ASCOM ELISE2 User manual

TD 92232GB
2005-06-15 / Ver.G
Installation Guide
ELISE2

TD 92232GB
2005-06-15 / Ver.G
Installation Guide
ELISE2
Contents
1 Introduction............................................................................................................. 1
2 Board Description.................................................................................................... 2
3 General Information ............................................................................................... 4
3.1 Licence .............................................................................................................. 4
3.2 Power Down and Restart of ELISE2 .................................................................... 4
3.3 Operating Modes ............................................................................................... 4
3.4 Selection of Operating Mode ............................................................................. 5
3.5 Function Indicator .............................................................................................. 6
3.6 Administration and Authentication .................................................................... 7
4 Installation............................................................................................................... 8
4.1 Opening the Housing ......................................................................................... 9
4.2 Wiring Runs ..................................................................................................... 10
4.3 Selection of A or B-bus .................................................................................... 11
4.4 ELISE2 controlling the Communication on the A/B-bus ..................................... 11
4.5 Mounting ........................................................................................................ 13
4.6 Mounting Together with Other Units ................................................................ 13
4.7 System 900 Addressing .................................................................................... 14
4.8 Connection of System Bus ............................................................................... 14
4.9 Connection of Supply Voltage .......................................................................... 16
4.10 Additional Connections .................................................................................. 17
4.11 Activation of Battery ..................................................................................... 19
4.12 Setup of Network Parameters ........................................................................ 20
4.13 Connection of Ethernet .................................................................................. 22
4.14 Installation Test Procedure .............................................................................. 22
4.15 Clock Synchronisation and Time Settings ....................................................... 23
4.16 Message Distribution ..................................................................................... 24
4.17 Unite Name Server (UNS) ............................................................................... 25
5 Maintenance Information..................................................................................... 25
5.1 Replacement of the Compact Flash .................................................................. 25
5.2 Updating Application Software ........................................................................ 25
5.3 Replacing an Image on the Compact Flash ....................................................... 26
5.4 Installing an Image on an empty Compact Flash ............................................... 26
5.5 Updating the Software Licence ........................................................................ 26
5.6 Circuit Board Replacement ............................................................................... 27
Appendix A: LON Piggy Back Circuit Board (LPB) .................................................. 28

TD 92232GB
2005-06-15 / Ver.G
Installation Guide
ELISE2
1
1 Introduction
The ELISE2 module can be used as a platform for a wide range of applications. The
module can be used as an interface between systems, for example a TCP/IP network and
the System 900 bus.
The licence is application dependent and therefore described in the application
documentation.
The parameter setup of ELISE2 is done with a web browser.
Figure 1. The ELISE2 module.
Supply voltage: 12 – 24 V/DC ±10%
Current consumption: max 0.4 A at 12 V
max 0.2 A at 24 V
Delivery includes: ELISE2
System Bus Cabling
Ethernet cable
Tools etc. required: Screwdriver
Cutting pliers
Screws for installation
Multimeter
Power supply
PC with Microsoft Internet Explorer 5.5 or later
Software "Route to ELISE". (Available from the
distributor)
001

TD 92232GB
2005-06-15 / Ver.G
Installation Guide
ELISE2
2
2 Board Description
Figure 2. The ELISE2 circuit board.
0
02
J2 IC2
J10
J16
J15
J4
J13J12J11J8
J7
J24
J14J6J5
J20
S3
LED6
RS232:3
ETH
900 900RS232:2 RS232:1
LED7
S4
S5
S1
S2
IC24
J22
J9
IC1
CPU
BAT1
SW4 LED LED1
J1
SW2
SW3
1
1
8
1
8
1
6
221
1414 1
2 3 4 5

