Axiom MF Series Owner's manual

2615 Wentz Avenue, Saskatoon, SK S7K 5J1 Ph: (306) 651-1815 Fax: (306) 651-2293
I
NDUSTRIES LIMITED
Installation, Operation & Maintenance
Instructions for MF Series Solution Feeders
En Français Page 12
Startup Procedure
1) Close isolation valve between feeder and system
connection point
2) Fill reservoir, turn valve on feeder to mix/purge and
plug in
3) Ensure pump is cycling fluid through reservoir (primed)
4) Turn valve to run and open isolation valve to system

MF200 and MF300 HYDRONIC SYSTEM FEEDER
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
The System Feeder is used to maintain a minimum system pressure within a hydronic heating
or cooling system. It should be used to pressurize the system while system temperature is at
it’s lowest.
Installation Instructions
1. Set System Feeder on a secure and level base or in the optional tank shelf.
2. Connect the unit to the system using copper or plastic tubing. Ensure that there is a system
isolation valve installed to allow for isolation of the unit. DO NOT INSTALL A CHECK
VALVE OR PRESSURE REGULATOR BETWEEN SYSTEM FEEDER AND SYSTEM.
3. Mount power supply and secure with mounting bracket. Do not power up System Feeder
until a system connection is made, isolation valve is closed and Feeder valve is set to mix.
4. If the System Feeder will be connected to an alarm system connect alarm circuit to terminals
below discharge connection.
5. Install proper water/glycol mix in the tank to a level above minimum level indication on tank
scale. A 30-50% Polypropylene Glycol is Recommended.
6. Close system isolation valve, turn feeder valve to vertical position (mix position).
7. Insert DC plug into the System Feeder first, and then plug power supply into 120v outlet.
The red LED in the power supply cord should light up. If it does not, check the fuse and
power receptacle.
8. Once the pump is primed, turn the feeder valve handle to horizontal position (run position),
open system isolation valve and allow pump to pressurize system. If system pressure is
below pressure switch setting (18 psi), the pump will start. The System Feeder will run until
system is pressurized to approximately 18 psi. and shut-off. It may cycle rapidly a number of
times while system pressure stabilizes and while air is removed from the system. The
cycling will stop once system pressure rises above 18 psi due to thermal expansion.
9. If a higher fill pressure is required (up to 25 psi) the internal pressure switch may be
adjusted by turning the center adjusting screw clockwise to increase pressure. Access to the
pressure switch can be gained by lifting the left side of the top cover.
10. The MF200 is shipped with a small amount of 50% propylene glycol (non-toxic) in the
discharge tubing between the pump and the check valve. This is to aid in priming.
Please note that the pressure gauge supplied with the unit may read differently from another
gauge, which may be installed elsewhere in the system. This may be due to gauge calibration or
differences in elevation within the system and should not be a concern.
The System Feeder does not require any scheduled maintenance. Should you wish to test
pump operation, turn mix/purge valve to vertical position to start pump. Turning mix/purge valve
handle to horizontal position will stop pump.
I
NDUSTRIES LIMITED

COLD STATIC FILL PRESSURE
The cold static fill pressure (CSFP) in a closed hydronic system has to be high enough to
accomplish three things.
1) Overcome the static head (height) between the fill point and the highest point in the system.
2) Provide adequate pressure (minimum 4 psig) at the top of the system for proper air venting.
3) Maintain adequate pressure at the inlet of the system pumps to prevent cavitation.
The formula for calculating the required CSFP to satisfy points 1 & 2 is:
(Static height in feet/2.31) + 4 = CSFP in psig.
As an example, the CSFP for a system with a static height above the fill point of 40 feet would
be: (40/2.31) + 4 = 21.3 psig.
For most closed hydronic systems operating below about 210 F, maintaining the minimum top-
of-system pressure at 4 psig will be adequate to prevent pump cavitation even if the pumps are at
or near the top of the system as well.
IMPORTANT NOTE – For air-charged diaphragm or bladder tanks, the air charge in the tank
must be adjusted to equal the cold static fill pressure before it is connected to the system.

