Austin Hughes InfraSolution X Series User manual

www.austin-hughes.comUM-X-800-XMS-02-S-Q420V1
User Manual
Smartcard Access Control for Racks
Designed and manufactured by Austin Hughes
X-2000
X-1000
XMS-02-S, InfraBox GUI & SNMP
X-800
Smartcard Handle

www.austin-hughes.comUM-X-800-XMS-02-S-Q420V1
Legal Information
First English printing, November 2020
Information in this document has been carefully checked for accuracy; however, no guarantee is given to the correctness
of the contents. The information in this document is subject to change without notice. We are not liable for any injury or
loss that results from the use of this equipment.
Safety Instructions
Please read all of these instructions carefully before you use the device. Save this manual for
future reference.
■Unplug equipment before cleaning. Don’t use liquid or spray detergent; use a moist cloth.
■Keep equipment away from excessive humidity and heat. Preferably, keep it in an air-conditioned environment with
temperatures not exceeding 40º Celsius (104º Fahrenheit).
■When installing, place the equipment on a sturdy, level surface to prevent it from accidentally falling and causing
damage to other equipment or injury to persons nearby.
■When the equipment is in an open position, do not cover, block or in any way obstruct the gap between it and the
power supply. Proper air convection is necessary to keep it from overheating.
■Arrange the equipment’s power cord in such a way that others won’t trip or fall over it.
■If you are using a power cord that didn’t ship with the equipment, ensure that it is rated for the voltage and current
labeled on the equipment’s electrical ratings label. The voltage rating on the cord should be higher than the one listed
on the equipment’s ratings label.
■Observe all precautions and warnings attached to the equipment.
■If you don’t intend on using the equipment for a long time, disconnect it from the power outlet to prevent being
damaged by transient over-voltage.
■Keep all liquids away from the equipment to minimize the risk of accidental spillage. Liquid spilled on to the power
supply or on other hardware may cause damage, fire or electrical shock.
■Only qualified service personnel should open the chassis. Opening it yourself could damage the equipment and
invalidate its warranty.
■If any part of the equipment becomes damaged or stops functioning, have it checked by qualified service personnel.
What the warranty does not cover
■Any product, on which the serial number has been defaced, modified or removed.
■Damage, deterioration or malfunction resulting from:
□Accident, misuse, neglect, fire, water, lightning, or other acts of nature, unauthorized product modification, or
failure to follow instructions supplied with the product.
□Repair or attempted repair by anyone not authorized by us.
□Any damage of the product due to shipment.
□Removal or installation of the product.
□Causes external to the product, such as electric power fluctuation or failure.
□Use of supplies or parts not meeting our specifications.
□Normal wear and tear.
□Any other causes which does not relate to a product defect.
■Removal, installation, and set-up service charges.
Regulatory Notices Federal Communications Commission (FCC)
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of
the FCC rules. These limits are designed to provide reasonable protection against harmful interference in a residential
installation.
Any changes or modifications made to this equipment may void the user’s authority to operate this equipment. This
equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause
harmful interference to radio or television reception, which can be determined by turning the equipment offand on, the
user is encouraged to try to correct the interference by one or more of the following measures:
■Re-position or relocate the receiving antenna.
■Increase the separation between the equipment and receiver.
■Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Notice : The changes or modifications not expressly approved by the party responsible for compliance could void the
user’s authority to operate the equipment.
IMPORTANT NOTE: To comply with the FCC RF exposure compliance requirements, no change to the antenna or the
device is permitted. Any change to the antenna or the device could result in the device exceeding the RF exposure
requirements and void user’s authority to operate the device.

www.austin-hughes.comUM-X-800-XMS-02-S-Q420V1
■It is very important to locate the equipment in a suitable environment.
■The surface for placing and fixing the equipment should be stable and level or mounted into a suitable
cabinet.
■Make sure the place has good ventilation, is out of direct sunlight, away from sources of excessive dust, dirt, heat,
water, moisture and vibration.
■Position the equipment with respect to related facilities.
Before Installation
InfraBox Installation ■Suggest the installation at the rear top mounting of cabinet
■M6 screws set not provided.

