Baso C107U User manual

Installation Instructions C107U
Issue Date June 7, 2018
24 VAC Direct Spark Gas Ignition
© 2018 BASO Gas Products 1
Part No. BASO-INS-C107U, Rev. C www.baso.com
24 VAC Universal Direct Spark Gas Ignition Control
Quick Reference Guide
The C107U Universal Direct Spark Ignition Control module replaces many
popular flame rectification type of direct spark ignition (DSI) modules, including
those manufactured by Honeywell, Robert Shaw, ICM, Fenwal, and Johnson
Controls.
The following is an overview of the C107U series control, and is intended to only
be used by Certified Service Technicians.
APPLICATION
•Gas Furnaces
•Boilers
•Water Heaters
•Commercial Cooking
FEATURES
•24 VAC microprocessor based DSI control
•System diagnostics
•32 Selectable preset timings of popular models
•Universal flame sensing (Local/Internal or Remote/External)
•Full time flame sensing
•Flame sense test pins
•4 mounting hole positions, 2 that match Honeywell and Fenwal
•Built-in burner ground
•Voltage/Frequency monitoring

24 VAC Universa Direct Spark Gas Ignition Control
© 2019 BASO Gas Products 2
Part No. BASO-INS-C107UQRG, Rev. C www.baso.com
SPECIFICATIONS
Input Voltage Control: 24 VAC (18-30 VAC) 50/60 Hz
Input Current 0.3 A nominal + valves
Gas Valve Contact Rating 4A Main @ 24 VAC
Alarm Output 2QA @ 24 VAC
Operating Temperature -40 to 176°F (-40 to 80°C)
Flame Detection Means Flame Rectification
Flame Detection Type Local/Internal or Remote/External
Minimum Flame Current 0.07 microamperes
Flame Failure Response Time 1.0 second maximum
Ignition Source High voltage spark, capacitive discharge
Maximum Spark Gap 0.2 in. (5.1 mm)
High Voltage Cable 48 in. (1219 mm) max., rated 15kV min.
(Resistive recommended)
Flame Sense Cable 48 in. (1219 mm) max., rated 15kV min.
(Shielded recommended)
Spark 30 sparks/second
Humidity 0% to 95% RH (non-condensing)
Gas Types Natural, LP, or Manufactured
Trials Before Lockout * Default, 1, or 3
Trial for Ignition (TFI) Time* Default, 4, 7, 11, or 21 seconds
Pre-Purge Time * Default, 0, or 30 seconds
Inter-Purge Time * Default, 0, 15, 30, or 90 seconds
Retry Delay Period *, ** Default, 0, 5*, or 60* minutes
Lockout Recovery Power cycle
*32 Selectable preset timings via. 5 position DIP Switch.
**Retry is not available in CE ignitions.
Agency Certifications
UL 60370-1, UL 60730-2-5 File: M2926 Software conforms to UL60730
Requirement Component Recognized System
(US & Canada)
EN298:2012 File: 657989

24 VAC Universal Direct Spark Gas Ignition Control
© 2019 BASO Gas Products 3
Part No. BASO-INS-C107UQRG, Rev. C www.baso.com
WIRING
TABLE 1: Typical Wiring Connections.
Label Term. Type Description
FC
- +
2-pin Flame Current measuring for microammeter probes in µAmp DC
BRN
GND
Mounting Tab
(Lower left)
Burner Ground connection*
24V GND
BRN GND
1/4" male QC Common side (return) of transformer connection
VLV COM 1/4" male QC Gas Valve common terminal
VLV 1/4" male QC Gas Valve connection
ALM N/A Not Available
TH-W N/A Thermostat connection
R/O N/A Rollout Switch connection
24V 1/4" male QC 24V Power connection
DIP
SWITCH
S1
5 position
DIP switch
32 selectable timings of the most popular settings
SENSE 1/4" male QC Flame Sensor connection
- For dual rod (remote/external) flame sensing,
remove Jumper Wire installed and connect flame
sense wire from the burner/igniter to this terminal
- For single rod (local/internal) sensing leave
Jumper Wire connected to the INT connector
INT 1/4" male QC - For single rod (local/internal) sensing a Jumper
Wire is connected to the SENSE connector
NOTE: Remove and discard Jumper Wire for two
rod (remote/external) flame sensing
SPARK 1/4" male QC High voltage sparking electrode
* If the existing system uses a burner ground wire, this can be attached to the 24V
GND/BRN GND terminal using the supplied dual spade connector, or otherwise
connected to the burner ground mounting tab.

