6Cassee Stove Installaon Guide — BK605 Rev 04
Air For Combuson
All stoves require venlaon to burn safely and
correctly. There are a number of requirements that
need to be met when installing a stove, for example,
allowing for the permeability of the house (air
permeability is the general seepage of air into the
house via air vents, doors and windows etc.).
There must always be a permanent means of
providing air for combuson into the room in which
the stove is installed. Air starvaon will result in poor
ue draw and may cause smoke to leak into the room.
For all installaons it is recommended that a
permanent vent with a total free area of at least
550mm2 for every kW above 5kW should be
connected directly to the outside air. Installaons in
properes built aer 2008 should have their vent
increased by a further 330mm2 for each of the rst
5kW. Alternavely this air can be supplied through an
external wall of an adjacent room, which itself has to
be connected to the room the appliance is installed by
a permanent vent of the same size.
Note: If the appliance is ed with a draught stabiliser
(or if one is ed to the ue pipe or chimney in the
same room as the appliance) then the permanent air
entry opening (or openings) should be increased by
300mm2 for each kW of rated output up to 5kW and
an addional 850mm2 for each kW output over 5kW.
If there is more than one appliance in the property
then each appliance must be supplied with adequate
combuson air so that all appliances can be lit
simultaneously.
The posioning of any air vent must be so that it
cannot be liable to blockage or obstrucon. Ideally it
should also be posioned where it is unlikely to cause
a cold draught. It should not be posioned in the
replace recess.
For more detailed guidelines on required venlaon
sizes please refer to the Document J Building
Regulaons (Combuson Appliances) at the
www.planningportal.gov.uk website.
If you plan to use an external air supply on appliance,
all I Series cassee stoves are factory ed with an air
supply adaptor located on the base of the appliance
that will accept a exible pipe of a diameter 102mm
externally, see Fig. 1 and 4 for details.
The air duct ed must be of a minimum diameter of
100mm, non combusble and ducted to the outside in
a manner that will not eect the performance of the
stove.
No sharp bends and a maximum duct length of 10
metres is permissible.
Where the duct terminates on an external wall ensure
that there is no risk of blockage with leaves or
accidental placement of items, ensure there is no risk
of ingress of moisture or access for rodents.
Avoid ng the air inlet pipe through a wall that may
be unduly eected by prevailing winds that may cause
a sucon on the pipe bringing combuson products
back down the ue.
In extreme cases the placement of the terminal on the
external wall may pose problems and remedial acon
may be required to relocate the terminal or provide
two terminals on apposite walls to balance the wind
eect.
Where the stove is connected to outside air and there
is NO draught stabiliser ed, there is no requirement
for a addional air vent, provided a successful ‘smoke
draw test’ has been carried out as part of
commissioning.
INSTALLATION REQUIREMENTS