TD 92232GB
2005-06-15 / Ver.G
Installation Guide
ELISE2
3
Connectors
Jumper points and push buttons
Switches
Module key and Backup battery
LEDs
J2 Connector for the Compact Flash
J5 Connection of supply voltage
J6 For connection of RS422 communication
J7 Modular jack (RJ45) for connection of RS232 communication. RS232:3
J8 Modular jack (RJ45) for connection of RS232 communication. RS232:2
J9, J10 LON/GP Interface Connector
J11 Modular jack (RJ45) for connection of RS232 communication. RS232:1
J12, J13 Modular jacks (RJ45) for connection of System 900 bus cabling
J14 Connector where an error relay output is available.
J16 Connects AUX Input and AUX Output
J20 For connection of 10baseT or 100baseT Ethernet TCP/IP network
J22 For internal use only
J24 For connection of A or B-bus from System 900 when modular system bus
cable is not used.
J1 Jumper that activates the backup battery. (Jumper pin 2-3 to activate).
J4 For grounding and production test
J15 Jumper that determines if the Error relay output should be active when
the relay operates or is released. Normally set to 1-2 to select operating.
S1, S2 Jumper points for selection of A or B-bus
S3 For internal use only
S4, S5 Jumper points used when ELISE2 controls the communication on the
A/B-bus.
SW4 Reset button for CPU
SW2 Module address selector switch for A or B-bus. If the setting of SW2 is
changed, the ELISE2 module detects this automatically and will reconnect
to the System 900 with the new address (it takes approximately 30 s).
SW3 Selector switch for operating mode
IC1 CPU
IC2 On-board flash
IC24 Module key
BAT1 Backup battery
LED1 Function indicator with green, orange and red indication
LED2-LED5 Application dependent functionality. See documentation on the
application for description.
LED6 Communication on the Ethernet
LED7 Ethernet speed indicator. ON 100 Mbit/s, OFF 10 Mbit/s

TD 92232GB
2005-06-15 / Ver.G
Installation Guide
ELISE2
4
3 General Information
3.1 Licence
All ELISE2 units must have a valid software licence.
The licence can be found on the administration web page, under the section System
Setup > Common > Licence.
IMPORTANT: Changing this field may seriously affect the functionality.
If no valid licence is present, the unit will not start and the Function Indicator (see figure 4)
will indicate licence error with a slow flashing red light. The unit can be started in
unlicensed mode, see Unlicensed Mode on page 5 and 3.4 Selection of Operating Mode
on page 5 for more information. Unlicensed mode is indicated by the Function Indicator
with an orange light (3000 ms ON/100 ms OFF), see also 3.5 Function Indicator on page 6.
3.2 Power Down and Restart of ELISE2
Power Down
1 Remove the cover from the ELISE2 module.
2 Press the push button SW4 to perform a shut down of the processor.
3 Wait until the Function Indicator is flashing orange.
4 Remove the power cable. The power must be removed within 10 minutes or ELISE2
will restart. If ELISE2 restarts, wait until the Function Indicator is not indicating
starting up (flashing orange) before pressing SW4 again.
Restart
There are two ways to restart an ELISE2; following the instruction above and then
replacing the power cable or initiate a restart from the administration web page.
3.3 Operating Modes
There are five different operating modes; normal, network setup, fail-safe, image
installation and unlicensed.
Network Setup Mode
To be able to contact the ELISE2, a valid and unique IP address is necessary. In this mode,
the IP address is set to 192.5.36.229, which is reserved for installation of ELISE2. Network
Setup Mode should only be used when ELISE2 has not got any IP address or when the IP
address has to be changed, i.e. if ELISE2 has been moved from one network to another.
Fail-safe Mode
This mode can be used when it is impossible to contact the ELISE2. When started in Fail-
safe Mode, no applications are started. It is possible to return to factory settings or a
backup copy of parameters from the web page xxx.xxx.xxx.xxx/admin (xxx.xxx.xxx.xxx is
the IP address given to the ELISE2). If there is a problem accessing this page, it is possible
to access xxx.xxx.xxx.xxx/system, where it is possible to change network parameters or
install new software.