24 VAC Universa Direct Spark Gas Ignition Control
© 2019 BASO Gas Products 4
Part No. BASO-INS-C107UQRG, Rev. C www.baso.com
SETUP AND ADJUSTMENTS
DIP Switch (S1) Settings
When replacing an existing ignition control with the C107U, refer to Table
2 for the correct DIP switch settings. For a complete list of the controls the
C107U replaces, see the BASO C107U Installation Instructions available
at www.baso.com.
The following timing parameters may be set with the 5-postion DIP switch
(see Table 2).
IMPORTANT:
The control timing configuration is permanently locked and cannot be reset
by changing the DIP switch settings after 10 consecutive power cycles.
FACTORY DEFAULT S1 DIP SWITCH SETTING
TIMING CONFIGURATION LABEL
Note: After the configured number
of trials for ignition with no established flame or the pre-defined number of
flame losses have occurred, controls with a retry time of 0 (i.e. none) will
enter a 100% Lockout mode, requiring the pre-defined lockout recovery
method (power cycle) to continue normal operation. However, controls
with a retry time of 5 or 60 minutes will enter a standby lockout mode for
the configured time before continuing to normal operation.
All switch settings are defaulted from the
factory to the “ON’ position. Refer to Table 2
for the desired timing configuration. The
default timings are printed on the label
located on the front of the ignition.
Once you have selected the desired timing
configuration, using a permanent marker,
write in the values and mark the DIP switch
settings on the label provided. Adhere the
label to the front of the control for future
reference.

24 VAC Universal Direct Spark Gas Ignition Control
© 2019 BASO Gas Products 5
Part No. BASO-INS-C107UQRG, Rev. C www.baso.com
Table 2 DIP Switch (S1) Settings.
SEL
Timing Configurations DIP (S1) Switch Settings
# of
Trials
Pre-
Purge TFI Inter-
Purge Retry
Time SW SW SW SW SW
# sec sec sec min 1 2 3 4 5
0 1 0 4 0 5 OFF OFF OFF OFF OFF
1 1 30 4 0 5 OFF OFF OFF OFF ON
2 1 0 7 0 5 OFF OFF OFF ON OFF
3 1 30 7 0 5 OFF OFF OFF ON ON
4 1 0 11 0 5 OFF OFF ON OFF OFF
5 1 30 11 0 5 OFF OFF ON OFF ON
6 3 0 4 30 5 OFF OFF ON ON OFF
7 3 0 4 90 5 OFF OFF ON ON ON
8 3 30 4 90 5 OFF ON OFF OFF OFF
9 3 30 7 30 5 OFF ON OFF OFF ON
10 3 0 7 90 5 OFF ON OFF ON OFF
11 3 30 7 90 5 OFF ON OFF ON ON
12 3 0 11 15 5 OFF ON ON OFF OFF
13 3 30 21 15 5 OFF ON ON OFF ON
14 3 30 21 30 5 OFF ON ON ON OFF
15 3 0 11 15 60 OFF ON ON ON ON
16* 1 0 4 0 0 ON OFF OFF OFF OFF
17* 1 30 4 0 0 ON OFF OFF OFF ON
18* 1 0 6 0 0 ON OFF OFF ON OFF
19* 1 30 6 0 0 ON OFF OFF ON ON
20* 1 0 7 0 0 ON OFF ON OFF OFF
21* 1 30 7 0 0 ON OFF ON OFF ON
22* 1 30 11 0 0 ON OFF ON ON OFF
23* 1 0 21 0 0 ON OFF ON ON ON
24* 1 30 21 0 0 ON ON OFF OFF OFF
25* 3 15 4 15 0 ON ON OFF OFF ON
26* 3 30 4 15 0 ON ON OFF ON OFF
27* 3 0 7 15 0 ON ON OFF ON ON
28* 3 30 7 15 0 ON ON ON OFF OFF
29* 3 0 11 15 0 ON ON ON OFF ON
30* 3 30 11 15 0 ON ON ON ON OFF
31* - - - - - ON ON ON ON ON
* Approved CE timing configurations.
NOTE: All controls have Quick Start and Re-ignition.

