BEINAT SGM600 User manual

Belonging to
Indispensabile instrument for the annual check of the probes
Instrument of testing TS1008
To facilitate the reading of the functional parameters of the probe as well
as the control of annual operating, the BEINAT S.r.l. has built a new
portable tester TS1008.
The tester allows to read all the data in the memory of the probes eand by
serial transmission,it prints the ticket that confirms the testing data.
The SGM600is born from the elegance and prestige thathas alwaysdistinguished BEINAT S.r.l.andfromthehome
fitness concept.
The probe is a Catalytic gas detection unit with IP66 protection that, together with one of BE INAT’s industrial
type Control Units, detects the presence of esplosive gas such as Methane, LPG, Hydrogen, and other types of
gas.
The probe is managed by a microprocessor which not only supplies an alarm signal to the control unit connected
to it, but also allows execution of a self-diagnosis and therefore an AUTOMATIC CALIBRATION, in order to always
have the maximum detection accuracy.
The self-calibration meansthe probe adapts in harsh and variable temperature environments, avoiding false alarms
due to anomalous events.
The probe has a 0 ÷ 20 % LEL linear output conforming to the 4 ÷ 20mA standard, for which can be connected
with one of BEINAT's industrial control units.
The important innovation of this probe is:
The possibility to substitute the sensor at the end of the operating cycle or fault by the technician without having
to send to BEINAT Srl.
CONFORMITY
Installation and user
guide
Important: Assembly / maintenance of the appliance must be carried out by qualified personnel and in
accordance with applicable laws and regulations.
The manufacturer assumes no responsibility for the use of products that have to comply with particular
environmental and / or installation standards.
Important note
Beforeconnecting the equipment, it is recommended that you read the instruction manual carefully and
keep it for future reference. It is also recommended to perform the electrical connections correctly as
per enclosed drawings, observing the instructions and the Standards.
N.B. Refer to the documentation in all cases where the symbol is on the side
EN50194
EN 50270
Compliant EN 60079-29-1
Installation EN60079-29-2
Reports issued by TUV Italia
Channel: Beinat gas solutions
Electricconnections alsoavailable on
Conventional Gas Sensor SGM600
V. R0

Page 2
Power Supply .................................................................................................... 12÷24VDC ± 10%
Power demand ................................................................. 90 mA in operating, 110 mA in alarm Max @ 13,8 V
Notifications ..................................................... green light normal operation, yellow light fault, red light alarm
Slot exspansion board relay; CARD-03 ....................... Fault , Prealarm, Allarm. Relay contacts 1A 30 VDC SELV
Sensor ............................................................................................................................... Cartalityc
Sensitive element working range ...................................................................................... To 100% of LEL
Analog output signal ...................................................................................... 4÷20 mA standard tolerance
Selection of the operating Range ................................................................ from 20% of LEL to 100% of LEL
Detector accuracy ..................................................................................................................... 1% FS
Long term shift in clean air ................................................................................................... < 3% of LEL
Auto zero procedure ............................................................................ Included in the software algorithms
Response Time ............................................................................................................................ <10”
Warm-up time ................................................................................................................... 1,30 minutes
Functioning humidity ........................................................................................ 0-90% non condensed
Functioning temperature ............................................................................................ -10°C to +60°C
Control units usable ............. BX444-Mc, BX449F, GS100M, BX180, BX280, BX150, GS300-Mc, BX316xp, BX308xp
Max. distance between probe and unit .......................................................................................... 100 m
Cable diameter for connecting probe .............................................................................................. 1 mm
Connection: The cable of connection of the probe must not be installed together with the power cables.
Otherwise, make sure to use a shielded cable
Electromagnetic compatibility Reference Norms ............................................................................ EN 50270
Probe’s body material ............................................................................................................. Aluminium
External degree of protection ........................................................................................................ IP66
Size ................................................................................................................................. 100x100x60
CHECK the integrity of the unit after having removed it from the box.
Check that the data written on the box correspond to the type of gas used.
When doing the electrical connections, follow the drawing closely.
Any use of the detector for purposes other than the intended one is considered improper,
and as a result of which BEINAT S.r.l. therefore disclaims any responsibility for possible
damages caused to people, animals or objects.
TERMS and EXPECTATIONS: The installation of the SGM600 Sensor, its ordinary and
extraordinary maintenance, every six months, and its out of service removal at the end of
the functional life guaranteed by the manufacturer, must be carried out by authorized or
specializedpersonnel.
Do not allow it to become wet.
The control unit can be seriously damaged as it is not waterproof either when immersed in water or exposed to high
levelsof humidity.
Do not drop it.
Heavy knocks or falls during transportation or installation can damage the appliance.
Avoid abrupttemperature fluctuations.
Sudden temperature variations can cause condensation and the control unit could work poorly.
Cleaning
Never clean the device with chemical products. If necessary, wash with a moist cloth.
Precautions
Technical Specifications
WARNING!
The CATALITIC sensor has a life span of 5 to 6 years in clean air.
The working temperature of the probe recommended is from -10 ° C to + 60 ° C.
Every puffy snapshot of gas over 100% of L.I.E. Takes months off the sensor.
Each immediate puff of gas that exceeds 100% of L.E.L. takes away months of life from the sensor.
The detector must be tested by simulating the presence of gas by issuing it from a pre-calibrated testing aerosol.
Important:
The test of operation and eventually offset cancellation must be performed at least once a year, by a qualified
technician.
Code Type of Gas Sensor Working range Temperature
SGM600met Methane Catalytic LEL0-100% -10+60°C
SGM600Agpl LPG Catalytic LEL0-100% -10+60°C
SGM600Aidr Hydrogen Catalytic LEL0-100% -10+60°C
SGM600Aamm Ammonia explosiv Catalytic LEL 0-100% -10+60°C
SGM600Aace Acetylene Catalytic LEL0-100% -10+60°C
SGM600Avbe Gasoline vapours Catalytic LEL 0-100% -10+60°C
SGM600Aalc Alcohol Catalytic LEL0-100% -10+60°C
Technical Features SGM600