TD 92232GB
2005-06-15 / Ver.G
Installation Guide
ELISE2
5
Image Installation Mode
The Compact Flash includes the ELISE2 operating system and application software. If all
information (operating system and application software) needs to be updated, then the
complete Compact Flash image must to be replaced. The ELISE2 is normally set in image
installation mode from the administration pages but it can also be set by the operating
mode switch. See 5.3 Replacing an Image on the Compact Flash on page 26 or 5.4
Installing an Image on an empty Compact Flash on page 26.
If the Compact Flash needs to be partly updated with new application software, the image
installation mode should not be used. For more information, see 5.2 Updating Application
Software on page 25.
Unlicensed Mode
It is possible to run the ELISE2, with limited functionality, without a licence. How the mode
functions is application dependent. For more exact information about the functionality
during unlicensed mode, see the application documentation.
In unlicensed mode, it is possible to enter a licence that does not match the current
hardware. This makes it possible to configure a Compact Flash on one hardware and move
the Compact Flash to another hardware without changing the licence.
3.4 Selection of Operating Mode
All 8 sections of SW3 are set to OFF for normal operating mode.
Figure 3. Switch for selection of operating mode.
Changing Operating Mode
1 Set the section that corresponds to the operating mode to ON.
2 Open the administration web page and press "Reboot" or follow the instructions in
3.2 Power Down and Restart of ELISE2 on page 4.
Section 1: Network setup mode
Section 2: Fail-safe mode
Section 3: Not used, must be set to OFF
Section 4: Image Installation mode
Section 5: Unlicensed mode
Section 6: Not used, must be set to OFF
Section 7: Not used, must be set to OFF
Section 8: Not used, must be set to OFF
1
OFF ON
8
SW3
003

TD 92232GB
2005-06-15 / Ver.G
Installation Guide
ELISE2
6
Starting the unit in Normal Mode
1 Set all sections on SW3 to OFF.
2 Open the page System Setup > General on the administration web page and check
that the correct licence is entered.
3 Press "Reboot".
3.5 Function Indicator
Figure 4. Status is indicated by the Function Indicator according to the list below.
Function indicator
004

TD 92232GB
2005-06-15 / Ver.G
Installation Guide
ELISE2
7
1Fail safe mode is indicated, even if SW3 pin 2 is not set to ON, if the application on
ELISE2 is not completely installed or when the application part of the Compact Flash is
erased.
2When ELISE2 is in Network setup mode, this will always be indicated and override LED
indications of other simultaneously activated modes, for example Image installation mode.
3Starting up mode is indicated during start of applications or if an application has lost
connection to a required resource, for example A-bus.
3.6 Administration and Authentication
Administration on ELISE2 is done from a web browser. In order to access the
administration pages a user name and password have to be given.
IMPORTANT: The default passwords have to be changed, else anyone with knowledge
of a password and the IP address can access the administration web pages
and make changes.
Status
Colour
Green
Orange
OK. Running
Fail-safe mode1
Network setup mode2
LED Indication
Red
Orange
Orange
Orange
Orange
Red
Red
Red
Red
Red
Starting up3
Orange Image installation mode
Power up
Restart
Halted (auto. restart after 10 min.)
Unlicensed mode
Low voltage
Licence error
Watch-dog reset
Shut-down
Memory error (3 s ON / 3 s OFF)
Network error (IP interface initiation error)
Module key error (Module key not found)
Each segment = 100 ms
005

TD 92232GB
2005-06-15 / Ver.G
Installation Guide
ELISE2
8
Authentication
There are two different users in all ELISE2 products; admin and sysadmin.
The user admin has the default password "changeme" and is used for administration and
simple troubleshooting of the product. The admin has permission to change all passwords
except the sysadmin password.
The user sysadmin has the default password "setmeup" and is used for advanced
troubleshooting. The user also has access to all administration pages. The sysadmin has
permission to change passwords for all users in the product.
In addition, there are two other users in some ELISE2 products. One is called user and the
default password is "password". This user is product dependent and what it is used for is
described in corresponding product documentation. This user does not have access to the
administration pages where passwords normally are changed. The user can change its
own password on the following page;
http://xxx.xxx.xxx.xxx/admin/public/user_chpass.shtml. The password can also be changed
by the users admin and sysadmin.
The other user is called ftpuser and the default password is "changemetoo". The user is
available in products with a FTP area. The user can change its own password on the
following page; http://xxx.xxx.xxx.xxx/admin/public/ftpuser_chpass.shtml.
Administration
To access the web pages below, the user admin is used.
The web page "xxx.xxx.xxx.xxx/admin" is used in most occasions, for example:
• System setup, i.e. System 900 configuration
• Troubleshooting information
• Changing passwords
On the following occasions, the web page "xxx.xxx.xxx.xxx/system" must be used.
• Current software installation has to be replaced.
• No software is installed on ELISE2.
• Compact Flash image update or installation
The system page can also be used when configuring network parameters.
4 Installation
ELISE2 should be placed in a dry environment with a temperature range of 0 to +40°C.
The ELISE2 module can be connected via system bus cabling, or via twisted-pairs together
with other units in the System 900. The ELISE2 modules can communicate with each other
via the TCP/IP network.
IMPORTANT: The ELISE2 module must be mounted in a vertical position to ensure
sufficient cooling for the electrical components.
IMPORTANT: Always follow the instructions in 3.2 Power Down and Restart of ELISE2 on
page 4 when disconnecting the power to the ELISE2 module.

