Bard CRVMP-5 User manual

Manual 2100-457D
Page 1 of 16
COMMERCIAL ROOM VENTILATORS
WITH EXHAUST
MODEL
CRVMP-5
For Use with Bard 3 through 5 Ton
WA*S Series Wall Mount Air Conditioners
INSTALLATION INSTRUCTIONS
Manual : 2100-457D
Supersedes: 2100-457C
File: Volume III Tab 19
Date: 01-24-14
Bard Manufacturing Company, Inc.
Bryan, Ohio 43506
Since 1914...Moving ahead just as planned.

Manual 2100-457D
Page 2 of 16
CONTENTS
General
General Information..................................................3
Unpacking.................................................................3
Description................................................................3
Models .................................................................3
Installation
Basic Installation....................................................4-8
Blade Adjustment for Desired Ventilator Air............10
Adding Optional CO2Control Sensor......................13
Commercial Room Ventilator Sequence.........15 & 16
Figures
Figure 1 Removal of Exterior Panels......................4
Figure 2
Remove Air Filter & Exhaust Cover Plate
.....5
Figure 3 Install Ventilator........................................6
Figure 4 Step Control Installation...........................8
Figure 5 Damper Control Board.............................9
Figure 6 CO2Sensor Set-Up (8403-056) .............14
Figure 7 Call for Blower Operation.......................15
Figure 8 Call for Cooling Operation......................16
Tables
Table 1 .................................................................4
Graphs
WA3S Ventilation Airow......................................... 11
WA4S Ventilation Airow......................................... 11
WA5S Ventilation Airow.........................................12
BARD MANUFACTURING COMPANY, INC.
BRYAN, OHIO USA 43506

Manual 2100-457D
Page 3 of 16
GENERAL
GENERAL INFORMATION
The ventilator should only be installed by a trained
heating and air conditioning technician. These
instructions serve as a guide to the technician installing
the ventilator package. They are not intended as a step
by step procedure with which the mechanically inclined
owner can install the package.
The ventilator housing is shipped in one carton which
contains the electrical harness, step control assembly,
miscellaneous hardware and installation instructions.
UNPACKING
Upon receipt of the equipment be sure to compare the
model number found on the shipping label with the
accessory identication information on the ordering and
shipping document to verify that the correct accessory
has been shipped.
Inspect the carton housing of each ventilator as it is
received, and before signing the freight bill, verify that
all items have been received and that there is no visible
damage. Note any shortages or damage on all copies
of the freight bill. The receiving party must contact
the last carrier immediately, preferably in writing,
requesting inspection by the carrier’s agent. Concealed
damage not discovered until after loading must be
reported to the carrier within 15 days of its receipt.
DESCRIPTION
The CRVMP-5 ventilator is designed to be used with
Bard 3 through 5 ton wall mount series step capacity
air conditioners. It is an electromechanical vent system
designed to provide fresh air to meet indoor air quality
standards. It automatically adjusts to the mode of
operation to maintain consistent fresh air intake levels.
Examples are blower only, stage 1 cooling and stage 2
cooling, which are all set for different total airows.
MODELS
When installed in the above-listed models, the
CRVMP-5 provides built in exhaust provisions.
When
the damper blade opens to bring fresh air in, the damper
also opens an exhaust relief. The exhaust air will ow
into the condenser section of the unit. The condenser
fan will help draw exhaust air out.

Manual 2100-457D
Page 4 of 16
2. Remove and save the existing exterior blower
access and service access panels on the Bard wall
mount unit. (See Figure 1.)
INSTALLATION
BASIC INSTALLATION
1. Unpack the ventilator assembly which includes the
integral ventilator with attached electrical harness,
step control assembly and miscellaneous hardware.
WARNING
Open and lock unit disconnect switch before
installing this accessory to prevent injury or
death due to electrical shock or contact with
moving parts. Turn thermostat to off.
TABLE 1
Model FOR USE WITH
FOLLOWING UNITS
CRVMP-5 WA3S
WA4S
WA5S
FIGURE 1
REMOVAL OF EXTERIOR PANELS

Manual 2100-457D
Page 5 of 16
FIGURE 2
REMOVE AIR FILTER AND EXHAUST COVER PLATE
3. Remove and save existing unit air lter and screws
from front center grille. (See Figure 2.) 4. Remove and discard the exhaust cover plate.