Page 3
The installation of the detector does not exempt from the compliance with all regulations concerning the characteristics,
installation and use of gas appliances. The ventilation of the spaces and the elimination of combustion products are described
in the UNI norms according to ART. 3 LAW 1083 / 71 and relevant legal provisions.
Compatible control units
CONTROL UNITS MOUNTING PROBES Max. DEGREE PRE ALARMS POSITIVE OPERATING
protec. alarms safety range
GS100M unit 1 zone Wall/cabinet 1 IP44 2 1 YES NO
GS300-Mc unit 1 zone Wall/cabinet 3 IP44 2 1 YES NO
BX444-MC unit 1 zone Wall/cabinet 4 IP44 2 1 YES NO
BX150 unit 1 zone Panel 1 IP42 1 1 YES NO
BX180 unit 1 zone Omega bar DIN 1 IP20 1 1 YES NO
BX280 unit 1 zone Omega bar DIN 2 IP20 1 1 YES NO
BX449F unit 1 zone Omega bar DIN 4 IP20 1 1 YES NO
BX308 unit 1 zone Omega bar DIN 8 IP20 1 1 YES YES
BX308/Box unit 1 zone Wall 8 IP65 1 1 YES YES
BX316 unit 2 zones Barra Omega 16 IP20 1 2 YES YES
BX316/Box unit 2 zones Wall 16 IP65 1 2 YES YES
TAKITJ8 * Data Collector Wall 8 IP65 - - - -
MAINTENANCE
The user periodically (every 6 months) must perform a check of the operation of the control unit by spraying
a suitable test gas at the base of the probes connected until the alarm condition is reached.
• At least once a year make a more accurate check by a specialist technician.
• Disabling the detector must be carried out by qualified personnel.
Side View
60 mm
80 mm
80 mm
Rearward View
Foro 6,5 mm
100 mm
100 mm
40 mm
Front View