TD 92232GB
2005-06-15 / Ver.G
Installation Guide
ELISE2
9
Note: Only install one ELISE2 module at a time, otherwise problems might occur during IP
addressing.
Installation Procedure
1 Read chapters 4.1 and 4.2 before starting the installation.
2 At delivery ELISE2 is configured for system communication on the A-bus. If modular
system bus cabling is used and the B-bus shall be used for system communication,
follow the instructions in 4.3 Selection of A or B-bus on page 11.
3 At delivery, the ELISE2 is configured to be connected to a Central Unit on the A/B-
bus. If the ELISE2 should control the communication on the A/B-bus, follow
instructions in 4.4 ELISE2 controlling the Communication on the A/B-bus on page
11.
4 Mount ELISE2 on the wall, follow instructions in 4.5 Mounting on page 13 and
4.6 Mounting Together with Other Units on page 13.
5 Set the system bus address, follow instructions in 4.7 System 900 Addressing on
page 14.
6 Connect the system bus, follow instructions in 4.8 Connection of System Bus on
page 14 and 4.9 Connection of Supply Voltage on page 16.
7 Optionally connect outputs and inputs described in 4.10 Additional Connections on
page 17.
8 Activate the battery, follow instructions in 4.11 Activation of Battery on page 19.
9 Perform a network parameter setup of ELISE2, follow instructions in 4.12 Setup of
Network Parameters on page 20.
10 Connect Ethernet connector to the Local Area Network, follow instructions in 4.13
Connection of Ethernet on page 22.
11 Perform a test of the installation, follow the instructions in 4.14 Installation Test
Procedure on page 22.
12 Continue with additional parameter setup for the unit according to chapter
4.15- 4.17 and respective software application documentation.
13 Make a backup copy of all parameters.
4.1 Opening the Housing
Use a screwdriver or similar to release the cover by applying a light pressure to the two
snap catches (1) and remove the cover (2).
Figure 5. Opening the ELISE2 housing.
1
1
2
006

TD 92232GB
2005-06-15 / Ver.G
Installation Guide
ELISE2
10
4.2 Wiring Runs
The plastic partition is scored to facilitate breaking at convenient intervals.
1 Use pliers to break off a suitable section.
2 Run the wiring out through the partition. Wiring can be run three ways from the
ELISE2 module:
• Remove the rectangular covers and run the cabling out through the side (1).
• Break off sections at short side of case and run the cabling downwards (2).
• Run the cabling through the round holes at the bottom of the case (3).
3 Secure the wiring with cable straps.
009
2
1
2
3
1
3
010