Purger
Expansion
Tank MF 200
Pump
Connection Schematic – MF 200 Packaged System Feeder

Connecting the Alarm Contacts in the MF Series to Other Alarm Systems
The alarm switch contacts in the MF series are factory wired to be OPEN on LOW
PRESSURE. The switch is SPDT, so if some other alarm system is connected to this
alarm contact and can not be configured to work with an open contact, the wiring on the
low-pressure micro-switch can be changed to provide a closed contact on low pressure.
Remove the screws fastening the top cover to the unit and lift the cover to get access to
the pressure switch. Disconnect the power before doing this.
Pump Leads
Contact Leads
Switch
Housing
Wiring MF200 Pressure Switch For
Closed Contact on Low Pressure
The upper micro-switch controls the pump. The lower micro-switch is used for a low-pressure
warning. Move the wire from the middle terminal on the lower micro-switch to the rear-most
terminal as shown in the diagram above to get an open circuit on low pressure. You should now
have a closed alarm circuit at low pressure.

side decal
½” OD plastic tubing
pressure gauge
brass reducer
adjustable pressure switch
¼” hose adapter
diverter mounting bracket
foot valve strainer
power adapter plug-in
AXIOM INDUSTRIES
13 OCTOBER 2005
PROJECT
CUSTOMER
DRWG. NO. EQUIP. NO. JOB NO. DATE
LEGEND
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
cable clamp
s/n decal
120V to 24DCV power adapter
tank bung
in-tank float
½” OD clear hose
3/8" plastic hose
pressure snubber
power adapter bracket
½” plastc clamp
fluid diverter block
pump & motor assembly
tank
tank lid
alarm hook up terminal block
ITEM # DESCRIPTION
PART #
MF200-0970
MF200-0101
MF200-0500
MF200-0800
MF200-0960
MF200-0700
MF200-0950
MF200-0930
MF200-0400
MF200-0900
MF200-1420
MF200-0200
MF200-1200
MF200-1520
MF200-0910
MF200-0110
MF200-0310
MF200-1000
MF200-0110
MF200-1100
MF200-0940
MF200-1410
MF200-1300
MF200-1600
MF200-1400
3
2
MF-200 (EXPLODE)
TLL-MF200-1005 PARTS LIST
11 22
6
5
10
12
7
17
26
13
14
26
19
16
21
18
20
4
9
8
15
23
5/8" plastic clamp
MF200-0970
26
24
25
MF200-0980
27 ¼” check valve
27
¼” angle ball valve
1

side decal
½” OD plastic tubing
pressure gauge
brass reducer
adjustable pressure switch
¼” hose adapter
diverter mounting bracket
foot valve strainer
power adapter plug-in
AXIOM INDUSTRIES
13 OCTOBER 2005
PROJECT
CUSTOMER
DRWG. NO. EQUIP. NO. JOB NO. DATE
LEGEND
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
cable clamp
s/n decal
120V to 24DCV power adapter
tank bung
in-tank float
½” OD clear hose
3/8" plastic hose
pressure snubber
power adapter bracket
½” plastc clamp
fluid diverter block
pump & motor assembly
tank
tank lid
alarm hook up terminal block
ITEM # DESCRIPTION
PART #
MF200-0970
MF200-0101
MF200-0500
MF200-0810
MF200-0960
MF200-0700
MF200-0950
MF200-0930
MF200-0400
MF200-0900
MF200-1420
MF200-0200
MF200-1200
MF200-1520
MF200-0910
MF200-0110
MF200-0310
MF200-1001
MF200-0110
MF200-1100
MF200-0940
MF200-1410
MF200-1300
MF200-1600
MF200-1400
3
2
MF-300 (EXPLODE)
TLL-MF300-1005 PARTS LIST
11 22
6
5
10
12
7
17
26
13
14
26
19
16
21
18
1
20
4
9
8
15
23
5/8" plastic clamp
MF200-0970
26
24
25
MF200-0980
27 ¼” check valve
27
¼” angle ball valve

Installation Instructions for the RIA10-1-SAA Control Panel for use
with MF200 & MF300 Feeders
The MF series alarm dry contacts are factory wired to provide an OPEN contact on LOW
PRESSURE. This is compatible with the alarm circuit in the RIA10-1-SAA panel. Connect
terminals 1 and 2 from terminal block TB2 in the panel to the contact terminals located beside
the power plug on the MF unit.
1
5
4
3
2
TB2 in RIA10-1-SAA
Terminals on MF unit
NC
NO
COM
To disable the audible alarm in the RIA10-1-SAA panel, remove the jumper from the control
board of the RIA10-1-SAA.