Page 4
The position of the probe is a crucial factor for a gas detection unit correct functioning.
In order to obtainthe maximum results from an appliance and minimize the probabilities of false alarms, we recommend
to follow this diagram and to keep in mind the following general rules.
The remote probe must be located at different heights, according to the type of gas.
These heights are:
- 30 cm from the lowest point of the floor in order to detect Heavy Gases :LPG, Gasoline vapours, Alcohol,
white spirit, Ethanol, Acetone, Chlorine, CO.
-30cmfrom thehighestpoint ofthe ceilingin orderto detect Lightgases: Methane,Hydrogen, Ammonia,Acetylene.
- The probe should not be placed near the appliances to be controlled (boilers, burners, industrial kitchens, etc.) but
on the opposite wall.
- The probe should not be affected by smoke, vapour, etc. as they could distort their measurement. It must be placed
away from sources of heat, suction fans, ventilation fans.
Positioning of the Sensor
Detectiondiagramsdata
30 cm. Heavy gases
Average height volatile gases
30 cm. Light gases
ppm
0 50 100 150 200 250 300
6,7
Toxic Gas Detection diagram
0 4 5 10 15 20
7,2
20
m A
Linear +/-5%
Zona Avaria
9,3
12
14,6 17,3
Explosive Gas Detection diagram
0 4% 8% 12% 16% 20%
0 4 5 10 15 20
7,2
10,4
13,6
16,8
20
m A
Linear +/-5%
L.I.E.
Zona Avaria
Current-Voltage Conversion Graph
with 220 Ohm Load Resistance
0 4 5 10 15 20
V.
m A
0,88 1,1 2,2 3,3 4,4
Linear +/-5%
NO ! NO !

Page 5
WARNING
Before connecting to the mains power, ensure the voltage is correct. Carefully follow the instructions and the
connections according to Regulations in force, keeping in mind that the signal cables should be laid separate
from the power cables
3 2 1
Led ON
100% 20%
Selection operation range
Warning !!
Before to do this, it may want to check the operation range of the control unit.
100% 20%
OPTIONALCARD03BOARDINSERTION
Before inserting the Open Collector CARD03
board, switch off the power to the probe.
Insert the board according to the drawing
keeping the terminal block on the left.
All relays are voltage free.
Contact capacity 1A 30VDC SELV
Electrical connections
1
2
3
4
5
6
7
1
2
3
4
5
6
7
1
2
3
4
5
6
7
ON
1 2 3 4 5 6
K1 K2 K3
Connettore a innesto
montato su sonda
LedON
connection USB port
Selec. operation range
{FUNCTIONING OF LED
TheintegratedLEDonthesondehasathreefold
function:
1) Green LED. Normal operation; In waiting
phase, the LED flashes.
2) Red LED. State of alarm; The frequency of
light changes according to the percentage of
gasmonitored.
3)Led yellow. The probe detects an anomaly,
FAULT
3 2 1
R
PowerSupply
12÷24 V.
Linear Output 4-20 mA
Optional Relay Board CARD03
1 2 3 4 5 6
C
NO
C
NO
C
NO
Fault Relay Pre-Allarme
Relay Main Alarm
Relay
SELECTIONOF THE OPERATING RANGE
The SGM600 ConventionalProbes, NOT SUITABLEIN ATEXZONE,
leave the factory with a default Operating Range value set at 20%
of the LEL
To select the operation range to 100% LEL you need to move
the jumper between the central and the left pole.

Page 6
Test after replacing the sensor.
Reconnect the power, the probe starts blinking to the waiting time (Warm-up).
After waiting you can proceed to test the functioning inputting the sample gas.
WARNING !! From this moment on for all the duration of 24 hours of self-calibration, the probe must stay in
clean air without loss of GAS.
The probe continues to blink at a low frequency again for 24 hours to make sure that the probe do the auto
calibration.
Before performing this operation disconnect the power to the probe
Attention!!
The regulations described in this paragraph must performed be authorized and specialized technician are suceptibile
to compromise the safety of the survey.
If the device does not start up.
Check that the 12/24 Vdc power is present, and that positive and negative polarity has not been inverted.
If the Fault LED lights up.
Check that the cables are connected accordingtothe drawing, and that the wire isolation sheath has not been pinched.
Check the voltage at the terminals 1-2. It must be higher than 10,80 Vdc and lesser than 26,4 Vdc.
Check that the connector of the sensor is correctly inserted.
If it’s connected to control unit. Check the voltage at the terminals 2-3. It must be from a minimum of 0.8 Vdc to
a maximum of 1.1 Vdc.
Remark.
If the probes are connected to the control units BX308 and BX316 the voltage at the terminals 2 and 3 must be from
a minimum of 0.6 to a maximum of 0.75 VDC
If other problems arise, a specialised and/or authorised technician and/or the Distributor of
BEINAT S.r.l. should be contacted directly.
WARNING.
These measurement should be performed in
clean air.
Moreover, this test must be performed only
with the probe connected to a control unit, or
with a 220 Ohm resistance installed between
terminal 2 and terminal 3.
.
Troubleshooting before calling atechnician
Maintenance and gas sensor replacement
Probewith sensor Probe with sensor Sensor Probe with sensor
to be raplaced removed remounted
LinearOtput4-20mA
3 2 1
R
013
2
1,1
V.
Voltmeter
PowerSupply
12÷24 V.