www.austin-hughes.comUM-X-800-XMS-02-S-Q420V1
Contents
< Part. 1 > Hardware
1.1 Tips for Hardware P.1
1.2 Package Contents P.2
1.3 InfraBox X-1000 / X-2000 P.3
1.4 Handle X-800P / X-800M P.8
1.5 Door Sensor Installation ( Inductive / IR / Mechanical ) P.19
< Part. 2 > PDU
2.1 PDU P.26
< Part. 3 > Environmental Sensor & Peripherals
3.1 Temp. & Humid Sensor P.27
3.2 Smoke Sensor P.28
3.3 Shock Sensor P.29
3.4 Water Sensor P.30
3.5 LED Light Bar P.31
3.6 LED Beacon P.32
< Part. 4 > XMS-02-S InfraBox GUI Software
4.1 Device Monitoring & Setting P.33
4.2 System Setting P.43
4.3 SNMP P.44

www.austin-hughes.comUM-X-800-XMS-02-S-Q420V1
Intentionally
Left
Blank

www.austin-hughes.comUM-X-800-XMS-02-S-Q420V1 P.1
< Part 1 > Hardware
< 1.1 > Tips for hardware
To install IP setup utilities Start
Complete
Place the rackmount box on the
top rear side of the cabinet
Place the sensor to the door
corner & connect to the handle
Connect sensor & peripheral
to InfraBox
Daisy Chain / Star / Mixed
connection
For each InfraBox ONE by ONE
For front & rear door
& connect cable to InfraBox
PDU daisy chain setting
Connect InfraBox by daisy chain
via Cat5/6 cable
InfraBox Cascade
Prepare a notebook computer
InfraBox installation
Door sensor installation
Configure IP setting
Smartcard handle installation
PDU installation
Sensor & peripheral installation
Network setup

www.austin-hughes.comUM-X-800-XMS-02-S-Q420V1 P.2
< 1.2 > Package Contents
The equipment comes with the standard parts shown on the package contents. Check and make sure they are included and in good
condition. If anything is missing, or damage, contact the supplier immediately.
Unpacking
Card# 12345678 Each package bundled with smartcard x 1. The card
on the bottom right shows card number information :
Card# 12
Patented and Worldwide
Patents Pending
- X-2000 OR X-1000 InfraBox, 1 pc
- 800 MiFARE OR Proximity smart card handle, pair
- Inductive OR Mechanical door sensor, pair
- Front door cable, 2-section with joint connector, 1 pc ( 3150mm )
- Rear door cable, 2-section with joint connector, 1 pc ( 2350mm )
- 6’ Power cord, 1 pc
- Activated smartcard, 1 pc
- Key, 1 pc
- Cable clip, 8 pcs
X-2000
X-800P X-800M
OR
OR
X-1000
Handle mounting screw set :
- Handle mounting bracket, 2 pcs
- M4 x 9mm screw, 4 pcs
- Square hole washer, 6 pcs
- Circle hole washer, 2 pcs
- M5 x 10mm screw, 2 pcs
- U bracket x 2
- M3 x 10mm screw, 4 pcs
- Extention spigot, 2 pcs

www.austin-hughes.comUM-X-800-XMS-02-S-Q420V1 P.3
< 1.3 > InfraBox X-1000 / X-2000
Power input
Dual power input ( option )
Door cable DB-9 connector x 2
Connect to the front and rear handle
“Act in Out” LED
Daisy chain RJ45 port x 2
( Link & Out )
Temp. LED display x 2
Smoke / Shock sensor port x 2
LED Light Bar port x 2
Port for 3rd party alarm board x 1
LED beacon port x 1
Temp. & Humid. sensor port x 2
PDU port x 1 ( RJ-45, up to PDU daisy chain level x 4 )
Fan unit port x 1 ( RJ-45, up to fan unit daisy chain level x 2 )
Water sensor port x 2
7
1 2 3
6 9
114
8 10
13125 14
X-2000
X-1000 / X-2000 Specification
X-1000
1
2
3
5
4
7
6
8
12
10
14
13
11
9
Product Dimension ( W x D x H ) 400 x 135 x 39.7 mm / 15.7 x 5.3 x 1.6 inch
Packing Dimension ( W x D x H ) 557 x 367 x 98 mm / 21.9 x 14.4 x 3.9 inch
Net / Gross Weight 1.06 kgs ( 2.3 lbs ) / 2.2 kgs ( 4.8 lbs )
Power Consumption Auto-sensing 100~240VAC, 50 / 60Hz 0.5A, Max. 48 Watt
Operating Temperature 0° to 55°C Degree
Storage Temperature -5° to 60 °C Degree
Relative Humidity 5~90%, non-condensing
Mounting 1U Rackmount
Safety Regulatory FCC & CE certified
Environmental RoHS2 & REACH compliant by SGS

www.austin-hughes.comUM-X-800-XMS-02-S-Q420V1 P.4
< 1.3 > InfraBox X-1000 / X-2000
Key hardware Installation Diagram - InfraBox / Handle / Door Sensor
InfraBox Daisy Chain Connection
1
3
5
2
4
InfraBox
SmartCard handle
Door sensor with 6’ cable
Door cable ( door section )
Door cable ( cabinet section )
Front Door
Rear Door
22
2
2
3
4
3
4
5
5
1
Up to 50 Infrabox in a single daisy chain
Up to 100 meters in a single daisy chain
InfraBox X-2000
InfraBox X-1000
InfraBox X-2000