Manual 2100-457D
Page 6 of 16
6. Open control panel to gain access to unit low
voltage terminal block.
7. Route electrical harness leads through the 7/8"
bushing in control panel (Figure 3) into low voltage
box.
5. Install ventilator sheet metal assembly by inserting
the ventilator into the unit to the far left side
clearing the right lter bracket. Once the ventilator
is fully inserted, slide the ventilator to the right
until it is tight against the back of the control panel.
(See Figure 3.)
IMPORTANT: Position front lip of ventilator on top of
front grille and condenser partition. (See Figure 3
inset.) This is important to ensure proper drainage
of any water entering damper assembly.
FIGURE 3
INSTALL VENTILATOR
FIGURE 3 INSET
SIDE SECTION

Manual 2100-457D
Page 7 of 16
8. Connect “orange lead” with the fork terminal to
either the “G” terminal of the low voltage strip
(will ventilate anytime there is a call for the
blower), or the “F” terminal (can be used as a
junction point for on-demand ventilation with a
capable thermostat or occupancy sensor).
9. The pink, purple and black wires will pass through
bushing on opposite side of low voltage box where
they entered, and will run up the wire loom to the
step-control assembly for connection installed in
Step #10, Figure 4 following the wiring diagram
(enclosed in Literature Assembly or on ventilator).
10. Locate the step control assembly packaged with the
assembly. This assembly will install in the upper
left-hand corner of the control panel by aligning
the plastic standoffs with pre-punched holes in the
control panel. See Figure 4.
11. Route the wires from the step control assembly
down the control panel through the wire looms,
and route them into the low voltage box through
the bushing. See Figure 4. Make connections
following the wiring diagram (enclosed in
Literature Assembly or on ventilator).
12. Replace left lter support, lter and four (4) screws
in condenser grille.
13. Reinstall the blower access panel at top of unit and
secure with sheet metal screws.
14. Ventilator checkout – (Note: It may be more
efcient to disconnect the thermostat from the
low voltage terminal strip and use a set of jumper
wires to perform these steps.)
A. Resupply power to the unit.
B.
Energize the evaporator blower by switching
thermostat to the manual fan position with
heat/cool in OFF position. (Jumper “R” to “G”)
C. Ventilator should open to the position set by
“R1”potentiometeronstepcontrolboard. (See
Figure 5.)
D. Now energize Stage #1 cooling/heating by
switching the thermostat to the corresponding
modeandsettingthetemperatureoffsetslightly
beyond the actual room temperature. (Jumper
“R” to “G” and “Y1”)
E. Ventilator should now open to the position set
by “R2” potentiometer on step control board.
(See Figure 5.)

Manual 2100-457D
Page 8 of 16
F. Now energize the Stage #2 cooling/heating by
increasing the thermostat setting to a greater
offset than the actual room temperature.
(Jumper “R” to “G”, “Y1” and “Y2”)
G. Ventilator should now open to the position set
by “R3” potentiometer on step control board.
(See Figure 5.)
H. Now turn the heat/cool selector to OFF, and set
the fan switch back to AUTO. The damper
blade should close. (Remove all jumper
connections.)
I. This completes the ventilator checkout.
15. Adjust damper blade for required ventilation.
(See next section.)
16. Replace mist eliminator lter. Be sure that it is
installed with the drain holes to the bottom.
17. Remove blank off plate or barometric fresh air
damper installed on service access door. Plug four
(4) mounting holes with the plastic plugs provided
with the ventilator.
18. Replace service access panel.
19. Close control panel cover.
20. Ventilator is now ready for operation.
910-1622 STEP CONTROL ASSEMBLY. INSTALLS
HERE BY SEATING PLASTIC STAND-OFFS INTO
PROVIDED HOLES
ROUTE WIRES THROUGH
EXISTING WIRE LOOMS
ROUTE WIRES THROUGH BUSHING
INTO LOW VOLTAGE BOX
WIRES FROM
DAMPER MOTOR
MIS-2116
FIGURE 4
STEP CONTROL INSTALLATION

Manual 2100-457D
Page 9 of 16
FIGURE 5
SETTING 3-POSITION CRV DAMPER CONTROL BOARD
(Utilize the charts for your specic model on the following pages)
MIS-2117 A
"R2" ADJUSTMENT POTENTIOMETER
FOR "STAGE #1" HEATING OR COOLING
DAMPERPOSITION. ("G" AND "Y1"
CONTROL SIGNALS)
FOR "STAGE #2" HEATING OR COOLING
DAMPERPOSITION. ("G", "Y1", AND
"Y2" CONTROL SIGNALS)
"R3" ADJUSTMENT POTENTIOMETER"R1" ADJUSTMENT POTENTIOMETER
FOR "BLOWER ONLY" DAMPERPOSITION.
("G" SIGNAL ONLY)
"R7" ADJUSTMENT POTENTIOMETER
FOR APPLICATIONS WITH CO
2
SENSORS.
SEE "ADDING OPTIONAL CO
2
CONTROL
SENSOR" IN THIS MANUAL.

