5Installation
5.1 Installation condition requirements
To ensure normal operation of the machine, the installation environment is required
as follows:
> The ingress protection of ATS is IP20. Moreover, as this product is an electronic equipment, it
shall not be placed in humid environment;
> Install indoors and avoid sunlight and rain;
> Ventilation of the room shall be good;
> The installation environment shall be clean;
> As some noise will be produced in operation, this equipment shall be installed far
from residential quarters;
> The installation ground shall be even enough, and firm enough to support the
weight of ATS;
> The installation position shall be convenient for maintenance;
> Ambient temperature range: –25°C~55°C;
> Appropriate space shall be reserved for the machine to ensure ventilation and
cooling.
We suggest ATS is installed in the distribution room. The floor, wall clearance,
Ventilation equipment and precaution should be designed by professional personnel
and satisfy the following requirements.
Foundation requirement
ATS is required to install on even ground with fire-retardant material as the
surface or channel steel support structure, and sag or tilt ground is prohibited. The foundation
shall be solid, safe and reliable. The foundation shall be capable of bearing the load of ATS. Its
load bearing ability shall be concerned throughout the installation place selection.
Clearance space
During installation of ATS, appropriate space shall be left to the wall or other equipment, in order
to satisfy the requirements on narrowest maintenance channel, emergency access and
ventilation.
In front of the installation place of ATS, a space of 1.1m or more shall be ensured, the back 1.1m
or more, the top 0.5m or more to ensure easy installation, cooling and maintenance.
Cable trench
The cable connection of ATS adopts bottom inlet and bottom outlet. Cable trenches are
recommended to ensure easy installation and maintenance.
The cable trenches are often designed and constructed by the construction side based on relevant
standards, with the equipment weight and dimensions required to be considered. Good electrical
connection is needed between different cable trenches and GND terminals.
Wiring specification
Cables in ATS can be classified into either power cables or data cables. In cabling, the power cable shall be
kept far away from, and the cable shall be kept in right angle at cross. The cable shall be as short as
possible, and an appropriate distance shall be kept to the power cable.
The power cable and data access shall be placed in different cable trenches respectively to avoid lengthy
routing between the power cable and other cables, so as to reduce the electromagnetic interruption
caused by sudden change of the output voltage. The distance among the power cable and data access
shall be more than 0.2m. When the cables are crossed, the cross angle shall be 90 degrees, while the
distance can be reduced appropriately.
Ventilation requirement
In operation, ATS will produce a lot of heat. When ambient temperature is too high, the electrical property
of the equipment may be affected, the equipment may even be damaged. Therefore, the heat release
shall be fully considered in designing the control room to ensure operation of the equipment in high
efficiency. In front of the installation place of ATS, a space of 1.5m or more shall be ensured, the back
0.6m or more, the top 0.6m or more to ensure easy installation, cooling and maintenance.
Ventilation environment
To satisfy the ventilation requirement of ATS, its installation environment shall meet the following
conditions:
※ ATS shall be prevented from being installed in the place of poor ventilation
condition and insufficient air flow;
※ The air inlet shall have enough air supplementation.
Ventilation equipment
To ensure safe and reliable operation of the equipment, the ambient temperature must be within the
permission range –25°C~ 55°C, therefore, appropriate ventilation devices must be equipped with to
release the heat generated by the equipment. We suggest the ventilation rate is more than 3665m³/h.