24 VAC Universa Direct Spark Gas Ignition Control
© 2019 BASO Gas Products 6
Part No. BASO-INS-C107UQRG, Rev. C www.baso.com
LED STATUS AND TROUBLESHOOTING
The ignition control has a multi-colored (GREEN, ORANGE, and RED)
LED which will flash different colors and codes to show status of the
ignition and will help troubleshoot the control.
Table 3: GREEN LED Indications of Normal Operation
Flash Indication
1 flash every 1 sec. Pre-purge, Inter-purge
Rapid flashing Trial for Ignition (TFI)
Solid on RUN (Flame, Main valve on)
Table 4: ORANGE LED Indications
Flash Indication Error Type
1 flash every 5 sec. Retry Standby
1 flash every 1 sec. Flame Present Standby
Table 5: RED LED Indications of ERROR Codes (100% Lockout)
Flash Indication Error Type
1 flash No flame in trial time 100% Lockout
2 flashes Flame sense stuck 100% Lockout
3 flashes Valve relay circuit 100% Lockout
7 flashes Repetitive flame loss 100% Lockout
8 or 9 flashes Internal control 100% Lockout
Solid on Line voltage/Frequency Standby
Note: There is a one-second pause after each flash code.
Warning: Do not install the control in areas that can be exposed to dripping water,
steam cleaning, heavy dust, grease, or corrosive chemicals. If the controls can be
subjected to this type of environment, use a NEMA 4 rated enclosure to protect the
ignition control module.
If not properly protected from the above environment, the control will prematurely fail or
malfunction. Excessive high temperatures can damage the ignition control and cause
it to malfunction. Make sure the ambient temperature around the ignition does not
exceed the rated temperature for the control.

24 VAC Universal Direct Spark Gas Ignition Control
© 2019 BASO Gas Products 7
Part No. BASO-INS-C107UQRG, Rev. C www.baso.com
TROUBLESHOOTING GUIDE
1. No power up
•Faulty 24 VAC wiring
•Thermostat or transformer
•Faulty control
•Safety limits
2. Control LED is blinking RED
•Determine error code, refer to error codes (Table 5), also
refer to the troubleshooting flow chart in the installation
instructions
3. No spark during Trial for Ignition (TFI) time
•Faulty spark electrode wiring
•Spark gap too wide
•Faulty control
4. Burner does not light during trial for ignition time
•Faulty valve wiring
•Bad Gas Valve
•Faulty Control
5. Burner lights but gas valve turns off after TFI
•Weak flame, flame not in contact with the spark electrode of
flame sensor. Check that flame sensor tip is in the flame.
For proper sensing, the rod tip must be 3/8” (10mm) to 1/2”
(13mm) in the flame. See Figure 1.
•Dirty or corroded flame sensor
•Faulty flame sensor wiring
•Poor burner ground
Note: For more information on BASO ignitions and other products, plus
complete installation instructions, please visit us at www.baso.com.
Figure 1: Proper Flame Sensor Position
CORRECT FLAME TOO LOW FLAME TOO HIGH

24 VAC Universa Direct Spark Gas Ignition Control
© 2019 BASO Gas Products 8
Part No. BASO-INS-C107UQRG, Rev. C www.baso.com
FLAME CURRENT MEASUREMENT
Flame current of the device can be measured using a standard
microammeter by simply touching the meter leads to the 2 PIN labeled FC,
as shown in Figure 2.
•Flame current must be measured with flame lit and main gas
flowing
•Set meter to DC μAmp scale.
•Make sure meter leads are positioned correctly [+/-].
•Typical Flame Sense Current of 0.4 to 1.0 μAmp DC.
Figure 2: Microammeter Connection.
Important: Preventative maintenance programs are an important part of maintaining
optimum and safe function of you BASO Products. Any attempt to repair this assembly
voids the manufacturer's 2-year warranty. For a replacement control, contact the original
equipment manufacturer or nearest BASO Gas Products distributer.
450 East Horseshoe Road
PO Box 170
Watertown, WI 53094 www.baso.com
1-877-227-6427 (1-877-BASOGAS) Published in U.S.A.
BLACK (-) RED (+)
Table of contents
Other Baso Control Unit manuals
Popular Control Unit manuals by other brands

LG Chem
LG Chem EM048063P3S installation manual

Mitsubishi
Mitsubishi NZ2GF2B-60DA4 user manual

Baumuller
Baumuller BM4-O-CAN-06 operating instructions

Trident
Trident FOAMATE 2.1 Technical manual

KUGELHAHN MÜLLER
KUGELHAHN MÜLLER KM-O Series Operating and maintenance instructions

Olfer
Olfer CAS-24V-ZHAGA-4P-40-DA instruction manual