TD 92232GB
2005-06-15 / Ver.G
Installation Guide
ELISE2
11
4.3 Selection of A or B-bus
When modular bus cabling is used for connection of the System 900 bus the A-bus is used
default. To use the B-bus, remove the 0 ohm resistors R111 and R112 from the circuit
board and solder jumper points S1 and S2 (R111 and R112 are situated on the bottom
side of the circuit board). See figure 6 on page 11.
Figure 6. Jumper points for adjusting the ELISE2 unit to use the System 900 B-bus
instead of the A-bus.
4.4 ELISE2 controlling the Communication on the A/B-bus
Depending on the software application on the ELISE2, it can be used to control the
communication on the A-bus, i.e. the Central Unit is not used for communication control.
This can be useful when System 900 is not used for messaging but only to communicate
with, for example, an Alarm Module or Output Module.
The same information that can be received when the ELISE2 is connected to an A-bus with
Central Unit, can also be received when it is controlling the communication. Examples of
information is input activity and pagings from the Alarm Modules (see respective software
application documentation for more information about the possibilities). Alarms and
Mobile data from handsets can be transferred from the ELISE2 to modules connected to
the A-bus. The ELISE2 does not have any other of the Central Unit functionality, for
example the possibility to address Pocket Units over the A-bus or handle absence
information received from Charging Racks.
011
J7
J20
LED6
RS232:3
ETH
LED7
J2
J10
J16
J15
J4
J13J12J11J8
J24
J14J6J5
S3
900 900RS232:2 RS232:1
S4
S5
S1
S2
IC24
J22
J9
IC1
BAT1
SW4 LED1
J1
SW2
SW3
1
LED2
LED3
LED4
LED5
1
8
1
8
16
221
1414 1
R112
C115
C116
R111
Bottom side
Top side
R112
C115
C116
R111
S1
S2
S1
S2

TD 92232GB
2005-06-15 / Ver.G
Installation Guide
ELISE2
12
System Installation
When the ELISE2 controls the communication on the A-bus, a maximum of 15 modules
can be connected to the A-bus. The ELISE2 should have the address 00 and other modules
that are connected to the A-bus must have addresses in the range 01-0F.
See also 4.16 Message Distribution on page 24 and documentation for the System 900.
Required Hardware Modifications
When ELISE2 shall control the communication on the A/B-bus, jumper points S4 and S5
has to be soldered, see figure 7 below.
Figure 7. Jumper points for configuring the ELISE2 unit to be a communication
controller on A/B-bus.
012
J7
J20
LED6
RS232:3
ETH
LED7
J2
J10
J16
J15
J4
J13J12J11J8
J24
J14J6J5
S3
900 900RS232:2 RS232:1
S4
S5
S1
S2
IC24
J22
J9
IC1
BAT1
SW4 LED1
J1
SW2
SW3
1
LED2
LED3
LED4
LED5
1
8
1
8
16
221
1414 1
S4
S5
S4
S5

TD 92232GB
2005-06-15 / Ver.G
Installation Guide
ELISE2
13
4.5 Mounting
Dimensions for installation of the ELISE2 module.
Note: To facilitate service after the unit is installed, we recommend a free space of about
150 mm above and 50 mm below the unit.
4.6 Mounting Together with Other Units
1 Remove the rectangular (1) and circular (2) covers.
2 The rectangular covers are used to fasten units to each other (3 and 4).
3 Fasten the unit with three screws, see the illustration in 4.5 Mounting on page 13.
Dimensions (H x W x D)
275 x 130 x 60 mm
56,5 112
99
188,5 275
65 130
013
1
2
014
4
3
015

TD 92232GB
2005-06-15 / Ver.G
Installation Guide
ELISE2
14
4.7 System 900 Addressing
The System 900 address consists of two hexadecimal digits that are selected by the eight
sections of the address switch, SW2. Sections 5-8 of the switch select the first (most
significant) digit and section 1-4 select the second (least significant) digit. The address
must not be the same as any other System 900 unit address (see document System
Installation, On-site Paging System, TD 90227GB for more information).
Figure 8. The ELISE2 module addressing switch.
4.8 Connection of System Bus
The ELISE2 module can be installed together with other System 900 units, either via
modular system bus cabling or via twisted-pair lines.
016
SW2
18
J2
J10
J16
J15
J4
J13J12J11J8
J7
J24
J14J6J5
J20
S3
LED6
RS232:3
ETH
900 900RS232:2 RS232:1
LED7
S4
S5
S1
S2
IC24
J22
J9
IC1
BAT1
SW4 LED1
J1
SW2
SW3
1
LED2
LED3
LED4
LED5
1
8
1
8
16
221
1414 1

TD 92232GB
2005-06-15 / Ver.G
Installation Guide
ELISE2
15
Bus Connection to Modular Jacks
1 The illustration above shows an ELISE2 module placed to the left of another System
900 unit. Connect the bus cable as shown, from connector J12/J13 on the ELISE2
module to the bus connector on the other unit.
Note: Make sure connectors are correctly inserted!
Bus Connection to Screw Terminals
If system bus cable is not used, connections are made with twisted pairs to screw
connector J24.
Figure 9. Connection of System 900 bus.
Other System 900 units are connected to A or B-bus, pin 1 and 2 at screw connector J24.
Note: Observe polarity. Use only twisted pairs for two-wire connections.
ELISE
Other unit
J12 J13
017
J24
2 BUS 2
1 BUS 1
To A or B-bus in other units
within the System 900
018

