OPERATION
5.5 Adjustable parameters
Parameter Selection or parameter range Default setting
Unit Metric or imperial metric
Operating
mode: Measuring mode or control mode measuring mode
Parameter Differential pressure ΔP [Pa or InH2O]
Volume flow V [m3/h or cfm]
differential
pressure ΔP [Pa]
K-factor: K = 70
Limit avalue:
Differential pressure from 0 % up to 100 % of measuring range.
Volume flow from 5 % up to 100 % of measuring range, k-factor is
considered.
OFF
Nominal
values
(setpoints):
Differential pressure from 0 % up to 100 % of measuring range.
Volume flow from 5 % up to 100 % of measuring range, k-factor is
considered.
Set 1: 75 %
Set 2: 25 %
Output
voltage: 0,0 … 10,0V DC Uout = 10,0V DC
P-fraction: 0 ... 1000 P = 50
I-fraction: 0,00 … 100,00 I = 3,15
Control
characteri-
stic:
positive / heating
Ifselectedparameter=volumeow
than follows the additional input for the k-factor
fan k-factor
k = 70
Button T1: reset value
Button T2: set value
Button T1: conrm value, display ashes once
Press button T2 to get to the next menu item
Volume flow calculation according to: V = k · √Δp
with:
Volume flow calculation up to 65.500 m3/h (38.514 cfm)
In measuring or control mode
Maximum volume flow (Vmax)
Measuring range: 50 Pa, k=1000
Measuring range: 500 Pa, k=1000
Measuring range: 1000 Pa, k=1000
Measuring range: 2000 Pa, k=1000
Measuring range: 4000 Pa, k=1000
V =Volume flow in m3/h or cfm
k = flow factor, adjustment range: 1...1000 measuring range
up to 4000 Pa
Δp = differential pressure in Pa or InH20
Vmax = 7.071 m3/h; (4.157 cfm)
Vmax = 22.360 m3/h; (13.147 cfm)
Vmax = 31.622 m3/h; (18.593 cfm)
Vmax = 44.721 m3/h; (26.295 cfm)
Vmax = 63.245 m3/h; (37.188 cfm)
positive/(heating):
negative/(cooling):
Control deviation = set value – actual value
The output increases when: set value > actual value.
Control deviation = actual value – set value
The output increases when: actual value > set value