Control access may be set to Local- or Remote control (local as default). When local control is
enabled it is not possible to control object trough bus and vice versa.
Type name of the object. As default objects are named as Object1…5.
Select
type of the object
between grounding disconnector, motor controlled disconnector,
circuit breaker, and withdraw able circuit breaker (circuit breaker as default).
Object status
can be between Bad, Closed, Open and Intermediate. Intermediate is the phase
between open and closed where both status inputs are equal to zero (0). When both status
inputs of the object are one (1) the status of the object is Bad.
Object withdraw status
could be Bad, Cart In, Cart Out or Intermediate. Intermediate is the
phase between open and closed where both status inputs are equal to zero (0). When both
status inputs of the cart are one (1) the withdrawn status is Bad.
Additional status information
gives feedback from the object whether the opening and closing is
allowed or blocked, whether the object is ready or the synchronization status is ok.
Activate Use Synchrocheck
or
Use Object Ready.
Closing the object is forbidden if sides are
out of sync or object is not ready to be closed.
Settings
-menu also includes statistics for open- and closed requests. Stats can be cleared by
choosing
Clear statistics
→
Clear
.
Object has Open- and Close inputs and withdrawable object has In- and Out inputs. Object
Ready- and external Synchrocheck permission have status inputs as well. Digital inputs, Logical
inputs or outputs, stage starting- tripping- or blocking, RTDs and object status information can
be used to indicate the status.
Object open- and close signals of an object are connected to physical output relays.
Separate timeouts for objects are set in Settings menu. Synchronization wait- and Object Ready
wait timeouts are settable between 0.02…500.00 s (default 200ms, step 20ms). If time expires
the controlling of object fails. Same time settings apply with Maximum close- and open
command pulse lengths. Control Termination Timeout is set to 10 seconds as default. After the
set delay if the controlled object does not respond accordingly the procedure is terminated and
there will be fail message.
Access level for MIMIC control is selected between User, Operator, Congurator and Super
user. To control MIMIC the terms of user access level (password) has to be fullled. As default
the access level is set to Congurator.
For object local and remote controlling digital inputs can be used. Remote controlling via bus is
congured in protocol level.