Arthur Grillo DPC200 User manual

Installation and operation manual
DPC200 -
DIFFERENTIAL PRESSURE CONTROLLER
Low pressure with PI-control-mode
Doc.-no.: DPC200_01_EN Issue: 11/2015

2
Doc.-no.: DPC200_01_EN Issue: 11/2015
Manufacturer:
Phone:
Fax:
E-Mail:
Website:
Issue:
Doc.-no.:
Arthur Grillo GmbH
Am Sandbach 7
40878 Ratingen
0 21 02 - 47 10 22
0 21 02 - 47 58 82
www.grillo-messgeraete.de
www.sensor-store.de
11/2015
DPC200_001_EN
This documentation including all parts is protected by copyright.Any utili-
sation or modication other than permissible under the strict limitations of
copyright law is prohibited and liable to prosecution without the approval
of the Arthur Grillo GmbH.This applies in particular to duplications, trans-
lations, microlming and storage and processing in electronic systems.

3
Doc.-no.: DPC200_01_EN Issue: 11/2015
TABLE OF CONTENT
Table of content
1 General safety instructions 04
1.1 Signal words for safety instructions 04
1.2 Used pictograms and symbols 04
1.3 General notes 04
2 Product description 04
2.1 Type plate 05
2.2 Intended use 05
2.3 Functional description 05
3 Installation 06
3.1 Dimensions 06
3.2 Wall mounting 06
4 Starting up 07
4.1 Overview DPC200 07
4.2 Schematic view inside 07
4.3 Pressure connections 07
4.4 Electrical connection 08
4.5 Zero adjustment 08
5 Operation 08
5.1 Start menu 08
5.2 Menu structure 09
5.3 Measuring mode 10
5.4 Control mode 11
5.5 Adjustable parameters 12
5.6 Function alarm output 13
6 Maintenance 13
7 Warranty 14
8 Troubleshooting 14
9 Disposal 14
10 Specications 15
10.1 CE-labelling 16

4
Doc.-no.: DPC200_01_EN Issue: 11/2015
GENERAL SAFETY INSTRUCTIONS
1. General safety instructions
1.1 Signal words for safety instructions
The safety instructions in this operation manual are designed to prevent hazards.They can
be found in the operation manual before an operation / task / activity is described, which
can entail a possible hazard.
Identication of a hazard with a low risk, which can lead to material
damage or minor or moderate bodily injuries.
CAUTION
1.2 Used pictograms and symbols
In this manual the following symbols are used:
General hazard symbol (dan-
ger, warning, caution)
2. Product description
The differential pressure controller DPC200 measures low pressure of non-aggressive
gases, particularly of air.
Signal word for important information regarding the product, which
needs to be specically pointed out.
NOTICE
Hazard word Type of hazard
Hazard source
Hazard prevention
1.3 General notes
This manual contains information for installation and operation of
the pressure controller and is exclusively for the operator and ex-
pert staff. The guidelines in this manual will help to avoid danger
and downtime.
NOTICE
General information

5
Doc.-no.: DPC200_01_EN Issue: 11/2015
2.1 Type plate
2.2 Intended use
The range of application of the device is e.g. in air conditioning systems for fan control,
for pressure control in rooms or lter control. As analogue output the operator can use
a signal from 0 ...10 V DC. Depending on the settings the device the signal has different
meanings:
1. Is the device is used as a pressure sensor, the output signal proceeds proportional to
the measured pressure.
2. As a volume ow sensor the device offers a square root signal.
3. With pressure resp. volume ow regulation the output signal stands for the control
variable of the PI-control.
2.3 Functional description
A soft silicone diaphragm is used as sensor. Under the inuence of the differential pressure
the membrane displaces against a measuring spring until spring force compensates the
pressure charging on the diaphragm. A contactless differential transformer and suitable
electronics convert this displacement into a continuously variable output voltage signal.
The DPC200 combines different functions:
1. On the one hand it is used as a measuring device. In the measuring mode the differ-
ential pressure is shown on the display, and it is given as a proportional 0...10 V DC
output signal.
2. Besides the measuring mode the DPC200 also can be operated in a control mode.
Two setpoints can be adjusted in the device and can be selected with the potential free
contact input. The PI-Algorithm settles the measured differential pressure with the
setpoint and operates the actuating variable so that a constant pressure results accord-
ing to the setpoints is set.The control variable is given as a 0...10V DC output signal.
Besides the quantity ‘differential pressure’ also the quantity ‘volume ow’ can be used for
measuring and for regulation.
PRODUCT DESCRIPTION
DPC200- 500
measurement ran
g
e:
supply voltage:
signal output:
part-no.: 2567 serial-no.: 15. 4700 IP54
Arthur Grillo GmbH • Ratingen Made in Germany
US(1+ 2-) = 10 ... 30 Vdc / 24 Vac
Uout (3+ 4-) = 0 ... 10 V
pressure controller
0 … 500 Pa
1. Product name
2. Measuring range
3. Supply voltage
4. Signal output
5. Serial no.
6. Manufacturer
1. 2.
3.
4.
5. 6.