TD 92232GB
2005-06-15 / Ver.G
Installation Guide
ELISE2
16
4.9 Connection of Supply Voltage
A separate power supply is connected to screw connector J5, pin1 and 2. A ferrite bead is
thread on the wire to prevent EMC disturbances. The current through J5 must not exceed
3A. See also the document System Installation, On-site Paging System, TD 90227GB under
"Power Supply".
Figure 10. Connection of supply voltage.
Figure 11. Ferrite bead attached and wired in the module.
1 To be able to fit the ferrite bead, break a section off the plastic partition, see also
4.2 Wiring Runs on page 10.
2 Attach the ferrite bead with a cable strap.
3 Run the power supply cable two turns through the ferrite bead.
4 Connect the power supply cable to J5:1-2.
J5
1 +12V
2 GND
Supply voltage out 3 +12V
4 GND
Supply voltage in
019
034
1

TD 92232GB
2005-06-15 / Ver.G
Installation Guide
ELISE2
17
4.10 Additional Connections
Error Relay Output
A relay output on connector J14 is used to indicate ELISE2 module malfunction and can
also be used to indicate other errors. See application documentation for more information
about functionality.
Figure 12. Jumpering that decides when the error relay output is active, either
when the relay operates or is released.
The jumpering J15 decides if the output shall be active when the relay is operating or
released. 1-2 selects operating and 2-3 selects released. In figure 12, the relay is released
and as the jumpering is set to 1-2 the circuit is open and the error relay output is inactive.
At power-up or restart of the ELISE2, the relay is released until the applications are
working properly. If the relay is released longer, ELISE2 is malfunctioning.
RS232 Communication with External Unit
The ELISE2 has three identical RS232 connectors; J7, J8 and J11. Depending on software
application the RS232 ports can be used or not. How to connect external equipment to
the ELISE2 is described in the documentation of the software application.
In figure 13, the RS232 connectors on the ELISE2 is described.
Figure 13. Description of the ELISE2 RS232 ports.
2
1
J14
ELISE
RE1 321
J15
Error relay output
020
1 (not used)
2 TX
3 RX
4 CTRL IN
5 CTRL OUT
6 (not used)
J11/J7/J8
7 GND
8 (not used)
ELISE
021
To external unit
using RS232
communication

TD 92232GB
2005-06-15 / Ver.G
Installation Guide
ELISE2
18
Connections for Serial Line Printer
To connect the serial line printer, see figure 14 for the pin-layout and wiring run.
Figure 14. Connections for serial line printing.
RS422 Communication with External Unit
Depending on software application the RS422 port is used or not. If it is used, the
connector J6 is connected to the external unit as shown in the figure below.
Figure 15. Connection of external unit via the RS422 port.
Connection of AUX Inputs and AUX Outputs
The application of the inputs and outputs are software dependent.
Two digital inputs and two digital outputs can be connected via J16. The outputs are of
open-collector type and the output signals are dimensioned for 100 mA at max 12 V.
A pull-up resistor should be connected to the output as shown in figure 16.
Galvanic isolation of the inputs and outputs is provided by using a separate power supply.
When galvanic isolation is not needed, supply voltage can be taken from the ELISE2 circuit
board by connecting J16-1 to J5-3 and J16-6 to J5-4.
1 (not used)
2 TX
3 RX
4 CTRL IN
5 CTRL OUT
6 (not used)
J11/J7/J8
7 GND
8 (not used)
ELISE
035
25-pin male
D-sub connector
DTR
DSR
DCD
TXD
RXD
GND
RTS
CTS
20
6
8
2
3
7
4
5
1 T(b)
2 T(a)
3 R(b)
4 R(a)
Rb
Ra
Tb
Ta
J6
To external unit
using RS422
communication
023
Table of contents
Other ASCOM Server manuals