Troubleshooting Chart
Symptom Possible Cause Resolution
Pump will not start Fluid level in tank is low Add correct fluid. Check for cause
of system fluid loss
Blown fuse Check LED indicator light on power
cord, check fuse and replace if
needed (2.5 Amps)
Power supply or Breaker Check LED indicator light on power
cord, flip breaker or obtain power
supply from reseller and replace
Power supply unplugged or loose
electrical connections Plug in power supply or correct
faulty electrical connection
Pressure switch out of adjustment Adjust pressure switch according
to the manufacturers
recommendations
Faulty pressure switch First obtain snubber from reseller
and replace. If problem continues
obtain pressure switch from
reseller then replace
Pump failure Obtain pump from reseller and
replace
Pump will not shut off Air lock in pump Turn purge/mixing valve to prime
pump
Leak in system or pump Inspect system and repair leak
Faulty pressure switch Obtain pressure switch and
snubber from reseller then replace
Pump will not prime Check valve stuck Tap check valve lightly
Fluid level in tank is low Add correct fluid. Check for cause
of system fluid loss
Strainer on inlet hose is blocked Clean strainer
Product in tank is too thick or
Congealed glycol Clean strainer and check
concentration of glycol mixture
Inlet tubing leak is drawing air Replace tubing and repair leak
Inlet/Outlet tube severely restricted
(Kinked) Replace tubing

Noisy / Rough operation Pump is overloaded and pump
pressure switch not cutting out Obtain Replacement pump from
reseller and install
Loose pump head or drive screws Tighten screws
Feeder is plumbed with rigid pipe
causing noise to transmit Plumb with PEX or plastic pipe
Feeder Leaking Manifold block over tightened and
cracked Obtain replacement manifold block
from reseller and install
Loose fittings Tighten fittings
Pump has punctured diaphragm Obtain Replacement pump from
reseller and install
System pressure low Fluid level in tank is low Add correct fluid. Check for cause
of system fluid loss
Blown fuse Check LED indicator light on power
cord, check fuse and replace if
needed
Power supply or Breaker Check LED indicator light on power
cord, flip breaker or obtain power
supply from reseller and replace
Pressure switch out of adjustment Adjust pressure switch according
to the manufacturers
recommendations
Snubber on pressure switch is
plugged Obtain snubber from reseller and
replace
Faulty pressure switch Obtain pressure switch and
snubber from reseller then replace
Power supply unplugged or loose
electrical connections Plug in power supply or correct
faulty electrical connection
Pump failure Obtain pump from reseller and
install
System pressure to high Pressure switch not adjusted to
proper setpoint Adjust pressure switch, refer to
maintenance manual for
instructions
Snubber on pressure switch is
plugged Obtain snubber from reseller and
replace. Ensure fluid in tank is
clean.
Faulty pressure switch Obtain pressure switch and
snubber from reseller then replace

Pump Cycles Continually Air is being removed from system
and pump is only making up fluid No action required
Leak in system Inspect system and repair leak
Check valve or Regulator installed
between System Feeder and
system
Remove check valve or regulator

2615, avenue Wentz, Saskatoon, SK S7K 5J1 Téléphone: (306) 651-1815 Télécopieur: (306) 651-2293
I
NDUSTRIES LTÉE
Alimentateurs de solution MF
Instructions d’installation, de fonctionnement et d’entretien
Procédure de mise en marche
1.Fermer le robinet d’isolement entre l’alimentateur et le
raccordement au système.
2.Remplir le réservoir, tourner la manette du robinet à
Mélange (Mix) sur l’alimentateur et brancher.
3.S’assurer que la pompe refoule la solution à partir du
réservoir (qu’elle est amorcée).
4.Tourner la manette du robinet à Marche (Run) et ouvrir le
robinet d’isolement du système.
I
NDUSTRIES LTÉE