6
Doc.-no.: DPC200_01_EN Issue: 11/2015
INSTALLATION
3. Installation
The differential pressure controller DPC200 is designed for wall mounting.
When selecting the installation site please note the following factors:
• The mounting surface must be solid enough and vibration-free.
• The environment has to full the ambient climatic conditions as given in the technical
data.
Material damage
Read the manual carefully before installation and operation
Only experienced stuff may connect the device and bring it into
operation.
CAUTION
• The device is position depended.
• It is important that the assembly is vertical.
• The DPC200 can be mounted on a wall.
NOTICE
3.1 Dimensions
All dimensions in mm.
3.2 Wall mounting
1. Hold the DPC200 against the wall. Mark the mounting holes.
2. Bore mounting holes for sufciently dimensioned screws resp. dowels.
3. Press in dowels.
4. Put the screws through the tightening channels of the housing screws so that the
screws stick out on the backside of the housing.
5. Place the device with the screws exactly onto the mounting holes with the dowels.
6. Tighten screws.
ø6
ø5
M16x1,5
4,5
-+
104
54
95
70

7
Doc.-no.: DPC200_01_EN Issue: 11/2015
INBETRIEBNAHME
4. Starting up
The differential pressure controller DPC200 is designed for wall mounting.
Please note when selecting the site, the following factors:
• The mounting surface must be solid enough and vibration-free.
• The environment must meet the environmental conditions specied in the technical
data.
4.1 Overview DPC200
1. Front cover
2. Cable gland
3. Pressure connection 1
4. Pressure connection 2
5. Cable gland
1.
2.
3.
4. 5.
4.2 Schematic view inside
Button 1 and 2 serve for the operation of the menu
4.3 Pressure connections
Connect all pressure connections properly with plastic hoses
(inner diameter 5 and 6 mm).
Button 1 Button 2

8
Doc.-no.: DPC200_01_EN Issue: 11/2015
OPERATION
4.4 Electrical connection
dry contact
open: Setpoint 1
close: Setpoint 2
+ 10...30 Vdc or 24 Vac (±15%) excitation
- GND (return)
1
2
3
4
5
6
7
8
+ 0...10 Vdc output
- GND (return)
∆P
Alarm output
high ohm: alarm off
low ohm: alarm on
maximum customer circuit 30 Vdc / 30 mA
DPC200
Alarm output: Open Collector
Potentialfreier Kontakt
offen: Sollwert 1
geschlossen: Sollwert 2
+ 10...30 Vdc oder 24 Vac (±15%) Versorgung
- GND
+ 0...10 Vdc Ausgang
- GND
Alarm Ausgang
hochohmig: Alarm aus
niederohmig: Alarm an
maximaler externer Stromkreis: 30 Vdc / 30 mA
1
2
3
4
5
6
7
8
∆P
DPC200
Alarm Ausgang: Open Collector
∆P
1 + Versorgung: 10...30 Vdc;
24 Vac +/-15%
2 - GND
3 + Ausgang 0...10 V
1. Unscrew screws of the front cover.
2. Open front cover.
3. Use M16 x 1,5 screws for connecting to terminals
4.5 Zero adjustment
Regardless of the menu the zero point can be readjusted with a small bar magnet without
opening the housing.
Adjustment:
The device is in measuring mode or con-
troll mode and not within the menu:
• Remove the hoses from the nozzles.
• Hold the bar magnet (N/S) to the zero
point adjustment for a short period of
time.
The new zero point will be stored.
5. Operation
5.1 Start menu
For operating the menu, unscrew the front cover to reach buttons T1 and T2.
N S

