
properly
and
ready for operation. Contractor is to confirm the cleanliness of the air piping. If existing header piping is used, the
air purge or water flush cleaning procedure is recommended prior to installation of Aquaflex units to remove any internal
debris that may have been accumulated inside the air pipeline. In order to avoid clogging from the inside the air supply pipes,
drops and header pipes must be cleaned from impurities, such as dust, sand, stones, pieces of wood, etc.
Should operation not start immediately after the test run, the water level should be increased up to 1 meter. This water level
must be maintained until the system is put into operation. Pay attention to water evaporation or ice formation. During periods
of frost, the water level must amount to at least 10% of the frost temperature (in meters). Example: the water level is 2m at
-20 °C. In order to avoid negative environmental influences on the membrane (e.g. UV-light), the period between installation
and trial run
(water coverage of diffusers) should be as short as possible.