Page 7
Gas imput Test
WARNING! Actions to be taken in case of alarm
Gas
1) Put out all free flames.
2) Close the main gas tap or the LPG cylinder tap.
3) Do not turn any lights on or off; do not turn on any electrical device or appliance.
4) Open windows and doors in order to increase ventilation.
If the alarm stops, its cause must be found and the relevant consequent measures taken.
If the alarm continues and the cause of gas presence cannot be found or removed, abandon the building and call
the emergency services when outside (fire department, distributors, etc.)
IMPORTANT: The operation test should not be carried out with the gas tap as this does not guarantee a sufficient
concentration to activate the general alarm.
Warning !!
If you have the following symptoms: vomiting, sleepiness, or else, go to the closest first aid station
and inform the operators that you could have been poisoned by Carbon Monoxide, or by an excess
or deficiency of oxygen
NOTES
The installation of the SGM600 probe, its ordinary and
extraordinary maintenance, and its out of service removal at
the end of the functional life guaranteed by the manufacturer,
must be carried out by authorized or specialized personnel.
Thegeneraltestshouldbe performedby issuing gasfromapre-
calibrated aerosol within the percentages illustrated on the
side.
Important: This test must be carried out at least once a year.
Gas
TEST SGM600
with pre calibrated gas bottle
at 20% of LEL ±2%
For GAS
Methane
LPG
Hydrogen
Ammonia-explosiv
Acetylene
Gasolinevapors
Alcohol

BE- V. R0 17 25
IP66 Madein Italy
BEINAT S.r.l.
Via Fatebenefratelli 122/C 10077, S. Maurizio C/se (TO) - ITALY
Tel. 011.921.04.84 - Fax 011.921.14.77
http:// www.beinat.com
Lo styling è della b & b design
Stamp and signature of the dealer
Purchase date:
Serial Number :
Sensor SGM600
INSURANCE. This device is insured by the SOCIETÀ REALE MUTUA for the PRODUCT'S GENERAL LIABILITY
up to a maximum of 1,500,000.00 EURO against damages caused by the device in case of failures in functioning.
WARRANTY. The warranty term is 3 years from manufacturing date, in agreement with the following
conditions. The components acknowledged as faulty will be replaced free of charge, excluding the replacement
of plastic or aluminium cases, bags, packing, batteries and technical reports.
The device must arrive free of shipment charges to BEINAT S.r.l.
Defects caused by unauthorized personnel tampering, incorrect installation and negligence resulting from
phenomena outside normal functioning shall be excluded from the warranty.
BEINAT S.r.l. is not liable for possible damage, direct or indirect, to people, animals, or things; from product
faults and from its enforced suspension of use.
DISPOSAL OF OLD ELECTRICAL & ELECTRONIC EQUIPMENT.
This symbol on the product or its packaging to indicates that this product shall not be treated as household waste. Instead, it shall be handed over to
the applicable collection point for the recycling of electrical and electronic equipment, such as for example:
- sales points, in case you buy a new and similar product
- local collection points (waste collection center, local recycling center, etc...).
By ensuring this product is disposed of correctly, you willhelpprevent potential negative consequence for the environment and human health, which could
otherwise be caused by inappropriate waste handing of this product. The recycling of materials will help to conserve natural resources. For more detailed
information about recycling of this product, please contact your local city office, your household waste disposal service or the shop where you purchased
theproduct.
Attention: in some countries of the European Union, the product is not included in the field of application of the National Law that applies the European
Directive 2002/96/EC and therefore these countries have no obligation to carry out a separate collection at the “end of life” of the product.
Help Desk - laboratorio@beinat.com
The Beinat S.r.l. following the targhet to improve its products, reserves the right to modify the technical features, aesthetic and functional any
time without prior notice.
Table of contents
Other BEINAT Accessories manuals
Popular Accessories manuals by other brands

Dorner
Dorner AquaPruf 7600 Series Installation, Maintenance, and Parts Manual

Steen QOS
Steen QOS SA079 Instruction for operation and maintenance

PCB Piezotronics
PCB Piezotronics M221B02 Installation and operating manual

Sunjoy
Sunjoy S-AW054PST-A owner's manual

Summit Treestands
Summit Treestands SU82024 Instruction booklet

senva
senva CHTWL Series installation instructions