9
Doc.-no.: DPC200_01_EN Issue: 11/2015
OPERATION
5.2 Menüstruktur
ΔP control set 1
150 Pa
Press button T1
about 2 seconds
to start menu
menu
unit
metric
Press
button T2
operating mode
measuring mode
parameter
diff. pressure
unit
imperial
parameter
volume flow
fan k-factor
k = 70
Button T1: reset
Button T2: set
Button T1: confirm
Display flashes once
operating mode
control mode
parameter
diff. pressure
parameter
volume flow
fan k-factor
k = 70
Button T1: reset
Button T2: set
Button T1: confirm
Display flashes once
setpoint 1
50 Pa
setpoint 2
250 Pa
Button T1: reset
Button T2: set
Button T1: confirm
Display flashes once
Button T1: reset
Button T2: set
Button T1: confirm
Display flashes once
Button T1: reset
Button T2: set
Button T1: confirm
Display flashes once
Button T1: reset
Button T2: set
Button T1: confirm
Display flashes once
Button T1: reset
Button T2: set
Button T1: confirm
Display flashes once
output voltage
U= 10,0 V
P - parameter
50
I - parameter
3,15
controlling mode
positive/heating
controlling mode
negative/cooling
back and confirm
Press button T2
for menu
menu
ΔP control set 1
150 Pa
Press button T1
to leave menu
Press
button T2 Press
button T2
Press
button T2
Press
button T2
Press
button T2
Press
button T2
Press
button T2
Press
button T2
Press
button T2
Press
button T2
Press
button T2
Press
button T2
Press
button T2
Press
button T2
Press
button T2
Press
button T1
Press button T1
Press
button T1
Press
button T1
Press
button T1
Press button T2
Press
button T2
limit switch V
300 m³/h
Press
button T2
Button T1: reset
Button T2: set
Button T1: confirm
Display flashes once
Press
button T2
limit switch ΔP
300 Pa
Button T1: reset
Button T2: set
Button T1: confirm
Display flashes once

10
Doc.-no.: DPC200_01_EN Issue: 11/2015
OPERATION
5.3 Measuring mode
Display Action
ΔPMeasurement
200 Pa
Start menu: Press button T1 approx. two seconds
menu Press button T2 to get to the next menu item
unit metric
Press button T1 to switch between:
metric <=> imperial
Press button T2 to get to the next menu item
operating mode
control mode
Press button T1 to switch between:
measuring mode <=> control mode
Press button T2 to get to the next menu item
parameter
diff. pressure
Press button T1 to switch between:
diff. pressure <=> volume flow
Press button T2 to get to the next menu item
If selected parameter = diff. pressure
limit switch
150 Pa
Button T1: reset value
Button T2: set value
Button T1: conrm value, display ashes once
Press button T2 to get to the next menu item
backandconrm Press button T1 to leave the menu
Press button T2 to stay in the menu
Ifselectedparameter=volumeow
than follows the additional input for the k-factor
fan k-factor
k = 70
Button T1: reset value
Button T2: set value
Button T1: conrm value, display ashes once
Press button T2 to get to the next menu item
limit switch
300 m³/h
Button T1: reset value
Button T2: set value
Button T1: confirm value, display flashes once
Press button T2 to get to the next menu item
backandconrm Press button T1 to leave the menu
Press button T2 to stay in the menu

11
Doc.-no.: DPC200_01_EN Issue: 11/2015
OPERATION
5.4 Control mode
Display Action
ΔPMeasurement
200 Pa
Start menu: Press button T1 approx. two seconds
menu Press button T2 to get to the next menu item
unit metric
Press button T1 to switch between:
metric <=> imperial
Press button T2 to get to the next menu item
operating mode
control mode
Press button T1 to switch between:
measuring mode <=> control mode
Press button T2 to get to the next menu item
parameter
diff. pressure
Press button T1 to switch between:
diff. pressure <=> volume flow
Press button T2 to get to the next menu item
If selected parameter = diff. pressure
resp. after the input of the k-factor follows:
setpoint 1
50 Pa
Button T1: reset value
Button T2: set value
Button T1: conrm value, display ashes once
Press button T2 to get to the next menu item
setpoint 2
250 Pa
Button T1: reset value
Button T2: set value
Button T1: confirm value, display flashes once
Press button T2 to get to the next menu item
output voltage
U = 10,0V DC
Button T1: reset value
Button T2: set value
Button T1: confirm value, display flashes once
Press button T2 to get to the next menu item
P - parameter
50
Button T1: reset value
Button T2: set value
Button T1: confirm value, display flashes once
Press button T2 to get to the next menu item
l - parameter
3,15
Button T1: reset value
Button T2: set value
Button T1: confirm value, display flashes once
Press button T2 to get to the next menu item
controlling mode
positive / heating
Press button T1 to switch between:
positive / heating <=> negative / cooling
Press button T2 to go to the next menu
backandconrm Press button T1 to leave the menu
Press button T2 to stay in the menu