www.austin-hughes.comUM-X-800-XMS-02-S-Q420V1 P.5
Installation Diagram - PDU / Fan / Sensor / Peripheral
Item Qty. Location
LED Light Bar 2front & rear top inside
Smoke Sensor 1rear inside top
Flashing LED Beacon 1front cabinet roof
Temp. & Humid. Sensor 2any inside position
Shock Sensor 1upper inside
Fan Unit 2door mount or rackmount
PDU 4vertical or rackmount
Water Sensor 1surrounding cabinet on floor
1
3
6
2
4
8
7
5
2
4
7
1
6
5
8
3
Front Door
Rear Door
< 1.3 > InfraBox X-1000 / X-2000

www.austin-hughes.comUM-X-800-XMS-02-S-Q420V1 P.6
< 1.3 > InfraBox X-1000 / X-2000
Before place the InfraBox to the cabinet, user MUST configure the IP setting for the InfraBox. It takes
around 1-2 minutes to complete :
1. Prepare a notebook computer to download the IP setup utilities from the link below :
http://www.austin-hughes.com/support/utilities/infrasolutionX/InfraBoxSetup.msi
2. Double click the InfraBoxSetup.msi and follow the instruction to complete the utilities installation.
3. Power ON the InfraBox.
4. Go to each InfraBox with the notebook computer & a piece of CAT. 5 / 6 cable to configure the InfraBox
as below.
To
notebook computer
LAN port
To
InfraBox LAN port
CAT. 5 / 6 cable
IP Setup for InfraBox

www.austin-hughes.comUM-X-800-XMS-02-S-Q420V1 P.7
Please take the procedure no. 3 to 6 for all InfraBoxes ONE BY ONE.
5. Click “ Scan “ to search the connected InfraBox.
6. Change the IP address / Subnet mask / Gateway, then Click “ Save “ to confim the setting of InfraBox.
The default IP address is as below :
IP address: 192.168.0.1
Subnet mask: 255.255.255.0
Gateway: 192.168.0.254
< 1.3 > InfraBox X-1000 / X-2000
IP Setup for InfraBox

www.austin-hughes.comUM-X-800-XMS-02-S-Q420V1 P.8
To achieve the highest level of interoperability offered in the cabinet industry, the X-800 handle applies the universal
mounting cut-out. It avoids costly and complicated door customization for the smartcard handle integration.
Universal Mounting Cut-out
Models of left / right side opening
X-800P / X-800M support left side open. If user requires right side open,
please order X-800P-R / X-800M-R.
Model Left side open Right side open
X-800P Proximity
X-800M MiFARE
X-800P - R Proximity
X-800M - R MiFARE
Back ViewCut-out Side View
Close
Side View
Open
Unit : mm
< 1.4 > Handle X-800P / X-800M

www.austin-hughes.comUM-X-800-XMS-02-S-Q420V1 P.9
< 1.4 > Handle X-800P / X-800M
Installation for Single Point Lock
1. Mount the smartcard handle to the universal mounting position.
2. Place the handle mounting bracket with M4 x 9mm screw x 2 to secure the handle.
3. Attach the Cam with square hole washer(s) to adjust and to fit the cam locking position.
The extension spigot required or not for installation is subject to the rack door locking design.
Note : - If the cam cannot fit the locking position after adjustment, customization for the cam is required.
- Cam customization service upon your request, please contact your sales representative.
4. Insert the M5 x 15mm screw x 1 with circle hole washer to secure the Cam to the handle.
5. Place the U bracket with M3 x 10mm screw x 2 to further secure the handle in place.
1
3
7
2
56
4
Handle mounting screw set for single point lock
Qty. Single Point Lock
Handle mounting bracket 2
M4 x 9mm screw for 4
Square hole washer 6
Circle hole washer w/ M5 x 15mm screw 2
U bracket 2
M3 x 10mm screw for 4
Extensions spigot 2
2
3
4
5
6
7
1
1
1
2
7
3
5
6
4
Rack door
Cam
>>>>>
>>>>>
5
While insert the screws to secure
the handle with electrical power
screwdriver, please set the torque
NOT exceed 8 kgf/cm

www.austin-hughes.comUM-X-800-XMS-02-S-Q420V1 P.10
1. Make sure
2. Make sure the rack door is rigid and no bending.
3. Don’t over tighten the fixing screws.
Cam lock can slide into the hole without stress.
The cut-out of the cam hole with enough space tolerance.
1
2
Pay attention to the following points when install the lock system.
Otherwise, it may cause handle distortion and malfunction.
Door
cam
lock
Cam lock hole Cam lock hole
enough
tolerance
Rigid
door
limited
tolerance
Bending
door
Door
cam
lock