Alimentateurs de solution MF
Instructions d’installation, de fonctionnement et d’entretien
Le MF200 est utilisé pour maintenir une pression minimum du système dans un système de
chauffage ou de refroidissement hydronique. Il devrait être utilisé pour pressuriser le système
quand la température du système est au plus bas.
Installation
1. Placer l’ensemble MF200 sur une surface plate et de niveau.
2. Raccorder l’appareil au système au moyen d'un tuyau de cuivre ou de plastique. S'assurer
qu’il y a un robinet d’isolement du système pour pouvoir isoler l’appareil. NE PAS
INSTALLER DE CLAPET ANTIRETOUR OU DE RÉGULATEUR DE PRESSION ENTRE
L'ALIMENTATEUR ET LE SYSTÈME.
3. Installer l’alimentation en électricité et fixer avec un support de fixation. Ne pas mettre le MF
200 sous tension avant de connecter le système et que le clapet d’isolement soit ouvert.
4. Si le MF200 est connecté à un système d’alarme, connecter le circuit d’alarme aux terminaux
sous la connexion de décharge.
5. Installer le bon mélange eau/glycol dans le réservoir sous l’indicateur de niveau minimum sur
l’échelle du réservoir. On recommande 30 à 50% de glycol polypropylène.
6. Fermer le robinet d’isolement du système, tourner la manette du robinet de
l’alimentateur en position verticale – Mélange (Mix).
7. Brancher d’abord la fiche CC dans l’alimentateur, puis le transformateur dans la prise à 120 V.
Le témoin DEL rouge sur le cordon d’alimentation devrait s’allumer, sinon vérifier le fusible et
la prise de courant.
8. Une fois la pompe amorcée, tourner la manette du robinet de l’alimentateur en position
horizontale (Marche), ouvrir le robinet d’isolement et laisser la pompe pressuriser le système.
Si la pression du système est en dessous du réglage du pressostat (18 lb/po2), la pompe
démarrera. L’alimentateur fonctionnera jusqu’à ce que le système soit pressurisé à 18 lb/po2
environ et fermera. Il pourra cycler rapidement quelque fois pendant que la pression du
système se stabilise et que l’air est retiré du système. Le cyclage s’arrêtera une fois que la
pression du système dépassera 18 lb/po2en raison de la dilatation thermique.
9. Si une pression de remplissage plus élevée est nécessaire (jusqu’à 25 lb/po2), on peut régler
le pressostat interne en tournant la vis de réglage centrale dans le sens horaire pour
augmenter la pression. On accède au pressostat en soulevant le côté gauche du couvercle.
10. L’alimentateur MF est expédié avec une petite quantité de propylène glycol (non toxique) à 50
% dans le tube de décharge entre la pompe et le clapet antiretour afin de faciliter l’amorçage
Veuillez noter que la jauge de pression fournie avec l’appareil peut se lire différemment d’une
autre jauge, qui peut être installée ailleurs dans le système. Cela peut être dû à l’étalonnage de la
jauge ou à une différence d’élévation dans le système et ne devrait pas vous inquiéter.
L’alimentateur ne nécessite pas d’entretien périodique. On peut toutefois vérifier le
fonctionnement de la pompe en tournant la manette de Mélange (Mix) en position verticale pour
la faire démarrer. La pompe arrêtera en retournant la manette en position horizontale.

PRESSION DE REMPLISSAGE STATIQUE À FROID
La pression de remplissage statique à froid dans un système hydronique en circuit fermé doit être
suffisamment élevée pour accomplir trois choses.
1) surmonter la charge statique (la hauteur) entre le point de remplissage et le point le plus élevé
dans le système.
2) fournir une pression suffisante (minimum 4 psi) en haut du système pour une bonne ventilation
de l’air.
3) Maintenir une pression suffisante à l’entrée des pompes du système pour empêcher la
cavitation.
La formule de calcul de la pression de remplissage statique à froid requise pour satisfaire aux
points 1 et 2 est la suivante:
(hauteur statique en pieds/2,31) + 4 = Pression de remplissage statique à froid en psi.
Par exemple, la pression de remplissage statique à froid pour un système ayant une hauteur
statique au-dessus du point de remplissage de 40 pieds sera : (40/2,31) + 4 = 21,3 psi
Pour la plupart des systèmes hydroniques en circuit fermé fonctionnant au-dessous de 210 F
environ, maintenir la pression minimum en haut du système à 4 psi suffira pour empêcher la
cavitation de la pompe même si les pompes sont en haut du système ou près du haut aussi.
REMARQUE IMPORTANTE – Pour les réservoirs à membrane remplie d’air ou les réservoirs
souples, la charge d’air dans le réservoir doit être réglée pour être égale à la pression de
remplissage statique à froid avant qu’il soit connecté au système.