12
Doc.-no.: DPC200_01_EN Issue: 11/2015
OPERATION
5.5 Adjustable parameters
Parameter Selection or parameter range Default setting
Unit Metric or imperial metric
Operating
mode: Measuring mode or control mode measuring mode
Parameter Differential pressure ΔP [Pa or InH2O]
Volume flow V [m3/h or cfm]
differential
pressure ΔP [Pa]
K-factor: K = 70
Limit avalue:
Differential pressure from 0 % up to 100 % of measuring range.
Volume flow from 5 % up to 100 % of measuring range, k-factor is
considered.
OFF
Nominal
values
(setpoints):
Differential pressure from 0 % up to 100 % of measuring range.
Volume flow from 5 % up to 100 % of measuring range, k-factor is
considered.
Set 1: 75 %
Set 2: 25 %
Output
voltage: 0,0 … 10,0V DC Uout = 10,0V DC
P-fraction: 0 ... 1000 P = 50
I-fraction: 0,00 … 100,00 I = 3,15
Control
characteri-
stic:
positive / heating
Ifselectedparameter=volumeow
than follows the additional input for the k-factor
fan k-factor
k = 70
Button T1: reset value
Button T2: set value
Button T1: conrm value, display ashes once
Press button T2 to get to the next menu item
Volume flow calculation according to: V = k · √Δp
with:
Volume flow calculation up to 65.500 m3/h (38.514 cfm)
In measuring or control mode
Maximum volume flow (Vmax)
Measuring range: 50 Pa, k=1000
Measuring range: 500 Pa, k=1000
Measuring range: 1000 Pa, k=1000
Measuring range: 2000 Pa, k=1000
Measuring range: 4000 Pa, k=1000
V =Volume flow in m3/h or cfm
k = flow factor, adjustment range: 1...1000 measuring range
up to 4000 Pa
Δp = differential pressure in Pa or InH20
Vmax = 7.071 m3/h; (4.157 cfm)
Vmax = 22.360 m3/h; (13.147 cfm)
Vmax = 31.622 m3/h; (18.593 cfm)
Vmax = 44.721 m3/h; (26.295 cfm)
Vmax = 63.245 m3/h; (37.188 cfm)
positive/(heating):
negative/(cooling):
Control deviation = set value – actual value
The output increases when: set value > actual value.
Control deviation = actual value – set value
The output increases when: actual value > set value

13
Doc.-no.: DPC200_01_EN Issue: 11/2015
BETRIEB
5.6 Function alarm output
The DPC200 has an open collector alarm output; depending on the operating mode the
function is different.
At the alarm event a contact between terminal no. 7 and no. 8 gets low-resistive and
can be loaded with a maximum of 30 V DC/ 30 mA.When the alarm is switched off the
contact will be high-resistive.
During alarm state in the control mode / measuring mode an exclamation point is displayed
(2nd line / 16th character).
Control mode:
In order to recognize the limits of control, the alarm output in the control mode refers to
the set maximum output voltage (MaxUout). MaxUout can be set in the menu item „output
voltage“.
In the default setting the value is set to 10V DC.
Alarm ON: Output voltage for 12 seconds constantly greater than: 0.95 • MaxUout
Alarm OFF: Output voltage for 12 seconds constantly less than: 0.9 • MaxUout
Measuring mode:
For limit value monitoring a limit value can be entered.This value is set in the menu item
„limit switch“. The previously set parameters are taken into account (unit, parameter,
k-factor and the measuring range).
In the default setting the limits are not active. Display 2nd line: „OFF“
Alarm ON: Measurement for 12 seconds constantly greater than 1 • limit value
Alarm OFF: Measurement for 12 seconds constantly less than 0.95 • limit value