www.austin-hughes.comUM-X-800-XMS-02-S-Q420V1 P.11
< 1.4 > Handle X-800P / X-800M
Installation for ( light-duty rod-latch )
2 - point Lock
1
2
3
4
Handle mounting screw set for 2-point lock ( light-duty )
1. Mount the smartcard handle to the universal mounting position.
2. Place the handle mounting bracket with M4 x 9mm screw x 2 to secure the handle.
3. Attach the Rod-latch with square hole washer(s) to adjust and to fit the door top & bottom locking position.
4. Insert the M5 x 15mm screw x 1 with circle hole washer to secure the Rod-latch to the handle.
5. Place the U bracket with M3 x 10mm screw x 2 to further secure the handle in place.
1
3
2
4
Rack door
>>>>>
Rod latch
>>>>>
5
6
56
While insert the screws to secure
the handle with electrical power
screwdriver, please set the torque
NOT exceed 8 kgf/cm
Qty. 2-Point Lock
light-duty
Handle mounting bracket 2
M4 x 9mm screw for 4
Square hole washer 6
Circle hole washer w/ M5 x 15mm screw 2
U bracket 2
M3 x 10mm screw for 4
Extensions spigot 2 X
2
3
4
5
6
7
1
1
5

www.austin-hughes.comUM-X-800-XMS-02-S-Q420V1 P.12
1. Make sure
2. Make sure the rack door is rigid and no bending.
3. Don’t over tighten the fixing screws.
Two ends of latch rod can entry into the top & bottom holes without stress.
The top & bottom holes with enough space tolerance.
1
2
Pay attention to the following points when install the lock system.
Otherwise, it may cause handle distortion and malfunction.
Lock hole Lock hole
Rod Rod
2-point lock holes
( top & bottom )
2-point lock holes
( top & bottom )
enough
tolerance
Rigid
door
limited
tolerance
Bending
door

www.austin-hughes.comUM-X-800-XMS-02-S-Q420V1 P.13
< 1.4 > Handle X-800P / X-800M
Installation for ( rod control system )
2 - point Lock
Handle mounting screw set for 2-Point Lock ( with rod control )
Rod control
system
Rack door
>>>>>
>>>>>
Orignal
handle screws
>>> >>>
1. Mount the smartcard handle to the universal mounting position.
2. Attach the Rod control system to the handle and insert the M5 x 15mm screw x 1 with circle hole
washer to secure the position.
3. Insert Orignal handle screws x 2 through the Rod control system and door to the handle to fix it in place.
4. Place the U bracket with M3 x 10mm screw x 2 to further secure the handle in place.
4
4
5
6
Qty. 2-Point Lock
( with rod control )
Handle mounting bracket 2 X
M4 x 9mm screw for 4 X
Square hole washer 6 X
Circle hole washer w/ M5 x 15mm screw 2
U bracket 2
M3 x 10mm screw for 4
Extensions spigot 2 X
2
3
4
1
1
5
6
7
5
56
While insert the screws to secure
the handle with electrical power
screwdriver, please set the torque
NOT exceed 8 kgf/cm

www.austin-hughes.comUM-X-800-XMS-02-S-Q420V1 P.14
1. Make sure
2. Make sure the rack door is rigid and no bending.
3. Don’t over tighten the fixing screws.
Two ends of latch rod can entry into the top & bottom holes without stress.
The top & bottom holes with enough space tolerance.
1
2
Pay attention to the following points when install the lock system.
Otherwise, it may cause handle distortion and malfunction.
Lock hole Lock hole
Rod Rod
2-point lock holes
( top & bottom )
2-point lock holes
( top & bottom )
enough
tolerance
Rigid
door
limited
tolerance
Bending
door

www.austin-hughes.comUM-X-800-XMS-02-S-Q420V1 P.15
Sensor
area
Present the smartcard and
touch the handle sensor
area for 1 to 2 seconds
Smartcard mode
For smartcard operation,
keep key cylinder always
to 12 o’clock direction.
Key cylinder to 3 o’clock direction
Under key unlock mode, the handle
keeps unlocked.
Key cylinder to 9 o’clock direction
Under key lock mode, even present the
smartcard, the handle still keeps locked.
Key unlock mode
Key lock mode
Under Smartcard mode, always keep key cylinder to 12 o’clock direction.
Important Note for Key lock
Key cylinder to 3 o’clock direction.
Key cylinder to 9 o’clock direction.
Key unlock mode
Key lock mode
Unless the smartcard handle is defective, lock / unlock the handle by key is NOT recommended
Please insert & turn the key with push force
< 1.4 > Handle X-800P / X-800M
This manual suits for next models
5