ARCOL FFLB Series User manual

FFLB User Manual 200214 Page 1 of 8
USER MANUAL
PORTABLE LOAD –FFLB Series

FFLB User Manual 200214 Page 2 of 8
INDEX
1. TECHNICAL DATA
1.1 GENERAL DATA
1.2 LOAD DATA
2. COMMISSIONING
2.1 HANDLING
2.2 INSTALLATION
2.3 CONNECTIONS
2.4 SAFETY
3. LOAD CONTROL
3.1 CONTROL PANEL
3.2 PROCESS FLOW
3.3 SHUTDOWN
4. MAINTENANCE
4.1 GENERAL
4.2 TROUBLESHOOTING

FFLB User Manual 200214 Page 3 of 8
1. TECHNICAL DATA
1.1 GENERAL DATA
a. Control/Auxiliary voltage : 230V AC or 115V AC (Based on Model Selected in Table-1)
b. Control protection : Miniature Circuit Breaker (MCB)
c. Over Temperature Protection : Thermal Switch
d. Degree of protection : IP20
e. Overall Dimensions :
1.2 LOAD DATA
Model
Aux.
Supply
Test Voltage
Power
Load Steps
FFLB1KW-110V AC
230V AC
110V AC
1KW
0.25KW x 4
FFLB1KW-230V AC
230V AC
230V AC
1KW
0.25KW x 4
FFLB3KW-110V AC
230V AC
110V AC
3KW
1KW x2; 0.5KW x1; 0.25KW x2
FFLB3KW-230V AC
230V AC
230V AC
3KW
1KW x2; 0.5KW x1; 0.25KW x2
FFLB5KW-110V AC
230V AC
110V AC
5KW
2KW x1; 1KW x2;
0.5KW x1; 0.25KW x2
FFLB5KW-230V AC
230V AC
230V AC
5KW
2KW x1; 1KW x2;
0.5KW x1; 0.25KW x2
FFLB1KW-110V AC_A
115V AC
110V AC
1KW
0.25KW x 4
FFLB1KW-230V AC_A
115V AC
230V AC
1KW
0.25KW x 4
FFLB3KW-110V AC_A
115V AC
110V AC
3KW
1KW x2; 0.5KW x1; 0.25KW x2
FFLB3KW-230V AC_A
115V AC
230V AC
3KW
1KW x2; 0.5KW x1; 0.25KW x2
FFLB5KW-110V AC_A
115V AC
110V AC
5KW
2KW x1; 1KW x2;
0.5KW x1; 0.25KW x2
FFLB5KW-230V AC_A
115V AC
230V AC
5KW
2KW x1; 1KW x2;
0.5KW x1; 0.25KW x2
Table 1
Series
W x D x H in mm
FFLB1KW
482 x 375 x 179
FFLB3KW
482 x 375 x 311
FFLB5KW
482 x 375 x 356

FFLB User Manual 200214 Page 4 of 8
2. COMMISSIONING
2.1 HANDLING
Lifting handles can be used to move the equipment. Please ensure the equipment is handled carefully and
that it is not dropped.
2.2 INSTALLATION
The fans on the front panel provides the forced cooling the unit needs to work efficiently. Hence care must
be taken to ensure nothing blocks the fan and the air outlet.
The unit is designed to provide a protection conforming to IP20 level and is intended for indoor use only.
2.3 CONNECTIONS
An auxiliary/control voltage is required for the operation of the fans, meters and some internal controls.
A steady 230Vac 5A or 115Vac 5A (Based on Model Selected as per Table-1) source can be connected on
the front panel marked Aux Supply with the cable provided.
2.4 SAFETY
oIt is suggested that the unit is operated by a competent person who has received adequate training.
oNever connect or disconnect the load cables under testing. Perform a full shutting down of the load as
per 3.3 before disconnection
oNever exceed the maximum test voltage of the unit.
oExtra care must be taken when relocating the load bank, dropping the unit could damage the functionality
of the unit.

FFLB User Manual 200214 Page 5 of 8
3. LOAD CONTROL
3.1 CONTROL PANEL - FFLB1KW
MASTER LOAD (Green Indicator): Indicates load is in ON condition and load step switches can be activated
OVER TEMPERATURE (Red Indicator): Indicates an over temperature in the unit.
CIRCUIT BREAKER: Protects the load unit from over current & short circuit.
STEP CONTROL SWITCHES (Toggle switches): The switches control the defined power steps. The total power
of the system will be the sum of the activated steps.
LOAD OUTPUT TERMINALS (P, N & E): The test source, Phase (P), Neutral (N) and Earth (E) should be connected
to these terminals
VOLTAGE: These terminals are to be used if an external voltmeter is to be connected.
CURRENT: These terminals are to be used if an external ammeter is to be connected. The shorting link can be
removed before using an external ammeter. The link must be in place to function without an externally connected
ammeter.

FFLB User Manual 200214 Page 6 of 8
3.2 CONTROL PANEL - FFLB3KW & FFLB5KW
MASTER LOAD (Green Indicator): Indicates load is in ON condition and load step switches can be activated
OVER TEMPERATURE (Red Indicator): Indicates an over temperature in the Unit.
CIRCUIT BREAKER: Protects load unit from over current & short circuit.
STEP CONTROL SWITCHES (Toggle switches): The switches control the defined power steps. The total power
of the system will be sum of the activated steps.
LOAD OUTPUT TERMINALS (P, N & E): The Phase (P), Neutral (N) and Earth (E) of the test source are to be
connected to these terminals
DIGITAL METERS: Meters will show the voltage and current readings.

FFLB User Manual 200214 Page 7 of 8
3.2 PROCESS FLOW
3.3 SHUTDOWN
1. Turn off all the step control switches.
2. Turn off the Circuit Breaker.
3. Turn off the Auxiliary Supply.
Start
Connect the Auxiliary
Power 230V AC or 115V AC
to Load unit
Connect the Test supply to
Load output (P & N)
Terminals
ON?
Check Power
Connection &
Fuse
Observe
FAULT
Indicator
Y
N
N
ON?
Consult
Troubleshooting
Guide 4.2
Y
Observe the MASTER
LOAD indicator and Fans
Shutdown
Turn on Aux Power switch
& Circuit breaker
Testing
Enable the Desired load
steps

FFLB User Manual 200214 Page 8 of 8
4. Maintenance
4.1 GENERAL
oThe unit is designed to have a maintenance free operation. Care to be taken that the air inlet and outlets
are not blocked.
4.2 TROUBLESHOOTING
oNo indicator is glowing:
✓Auxiliary supply not connected or not available
✓Failure of internal power supply
✓Failure in control Circuit
oFans are not running:
✓Fuse may have blown out
✓Failure in internal power supply
✓Auxiliary Switch may have problem
oMASTER LOAD indicator is not glowing:
✓Fuse may have blown out
✓Indicator is damaged
oStep Control Switches are not working when it activated:
✓Circuit breaker is not turned ON
✓Thermal switch is not working
✓Internal connection may have got disconnected
For any further queries & any information, please contact:
ARCOL UK Ltd
Unit 5, Threemilestone Industrial Estate
Threemilestone
Truro
Cornwall
TR4 9LG
U.K
This manual suits for next models
15
Table of contents