14
Doc.-no.: DPC200_01_EN Issue: 11/2015
6. Maintenance
The DPC200 contains no wearing or consumable parts. Servicing is not required.
On request, Arthur Grillo GmbH offers an annual calibration with factory certicate.
For information, please contact:
7. Warranty
Warranty and liability claims for personal and property damage are excluded if they are
caused by one or more of the following reasons:
• Improper use of the device.
• Improper installation, commissioning, operation and maintenance of the de-vice.
• Unauthorized modications to the device beyond the intended use.
• Disasters due to external inuences and force majeure.
8. Troubleshooting
9. Disposal
Dispose of parts so as not to endanger the health or environment. Follow the laws in the
country of use for disposing of electronic components and devices during disposal.
Description Activity
Display does not show
anything Check electrical connection
Measurement stays zero Function test with a slight pressure increase in measu-
ring mode for differential pressure
Measuring error Perform zeroing as described in chapter 4.5.
Error remains Contact manufacturer
Arthur Grillo GmbH Phone: 0 21 02 - 47 10 22
Am Sandbach 7 Fax: 0 21 02 - 47 58 82
WARRANTY & SUPPORT

15
Doc.-no.: DPC200_01_EN Issue: 11/2015
GEWÄHRLEISTUNG & SUPPORT
10. Specications
Specications
Measuring medium:
Measuring principle:
Lowest span:
Highest span:
Overpressure protection:
Static pressure:
Pressure connections:
Case:
Supply voltage:
Current consumption:
Output:
Display:
Mode:
Controlling algorithm:
Set points:
Protection class:
Ambient temperature:
Weight:
Mounting:
Interference emission:
Inuences limits:
Air or non-aggressive gases
Silicon diaphragm with spring and differential transformer
0...50 Pa
0...6000 Pa
0,2 bar
max. 0,2 bar
hose liners 5 mm ø and 6 mm ø
UL 94 HB; Case polyamid, cover ABS
10...30 Vdc or 24 Vac ± 15 %
Electronic protection against faulty polarization
ca. 10 mA @ 10 Vdc, ca. 12 mA @ 24 Vdc
0...10 V (Imax = 0,5 mA @ 10 Vdc, Imax = 2 mA @ 20 Vdc)
Open Collector, max. 30 V / 30 mA
LCD-Display, 2x16 characters
Measuring mode or controlling mode
PI
2 set points adjustable within software,
Set points are selectable with oating contact input
IP 54 according EN 60529
0...+50 °C
approx. 90 g
vertical, position dependence by turning of 90°: approx. 25 Pa
According EN 50081-2, EN 50082-2, CE mark
Zero error: ± 0,75 %
Sum of linearity and hysteresis
(depends on measuring range): ± 0,5 %
Temperature drift, zero point: ± 0,3 % / 10 K
Temperature drift, span: ± 0,2 % / 10 K

16
Doc.-no.: DPC200_01_EN Issue: 11/2015
CE-LABELLING
10.1 CE-labelling
As an electric device the DPC200 falls within the scope of the directive 2004/108/EG
(EMV-directive). In the scope of the EMV-directive the following norms were applied:
DIN EN 61000-6-2:2006-03
Berichtigung 1:2011-06
Electromagnetic compatibility (EMC) - Part 6-2: Generic
standards - Immunity for industrial environments
DIN EN 61000-6-3:2011-09
Electromagnetic compatibility (EMC) - Part 6-3: Generic
standards - Emission standard for residential, commer-
cial and light industrial environments
You can order the Declaration of Conformity at:
Arthur Grillo GmbH
Am Sandbach 7
40878 Ratingen
Telefon: 0 21 02 - 47 10 22
Telefax: 0 21 02 - 47 58 82
E-Mail: [email protected]
Other manuals for DPC200
2
Table of contents
Other Arthur Grillo Controllers manuals
Popular Controllers manuals by other brands

Technische Alternative
Technische Alternative UVR610S-OD-MODB installation instructions

Mitsubishi Electric
Mitsubishi Electric MELSEC iQ-F FX5 Hardware manual

PowerTech
PowerTech MP3755 user manual

Emerson
Emerson Fisher 67C Series installation guide

Siemens
Siemens instabus JB 527C23 Technical manual

Omron
Omron E5EN instruction manual

Balmar
Balmar Centerfielder Installation and operator's manual

CDI
CDI 197-0002 Installation and troubleshooting guide

Macron Dynamics
Macron Dynamics MSA series USER GUIDE, MAINTENANCE MANUAL

SKYDANCE
SKYDANCE XC user manual

Emerson
Emerson EC2-712 operating instructions

Deltronic Labs
Deltronic Labs Sounder quick start guide