
Manual 2100-488
Page 13 of 26
WIRING — MAIN POWER
Refer to the unit rating plate for wire sizing information and
maximum fuse or “HACR” type circuit breaker size. Each
outdoor unit is marked with a “Minimum Circuit Ampacity”.
This means that the field wiring used must be sized to carry
that amount of current. Depending on the installed KW of
electric heat, there may be two field power circuits required.
If this is the case, the unit serial plate will so indicate. All
models are suitable only for connection with copper wire.
Each unit and/or wiring diagram will be marked “Use
Copper Conductors Only”. These instructions must be
adhered to. Refer to the National Electrical Code (NEC) for
complete current carrying capacity data on the various
insulation grades of wiring material. All wiring must
conform to NEC and all local codes.
The electrical data lists fuse and wire sizes (75ºC copper)
for all models, including the most commonly used heater
sizes. Also shown are the number of field power circuits
required for the various models with heaters.
The unit rating plate lists a “Maximum Time Delay Relay
Fuse” or “HACR” type circuit breaker that is to be used
with the equipment. The correct size must be used for
proper circuit protection and also to assure that there will
be no nuisance tripping due to the momentary high
starting current of the compressor motor.
The disconnect access door on this unit may be locked to
prevent unauthorized access to the disconnect. To convert
for the locking capability, bend the tab located in the
bottom left hand corner of the disconnect opening under
the disconnect access panel straight out. This tab will now
line up with the slot in the door. When shut, a padlock
may be placed through the hole in the tab preventing entry.
See Start-up section for information on three phase scroll
compressor start-ups.
WIRING — LOW VOLTAGE WIRING
230/208V, 1 phase and 3 phase equipment dual primary
voltage transformers. All equipment leaves the factory
wired on 240V tap. For 208V operation, reconnect from
240V to 208V tap. The acceptable operating voltage
range for the 240 and 208V taps are:
NOTE: The voltage should be measured at the field
power connection point in the unit and while
the unit is operating at full load (maximum
amperage operating condition).
LOW VOLTAGE CONNECTIONS
These units use a grounded 24 volt AC low voltage
circuit.
The “R” terminal is the hot terminal and the “C”
terminal is grounded.
“G” terminal is the fan input.
“Y” terminal is the compressor input.
“B” terminal is the reversing valve input. The reversing
valve must be energized for heating mode.
“R” terminal is 24 VAC hot.
“C” terminal is 24 VAC grounded.
“L” terminal is compressor lockout output. This
terminal is activated on a high or low pressure trip by
the electronic heat pump control. This is a 24 VAC
output.
“W2” terminal is second stage heat (if equipped).
“O1”terminal is the ventilation input. This terminal
energizes any factory installed ventilation option.
“E” terminal is the emergency heat input. This terminal
energizes the emergency heat relay.
“W3” terminal is the dehumidification input. This
terminal energizes compressor, blower and three-way
valve.
NOTE:For total and proper control using DDC, a total
of 7 controlled outputs are required (6 if no
ventilation system is installed). For proper
system operation under Emergency Heat
conditions where the compressor needs to be
deactivated, the B-W2-E outputs need to be
energized. Removing the Y (compressor) signal
alone turns the compressor off, but does not
activate the additional circuitry embedded in the
heat pump for proper and complete operation.
LOWVOLTAGECONNECTIONS
FOR
DDCCONTROL
Fan Only Energize G
Cooling Mode Energize Y, G
Heat Pump Heating Energize Y, G, B
2nd Stg Heating Energize G, W2, Y, B
w/Heat Pump (if employed)
Ventilation Energize G, O1
Emergency Heat Energize B, W2, E, G
Dehumidification Energize W3
paTegnaR
042612-352
802791-022
If the #8403-058 thermostat is used, nine (9) wires should
be run from the thermostat subbase to the 24V terminal
board in the unit. If the #8403-060 thermostat/humidistat
is used, ten (10) wires should be run from the thermostat
subbase to the 24V terminal board. A nine (9) or ten (10)
wire conductor (depending on thermostat used), 18 gauge
copper color-coded thermostat cable is recommended.
The connection points are shown in Figures 8 and 9.