Manual 2100-457D
Page 10 of 16
BLADE ADJUSTMENT FOR DESIRED
VENTILATOR AIR
The amount of ventilation air supplied by the
commercial room ventilator is dependent on ve (5)
factors.
1. Return air duct static pressure drop.
2. Supply air duct static pressure drop.
3. Indoor blower motor speed.
4. Damper blade open position setting for each mode
of operation.
5. Tightness or looseness of building envelope.
You will have to set the damper position for each mode
of operation using the set-point potentiometers on the
Damper Position Step Control Board. See Figure 5.
Refer to the graphs on the following pages to determine
the necessary blade setting to achieve the ventilation
air required based upon blower only, Stage #1 and
Stage #2 modes of operation. These charts are model
specic, so you will have to match the chart to the
specic model you are working with.
1. Set the damper position for blower only operation.
A. Energize the evaporator blower by switching
thermostat to the manual fan position with
heat/cool in OFF position (or Jumper “R” to
“G” with thermostat disconnected at unit).
B. Locate potentiometer “R1” on the Damper
Position Step Control Board. See Figure 5.
C. Using a small screwdriver, adjust
potentiometer until damper position aligns
with numerical location on the label interior
of the sheet metal damper assembly.
2. Set the damper position for Stage #1 cooling/
heating operation.
A. Energize the evaporator blower and
compressorbyswitchingthermostattotheheat
or cool mode, and setting it to a minimal offset
totheroomtemperaturetoengagethemodeof
operation desired (or Jumper “R” to “G”
and “Y1” with thermostat disconnected at
unit).
B. Locate potentiometer “R2” on the Damper
Position Step Control Board. See Figure 5.
C. Using a small screwdriver, adjust
potentiometer until damper position aligns
with numerical location on the label interior of
the sheet metal damper assembly. (Make sure
there is not a call on “Y2” or “W2”.)
3. Set the damper position for Stage #2 cooling/
heating operation.
A. Energize the evaporator blower and
compressor by switching thermostat to the heat
or cool mode and set a large temperature offset
to the room temperature to engage the mode of
operation desired (or Jumper “R” to “G”,
“Y1” and “Y2” with thermostat disconnected
at unit).
B. Locate potentiometer “R3” on the Damper
Position Step Control Board. See Figure 5.
C. Using a small screwdriver, adjust
potentiometer until damper position aligns
with numerical location on the label interior of
the sheet metal damper assembly per the chart.

Manual 2100-457D
Page 11 of 16
0
100
200
300
400
500
600
700
800
0
2.5
5
7.5
10
12.5
15
17.5
20
22.5
25
27.5
30
Ventilation Airflow (CFM)
Vent Position
WA3S Ventilation Airflow
Stage #2
Operation
BlowerOnly &
Stage #1
Operation
0
100
200
300
400
500
600
700
800
900
1000
0
2.5
5
7.5
10
12.5
15
17.5
20
22.5
25
27.5
30
Ventilation Airflow (CFM)
Vent Position
WA4S Ventilation Airflow
Stage #2
Operation
Stage #1
Operation
BlowerOnly

Manual 2100-457D
Page 12 of 16
0
100
200
300
400
500
600
700
800
900
1000
0
2.5
5
7.5
10
12.5
15
17.5
20
22.5
25
27.5
30
Ventilation Airflow (CFM)
VentPosition
WA5S VentilationAirflow
Stage #2
Operation
Stage #1
Operation
BlowerOnly

Manual 2100-457D
Page 13 of 16
ADDING OPTIONAL CO
2
CONTROL
SENSOR
Adding an optional Bard Part #8403-067 to this control
will maximize the capabilities of this vent by only
supplying fresh air intake to maintain CO2levels. This
has multiple benets.
• Minimizes ventilation load on structure as it only
brings in what is required to maintain CO2levels
lowering reconditioning requirements (not having to
heat/cool as much outside air).
• Will self-adjust for various occupancy levels so
that you are not bringing in fresh air beyond need.
For example, if a room is designed for a maximum
occupancy of 40 persons (the standard ventilation
control would have to be set for that occupancy), but
the room typically only contains 25 persons. This
control will self-adjust the amount of fresh air intake
from 600 to 375 CFM automatically (based upon 15
CFM per person standard rate to ASHRAE standards).
BASIC INSTALLATION
1. Make sure power is turned off to the unit
2. Follow steps beginning on page 2 for installation
for standard control and vent assembly, then
proceed with the following steps.
3. Run (4) wire thermostat wire from the unit to the
desired CO2sensor location.
4. Follow Figure 6 to congure the CO2sensor for
proper operation.
5. Connect the thermostat wiring from the CO2sensor
to step control assembly following the wiring
diagram (enclosed in Literature Assembly or on
ventilator).
6. Connect the orange wire from the “A” terminal
of the units low voltage connection strip to the
“OCC” terminal on the step control board.
7. To check operation, restore power to the unit.
8. Make sure that thermostatic control is in
“occupied” mode of operation calling for
ventilation.
9. Have someone stand in front of the CO2sensor and
breathe on it. The display should show an increase
in CO2ppm and the damper blade in the ventilation
package should increase (may be good to have a
helper - one to breathe on control and one to
observe damper).

Manual 2100-457D
Page 14 of 16
FIGURE 6
8403-067 CO2SENSOR SET UP
17
12
FULLY OPEN150020 16145019 15140018 14135017 12130016 11125015 10120014 9115013 81100
MIS-3009 A
4-20mA AN (ppm) Damper (1) Approc. Blade
Position (2)
4 700 FULLY CLOSED 0
5 750 1
6 800 2
7 850 3
8 900 4
9 950 5
10 1000 6
11 1050 7
Settings Recommended Default
RON Not Used
ROF Not Used
DSP C CT
UNI US US
COL 700 0
COH 1500 2000
TOL Not Used
TOH Not Used
BAR See Instrution with Controller
For High Altitude Installations
CAL Used for Field Calibration
(1) Damper should be fully closed at 700 ppm, if not Potentiometer R7 can be adjusted
clockwise (CW) to close it. If it is fully closed at 700 ppm or lower no adjustments required.
(2) Blade as referenced to the Blade Position Label.
PRESS UP AND DOWN
ARROWS TO ENTER
CONFIGURATION MODE
USE ARROWS TO SELECT
SETTING. PUSH MIDDLE
BUTTON TO CHANGE.
CONTROLLER WILL
SHOW SET.
FOR PROPER OPERATION
POSITIONED AS SHOWN
JUMPERS MUST BE
NOTE: MENU
JUMPER MUST
BE SET TO "ON"
TO CHANGE ANY
SETTINGS WITH
THE FRONT BUTTONS.
TO LOCK THE CO2
CONTROLLER MOVE
JUMPER TO "OFF" AFTER
IT HAS BEEN CONFIGURED

Manual 2100-457D
Page 15 of 16
FIGURE 7
CALL FOR BLOWER OPERATION
COMMERCIAL ROOM VENTILATOR –
WA*S SERIES
FEATURES
•One piece construction – easy to install with no
mechanical linkage adjustment required.
•Exhaust air damper – built in with positive closed
position. Provides exhaust air capability to prevent
pressurization of tight buildings.
•Actuator motor – 24 volt, power open, spring return
with built in torque limiting switch.
•Provides up to 75 percent of outside air.
COMMERCIAL ROOM VENTILATOR
SEQUENCE OF OPERATION
On a call for blower operation, CRV opens to a
position as set by Step Control Position Assembly. See
Figure 7.

Manual 2100-457D
Page 16 of 16
A call for cooling cycles the compressor, and dampers
remain in the ventilation mode. On loss of blower
operation, CRV closes fully. See Figure 8.
FIGURE 8
CALL FOR COOLING OPERATION
Table of contents
Other Bard Fan manuals
Popular Fan manuals by other brands

Casa Fan
Casa Fan ECO AVIATOS 132 Mounting and operating manual

Air King
Air King AKLS Series Important instructions & operating manual

Ebmpapst
Ebmpapst R3G250-AK41-71 operating instructions

Ebmpapst
Ebmpapst A3G910-AN46-23 operating instructions

Ebmpapst
Ebmpapst K4E400-AC11-13 operating instructions

Ebmpapst
Ebmpapst W3G800-GN36-21 operating instructions