Service Manual CD180 Service Manual CD180
DENOMINATION TERMINAL N° DESCRIPTION
MAX REC. 1Output: internal ralay contact relative ti the
max dynamic braking cycle alarm. It can
carry out a max voltage Vac = 110/115V, or
Vdc = 48V with a max current of 800mA.
With supplied converter
Contact in ON = OK
Contact in OFF = intervent protection
R.m.v. 2Output: internal relay contact relative to
the min. adjustable speed detector same
loading as for MAX REC.
Contact in ON = speed > min. speed
Contact in OFF = speed < min. speed
OK 3Output: internal relay contact relative to
the intervention of any alarm but MAX REC,
it is memorized. It is restored by taking away
and returning the voltage. Same loading as
for MAX REC and R.m.v.
Contact in on ON = protection OK
Contact in OFF = protection intervened
COMUNE 4Output: common of the contacts relative
to the terminal 1, 2 and 3.
RIF. ON 5Input: predisposition to signal of reference
electrically separated by opto insulator. To
be obtain bring this terminal to "0P".
PWM. ON 6Input: predisposition to modulation,
electrically separated by opto insulator. To
be obtained, bring the terminal to "0P".
Connectors
821
2.1 Signal connector 5.3 Calibrations (cont.)
Starting procedures
7) ACC/DEC RAMP CALIBRATION
If request, the ACC/DEC ramp circuit is available. Incline variations are possible adjusting
the T8 trimmer available on personal card. Clockwise rotation produces a decrease of
the ramp time (from 1" to a min. value of 0.1").
The max. ramp time of 1" can be extended by introducing a C1 capacitor on the perso-
nal card. Under request it is also available a switching on/off finction ramp stage provided
with a logical signal on the outside terminal n.7 of the signal connector.
These optional finction, if wanted, have to be request at the moment of the order.
8) BALANCING CALIBRATION
To make up for eventual external off-sets on the reference signal (which causes a light
rotation of the motor), operate on the T6-BAL trimmer to stop the rotation of the motor.
The operation has to be carried out with reference signal = 0V.
9) LIMIT CALIBRATION OF EXTERNAL TORQUES
It is possible to limit the current and as consequence the available torque at the driving
shaft, bringing the terminal n.9 of the signal connector from +10V to 0V, as reported in
the connection diagram. With +10V, 100% of the current torque is obtained, with 0V, the
result is 0%.
If this function is not request, it has to be excluded by bringing to 10V fixed the terminal
n.9, or closing the interiour welding point n.S7.
If interested, this function must be requested at the moment of the order.
10) EMERGENCY BRAKING
If requested it is possible to obtain the fast dynamic braking against blackout
conditions function which unables the interruption of the motor in case of blackout.To
obtain this function it is necessary to stop the PWM.ON predisposition relative to the
terminal n.6 of the signal connector, when the motor supply stops. In this way, the
motor is controlled in fast braking until the min. speed threshold set.
11) ALARM RESTORATION
To restore the alarm that has been used it is necessary to take away and return voltage
to the converter. Before returning voltage it is necessary to wait 10", if not the used
alarm keep on signalling even if the cause for its action is not present any longer.