MF 200
Séparateur d’air
et purgeur
Réservoir
d’expansion
Pump
Schéma de raccordement – Ensemble d'alimentation MF

Mode d’installation du panneau de contrôle RIA10-1-SAA à
utiliser avec les alimentateurs MF200 & MF300
Les contacts secs de l’alarme de la série MF sont réglés à l’usine pour fournir un
contact OUVERT à BASSE PRESSION. C’est compatible avec le circuit d’alarme dans
le panneau RIA10-1-SAA. Connecter les bornes 1 et 2 du bloc de bornes TB2 dans le
panneau aux bornes de contact situées près de la prise de courant de l’unité MF.
Enlever les vis qui retiennent le couvercle de l’appareil et soulever le couvercle pour accéder à
l’interrupteur de pression. Couper le courant avant de faire cela.
1
5
4
3
2
TB2 dans RIA10-1-SAA
Bornes sur l’unité MF
Pour désactiver l’alarme audible dans le panneau RIA10-1-SAA, enlever le fil de
connexion du panneau de contrôle de RIA10-1-SAA.


side decal
½” OD plastic tubing
pressure gauge
brass reducer
adjustable pressure switch
¼” hose adapter
diverter mounting bracket
foot valve strainer
power adapter plug-in
AXIOM INDUSTRIES
13 OCTOBER 2005
PROJECT
CUSTOMER
DRWG. NO. EQUIP. NO. JOB NO. DATE
LEGEND
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
cable clamp
s/n decal
120V to 24DCV power adapter
tank bung
in-tank float
½” OD clear hose
3/8" plastic hose
pressure snubber
power adapter bracket
½” plastc clamp
fluid diverter block
pump & motor assembly
tank
tank lid
alarm hook up terminal block
ITEM # DESCRIPTION
PART #
MF200-0970
MF200-0101
MF200-0500
MF200-0800
MF200-0960
MF200-0700
MF200-0950
MF200-0930
MF200-0400
MF200-0900
MF200-1420
MF200-0200
MF200-1200
MF200-1520
MF200-0910
MF200-0110
MF200-0310
MF200-1000
MF200-0110
MF200-1100
MF200-0940
MF200-1410
MF200-1300
MF200-1600
MF200-1400
3
2
MF-200 (EXPLODE)
TLL-MF200-1005 PARTS LIST
11 22
6
5
10
12
7
17
26
13
14
26
19
16
21
18
20
4
9
8
15
23
5/8" plastic clamp
MF200-0970
26
24
25
MF200-0980
27 ¼” check valve
27
¼” angle ball valve
1

side decal
½” OD plastic tubing
pressure gauge
brass reducer
adjustable pressure switch
¼” hose adapter
diverter mounting bracket
foot valve strainer
power adapter plug-in
AXIOM INDUSTRIES
13 OCTOBER 2005
PROJECT
CUSTOMER
DRWG. NO. EQUIP. NO. JOB NO. DATE
LEGEND
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
cable clamp
s/n decal
120V to 24DCV power adapter
tank bung
in-tank float
½” OD clear hose
3/8" plastic hose
pressure snubber
power adapter bracket
½” plastc clamp
fluid diverter block
pump & motor assembly
tank
tank lid
alarm hook up terminal block
ITEM # DESCRIPTION
PART #
MF200-0970
MF200-0101
MF200-0500
MF200-0810
MF200-0960
MF200-0700
MF200-0950
MF200-0930
MF200-0400
MF200-0900
MF200-1420
MF200-0200
MF200-1200
MF200-1520
MF200-0910
MF200-0110
MF200-0310
MF200-1001
MF200-0110
MF200-1100
MF200-0940
MF200-1410
MF200-1300
MF200-1600
MF200-1400
3
2
MF-300 (EXPLODE)
TLL-MF300-1005 PARTS LIST
11 22
6
5
10
12
7
17
26
13
14
26
19
16
21
18
1
20
4
9
8
15
23
5/8" plastic clamp
MF200-0970
26
24
25
MF200-0980
27 ¼” check valve
27
¼” angle ball valve
This manual suits for next models
2
Table of contents
Languages: