Beko DRYPOINT RAX 600-5000 NA User guide

EN - english
Instructions for installation and operation
Compressed air refrigeration dryer
DRYPOINT®RAX 600-5000 NA

2 DRYPOINT® RAX 600-5000 NA
Dear customer,
Thank you for deciding in favour of the DRYPOINT®RAX 600-5000 NA compressed-air refrigeration dryer. Please read
these installation and operating instructions carefully before mounting and starting up the DRYPOINT®RAX 600-5000
NA and follow our directions. Perfect functioning of the DRYPOINT®RAX 600-5000 NA and thus reliable
compressed-air drying can only be guaranteed when the provisions and notes stipulated here are strictly adhered to.

DRYPOINT® RAX 600-5000 NA 3
Contents
1Name plate 5
2Safety instructions 5
2.1Safety pictograms in accordance with DIN 4844 6
2.2Signal words in accordance with ANSI 8
2.3Overview of the safety instructions 8
3Proper use 11
4Exclusion from a field of application 11
5Operating instructions in accordance with the 97/23/EC Pressure Equipment Directive 12
6Transport 13
7Storage 13
8Installation 14
8.1Place of installation 14
8.2Installation plan 15
8.3Correction factors 16
8.4Connection to the compressed-air system 17
8.5Connection to the cooling-water network 17
8.6Minimum cooling-water requirements: 18
8.7Electrical connections 19
8.8Condensate drain 20
9Start-up 20
9.1Preliminary stages 20
9.2Initial start-up 21
9.3Start-up and shut down 22
10Technical data 23
10.1Technical data DRYPOINT RAX 600-5000 NA-RB 23
10.2Technical data DRYPOINT RAX 600-5000 NA-FB 24
11Technical description 25
11.1Control panel 25
11.2Functional description 25
11.3Flow chart (air-cooled) 26
11.4Flow chart (water-cooled) 26
11.5Refrigerating compressor 27
11.6Condenser (air-cooled) 27
11.7Condenser (water-cooled) 27
11.8Cooling-water regulating valve 27
11.9Filter dryer 27
11.10Capillary tube 27
11.11Aluminium heat exchanger 27
11.12Hot-gas bypass valve 27
11.13Refrigerant pressure switches LPS – HPS 27
11.14Compressor crankcase heater 28
11.15DMC 24 electronics (control unit compressed-air dryer) 28
11.15.1Switching the dryer on 28
11.15.2Switching the dryer off 29
11.15.3Indication of the operating parameters – Info menu 29
11.15.4Indication of a service warning 30
11.15.5Alarm indication 31
11.15.6Display of the alarm memory – log menu 32
11.15.7Control of the dryer via remote control 32
11.15.8Operation of the potential-free failure/alarm contact 32
11.15.9Connection to a serial line 32
11.15.10 Operating Parameters-SETUP Menu
11.16Electronically level-controlled BEKOMAT condensate drain 34
12Maintenance, troubleshooting, spare parts and dismantling 35
12.1Checks and maintenance 35
12.2Troubleshooting 36

4 DRYPOINT® RAX 600-5000 NA
12.3Recommended spare parts 41
12.4Maintenance works at the refrigeration cycle 43
12.5Dismantling the dryer 43
13Appendices 44
13.1Dryer dimensions 44
13.1.1Dimensions DRYPOINT RAX 600-1250 NA 44
13.1.2Dimensions DRYPOINT RAX 1500-2500 NA 45
13.1.3Dimensions DRYPOINT RAX 3000 NA 46
13.1.4Dimensions DRYPOINT RAX 4000-5000 NA 47
13.2Exploded diagrams 48
13.2.1Components of the exploded diagrams 48
13.2.2Exploded diagram DRYPOINT RAX 600-1250 NA /AC 49
13.2.3Exploded diagram DRYPOINT RAX 1500-2500 NA /AC 50
13.2.4Exploded diagram DRYPOINT RAX 3000 NA /AC 51
13.2.5Exploded diagram DRYPOINT RAX 4000-5000 NA /AC 52
13.2.6Exploded diagram DRYPOINT RAX 600-1250 NA /WC 53
13.2.7Exploded diagram DRYPOINT RAX 1500-2500 NA /WC 54
13.2.8Exploded diagram DRYPOINT RAX 3000 NA /WC 55
13.2.9Exploded diagram DRYPOINT RAX 4000-5000 NA /WC 56
13.3Electric diagrams 57
13.3.1Electric diagrams – list of components 57
13.3.2Electric diagrams DRYPOINT RAX 600-1250 NA - Electronic control unit DMC 24 Sheet 1/3 58
13.3.3Electric diagrams DRYPOINT RAX 600-1250 NA - Electronic control unit DMC 24 Sheet 2/3 59
13.3.4Electric diagrams DRYPOINT RAX 600-1250 NA - Electronic control unit DMC 24 Sheet 3/3 60
13.3.5Electric diagrams DRYPOINT RAX 1500-2500 NA - Electronic control unit DMC 24 Sheet 1/4 61
13.3.6Electric diagrams DRYPOINT RAX 1500-2500 NA - Electronic control unit DMC 24 Sheet 2/4 62
13.3.7Electric diagrams DRYPOINT RAX 1500-2500 NA - Electronic control unit DMC 24 Sheet 3/4 63
13.3.8Electric diagrams DRYPOINT RAX 1500-2500 NA - Electronic control unit DMC 24 Sheet 4/4 64
13.3.9Electric diagrams DRYPOINT RAX 3000-5000 NA - Electronic control unit DMC 24 Sheet 1/6 65
13.3.10Electric diagrams DRYPOINT RAX 3000-5000 NA - Electronic control unit DMC 24 Sheet 2/6 66
13.3.11Electric diagrams DRYPOINT RAX 3000-5000 NA - Electronic control unit DMC 24 Sheet 3/6 67
13.3.12Electric diagrams DRYPOINT RAX 3000-5000 NA - Electronic control unit DMC 24 Sheet 4/6 68
13.3.13Electric diagrams DRYPOINT RAX 3000-5000 NA - Electronic control unit DMC 24 Sheet 5/6 69
13.3.14Electric diagrams DRYPOINT RAX 3000-5000 NA - Electronic control unit DMC 24 Sheet 6/6 70

Name plate
DRYPOINT® RAX 600-5000 NA 5
Pos: 1 /B eko Tec hnische Do kumenta tion/Übe rschri ften/1/ Siche rheitsh inweise @ 0 \mod_11 836376 09261_6 .doc @ 5365
1 Name plate
The name plate is on the back of the dryer and comprises all primary data of the device. Always refer to these data
when contacting the manufacturer or the sales department.
All guarantee claims will expire in the event that the name plate is modified or removed.
2 Safety instructions
Pos:2 /Beko Technische Dokumentation/GlobaleTexte/AllgemeinerHinweisBM @ 0\mod_1183615737313_6.doc@ 4004
Pos:3 /Beko Technische Dokumentation/Sicherheit/HinweisAnleitung BEKO @ 0 \mod_1184147787557_6.doc@ 5 758
Please check whether or not these instructions correspond to the device type.
Please adhere to all advice given in these operating instructions. They include essential information
which must be observed during installation, operation and maintenance. Therefore, it must be ensured
that these operating instructions are read by the fitter and the responsible operator / certified skilled
personnel prior to installation, start-up and maintenance.
The operating instructions must be accessible at all times at the place of application of the DRYPOINT®
RAX 600-5000 NA compressed-air refrigeration dryer.
In addition to these operating instructions, local and national regulations need to be observed, where
required.
Ensure that operation of the DRYPOINT®RAX 600-5000 NA compressed-air refrigeration dryer only
takes place within the permissible limit values indicated on the name plate. Any deviation from these
limit values involves a risk for persons and for the material, and may result in malfunction or a
breakdown.
After installing the device correctly and in accordance with the instructions in this manual, the dryer is
ready to operate, further settings are not required. Operation is fully automatic and maintenance is
limited to several examinations and cleaning measures which are described in the following chapters.
This manual must be available at all times for future reference and is a constituent part of the dryer.
If you have any queries regarding these installation and operating instructions, please contact BEKO
TECHNOLOGIES GMBH.

Safety instructions
6 DRYPOINT® RAX 600-5000 NA
2.1 Safety pictograms in accordance with DIN 4844
Observe operating instructions
General danger symbol
Supply voltage
Danger: component or system under pressure
Hot surfaces
Non-breathable air
Do not use water to extinguish the fire
Do not operate with open cover (housing)
Maintenance works or controlling measures must only be carried out by qualified personnel 1
Do not smoke
Note
Pos:4 /Beko Technische Dokumentation/Sicherheit/GefahrDruckluft @ 0\mod_1184148143854_6.doc@ 577
6
ARIA
AIR
LUFT
AIR
Connection point compressed-air inlet
ARIA
AIR
LUFT
AIR
Connection point compressed-air outlet
Connection point condensate drain
Connection point cooling-water inlet (water-cooled)
Connection point cooling-water outlet (water-cooled)
1Certified skilled personnel are persons who are authorised by the manufacturer, with experience and technical training, who are
well-grounded in the respective provisions and laws and capable of carrying out the required works and of identifying and avoiding
any risks during the machine transport, installation, operation and maintenance.
Qualified and authorised operators are persons who are instructed by the manufacturer regarding the handling of the refrigeration
system, with experience and technical training, and who are well-grounded in the respective provisions and laws.

Safety instructions
DRYPOINT® RAX 600-5000 NA 7
Works can be carried out by the operator of the plant, provided that they are skilled accordingly
2
.
NOTE: Text that contains important specifications to be considered – does not refer to safety precautions.
The device was carefully designed with particular attention paid to environmental protection:
•CFC-free refrigerants
•CFC-free insulation material
•Energy-saving design
•Limited acoustic emissions
•Dryer and packaging comprise reusable materials
This symbol advises the user to observe the environmental aspects and comply with the recommendations
connected with this symbol.
2Certified skilled personnel are persons who are authorised by the manufacturer, with experience and technical training, who are
well-grounded in the respective provisions and laws and capable of carrying out the required works and of identifying and avoiding
any risks during the machine transport, installation, operation and maintenance.
Qualified and authorised operators are persons who are instructed by the manufacturer regarding the handling of the refrigeration
system, with experience and technical training, and who are well-grounded in the respective provisions and laws.

Safety instructions
8 DRYPOINT® RAX 600-5000 NA
2.2 Signal words in accordance with ANSI
Danger! Imminent hazard
Consequences of non-observance: serious injury or death
Warning! Potential hazard
Consequences of non-observance: possible serious injury or death
Caution! Imminent hazard
Consequences of non-observance: possible injury or property damage
Notice! Potential hazard
Consequences of non-observance: possible injury or property damage
Important! Additional advice, info, hints
Consequences of non-observance: disadvantages during operation and maintenance, no danger
2.3 Overview of the safety instructions
Certified skilled personnel
Installation works must exclusively be carried out by authorised and qualified skilled personnel. Prior to
undertaking any measures on the DRYPOINT®RAX 600-5000 NA compressed-air refrigeration dryer,
the certified skilled personnel shall read up on the device by carefully studying the operating
instructions. The operator is responsible for the adherence to these provisions. The respective
directives in force apply to the qualification and expertise of the certified skilled personnel.
For safe operation, the device must only be installed and operated in accordance with the indications in
the operating instructions. In addition, the national and operational statutory provisions and safety
regulations, as well as the accident prevention regulations required for the respective case of
application, need to be observed during employment. This applies accordingly when accessories are
used.
Danger!
Compressed air!
Risk of serious injury or death through contact with quickly or suddenly escaping compressed
air or through bursting and/or unsecured plant components.
Compressed air is a highly dangerous energy source.
Never work on the dryer when the system is under pressure.
Never direct the compressed-air outlet or condensate drain hoses at persons.
The user is responsible for the proper installation of the dryer. Non-observance of the instructions in the
"Installation" chapter leads to the expiration of the guarantee. Improper installation may result in
dangerous situations for the personnel and/or the device.
Pos:5 /Beko Technische Dokumentation/Sicherheit/MaßnahmenDruckluftBM @ 0\mod_1184148284291_6.doc@ 5812
Pos:6 /Beko Technische Dokumentation/Sicherheit/GefahrNetzspannung@ 0\mod_1184148186948_6.doc@ 5794
Danger!
Supply voltage!
Contact with non-insulated parts carrying supply voltage involves the risk of an electric shock
resulting in injuries and death.
Only qualified and skilled personnel are authorised to run electrically-operated devices. Prior to
undertaking maintenance measures at the device, the following requirements must be met:
Make sure that the power supply is switched off and that the device is off and marked for maintenance
measures. Please also ensure that the power supply cannot be re-established during the works.
Pos:7 /Beko Technische Dokumentation/Sicherheit/MaßnahmenNetzspannungBM 31/32/33@ 0\mod_1216898430699_6.doc@ 11319
Caution!
Refrigerant!
The compressed-air refrigeration dryer uses HFC-containing refrigerants as a coolant.
Please observe the corresponding paragraph entitled "Maintenance works at the refrigeration cycle".

Safety instructions
DRYPOINT® RAX 600-5000 NA 9
Warning!
Refrigerant leak!
A refrigerant leak involves the danger of serious injury and damage to the environment.
The DRYPOINT
®
RAX 600-5000 NA compressed-air refrigeration dryer contains fluorinated
greenhouse gas/refrigerant.
Installation, repair and maintenance works at the refrigeration system must only be carried out by
certified skilled personnel (specialists). A certification in accordance with EC regulation 303/2008 must
be available.
The requirements of the EC 842/2006 directive must be met under all circumstances.
Please refer to the indications on the name plate as regards the type and amount of refrigerant.
Comply with the following protective measures and rules of conduct:
•Storage: Keep the container tightly closed. Keep it in a cool and dry place. Protect it against heat
and direct sunlight. Keep it away from ignition sources.
•Handling: Take measures against electrostatic charging. Ensure good ventilation/suction at the
workplace. Check fittings, connections and ducts for tightness. Do not inhale the gas. Avoid contact
with the eyes or the skin.
•Prior to carrying out works on refrigerant-carrying parts, remove the refrigerant to such an extent that
safe working is possible.
•Do not eat, drink or smoke during work. Keep out of the reach of children.
•Breathing protection: ambient-air-independent respirator (at high concentrations).
•Eye protection: sealing goggles.
•Hand protection: protective gloves (e.g. made of leather).
•Personal protection: protective clothing.
•Skin protection: use protective cream.
In addition, the safety data sheet for the refrigerant needs to be observed!
Caution!
Hot surfaces!
During operation, several components can reach surface temperatures of more than 140°F
(60°C). There is the risk of burns.
All components concerned are installed inside of the closed housing. The housing must only be opened
by certified skilled personnel 3.
Caution!
Improper use!
The device is intended for the separation of water in compressed air. The dried compressed air cannot
be used for breathing-air purposes and is not suitable for the direct contact with food.
This dryer is not suitable for the treatment of contaminated air or of air containing solids.
3Certified skilled personnel are persons who are authorised by the manufacturer, with experience and technical training, who are
well-grounded in the respective provisions and laws and capable of carrying out the required works and of identifying and avoiding
any risks during the machine transport, installation, operation and maintenance.
Qualified and authorised operators are persons who are instructed by the manufacturer regarding the handling of the refrigeration
system, with experience and technical training, and who are well-grounded in the respective provisions and laws.

Safety instructions
10 DRYPOINT® RAX 600-5000 NA
Note!
Contaminated intake air!
In the event that the intake air is strongly contaminated (ISO 8573.1 class 3.-3 or poorer quality), we
recommend the additional installation of a prefilter (e.g. CLEARPOINT F040), to avoid clogging of the
heat exchanger.
Caution!
Heating-up through fire!
In the event of a heating-up through fire, the containers and pipes of the refrigerant system can
burst.
In this case, please proceed as follows:
Switch off the refrigeration plant.
Switch off the mechanical ventilation of the machinery compartment.
Use ambient-air-independent respirators.
Containers and plants which are filled with refrigerant can burst violently in the event of fire.
The refrigerants themselves are incombustible, but they are degraded to very toxic products at high
temperatures.
Remove the container/plant from the fire zone, as there is the risk of bursting!
Cool down containers and bottles via a directed water jet from a safe position.
In the event of fire, please use an approved fire extinguisher. Water is not a suitable agent to extinguish
an electrical fire.
This must only be carried out by persons who are trained and informed about the hazards emanating
from the product.
Caution!
Unauthorised intervention!
Unauthorised interventions may endanger persons and plants and lead to malfunction.
Unauthorised interventions, modification and abuse of the pressure devices are prohibited.
The removal of sealings and leadings at safety devices is prohibited.
Operators of the devices must observe the local and national pressure equipment regulations in the
country of installation.
Pos: 8 /B eko Technische D oku me ntati o n/S iche rhei t/S i cher he its hinw eis e, w ei tere B M (ni cht E x) @ 0\mod_11836 161 0377 0_ 6.do c @ 40 09o s: 9 /Beko TechnischeDokumentation/Sicherheit/ZusatzSic herheitshinweiseBM33 @ 0\mod_1231926887620_6.doc@ 12829s:10 /Beko TechnischeDokumentation/Sicherheit/VorsichtFehlfunktion@0\mod_1214378096290_6.doc@ 9359
Note!
Ambient conditions!
In the event that the dryer is not installed under suitable ambient conditions, the ability of the device to
condense refrigerant gas is impaired. This can result in a higher load of the refrigerating compressor,
and in a loss of efficiency and performance of the dryer.
This in turn leads to overheated condenser fan motors, to malfunction of electric components and to a
breakdown of the dryer. Failures of this type will affect warranty considerations.
Do not install the dryer in an environment in which chemicals with a corrosive effect, explosive gases,
toxic gases, evaporation heat, high ambient temperatures or extreme dust and dirt can be found.
Pos:1 2 /BekoTechnische Dokumentation/Überschriften/1/BestimmungsgemäßeVerwendung@ 0\mod_1183637706293_6.doc@ 5383

Proper use
DRYPOINT® RAX 600-5000 NA 11
3 Proper use
This dryer was designed, manufactured and tested to separate the moisture which normally exists in compressed air.
Any other use is considered improper.
The manufacturer shall not be liable for problems occurring as a consequence of improper use. The user alone is
responsible for any damage resulting from that.
Furthermore, the correct use includes the compliance with the installation instructions, in particular in respect of:
• The voltage and frequency of the main voltage supply.
• The pressure, temperature and flow rate of the inlet air.
• The pressure, temperature and cooling-water throughput (water-cooled).
• The ambient temperature.
When delivered, the dryer is tested and fully assembled. The customer only needs to connect the device to the system
in accordance with the instructions in the following chapters.
Pos:1 5 /Beko TechnischeDokumentation/Überschriften/1/Ausschlussvom Anwendungsbereich@ 0\mod_1236003439359_6.doc@13709
4 Exclusion from a field of application
Pos:1 6 /BekoTechnische Dokumentation/BestimmungsgemäßeVerwendung/BEKOMAT/AusschlußAnwendungBM 31/32/33 @ 0\mod_1236003837511_6.doc@ 13736
Note!
Improper use!
The device is intended for the separation of water in compressed air. The dried compressed air
cannot be used for breathing-air purposes and is not suitable for the direct contact with food.
This dryer is not suitable for the treatment of contaminated air or of air containing solids.

Operating instructions in accordance with the 97/23/EC Pressure Equipment Directive
12 DRYPOINT® RAX 600-5000 NA
5 Operating instructions in accordance with the 97/23/EC Pressure Equipment Directive
The DRYPOINT®RAX 600-5000 NA compressed-air refrigeration dryer contains pressure equipment in the sense of
the 97/23/EC Pressure Equipment Directive. Therefore, the entire plant needs to be registered with the supervisory
authority if required in accordance with the local regulations.
For the examination prior to the start-up and for periodic inspections, the national regulations need to be observed,
such as the industrial safety regulation in the Federal Republic of Germany. In countries outside the EU, the respective
regulations in force there need to be adhered to.
The proper use of pressure devices is the basic requirement for safe operation. As regards pressure devices, the
following points need to be observed:
•The DRYPOINT®RAX 600-5000 NA compressed-air refrigeration dryer must only be employed within the pressure
and temperature range limits indicated by the manufacturer on the name plate.
•No welding must be carried out on the pressure parts.
•The DRYPOINT®RAX 600-5000 NA compressed-air refrigeration dryer must neither be installed in insufficiently
ventilated rooms nor near heat sources or inflammable substances.
•To avoid fractures resulting from material fatigue, the refrigeration dryer should not be exposed to vibrations during
operation.
•The maximum operating pressure indicated by the manufacturer on the name plate must not be exceeded. It is the
installer's responsibility to install the appropriate safety and control devices. Prior to the start-up of the DRYPOINT®
RAX 600-5000 NA compressed-air refrigeration dryer, the connected pressure generator (compressor etc.) must
be set to the max. permissible operating pressure. The integrated safeguard needs to be checked by an approved
inspection agency.
•The documents related to the DRYPOINT®RAX 600-5000 NA compressed-air refrigeration dryer (manual,
operating instructions, manufacturer's declaration etc.) must be kept safe for future reference.
•No objects whatsoever must be installed at or placed on the DRYPOINT®RAX 600-5000 NA compressed-air
refrigeration dryer and the connecting lines.
•Installation of the plant in frost-free places only.
•Operation of the plant is only permissible with fully closed and intact housing and cover panels. Operation of the
plant with damaged housing/cover panels is prohibited.

Transport
DRYPOINT® RAX 600-5000 NA 13
6 Transport
Check the packaging for visible loss or damage. If no visible damage can be ascertained, place the unit in close
proximity to the place of installation and unpack the device.
During this procedure, the dryer must always remain in an upright position. The components may be damaged when
the unit is tilted or turned upside down.
Store the device in a dry environment and do not expose it to extreme weather conditions.
Handle with care. Strong shocks can cause irreparable damage.
7 Storage
SCC0001
Keep the device away from extreme weather conditions
even when packaged.
Keep the dryer in an upright position, also while it is
stored. Tilting the device or turning it upside down can
cause irreparable damage to some components.
When the dryer is not in use, it can be stored in its
packaging in a dust-free and protected place at a
temperature of up to max. 122°F (50°C),and at a specific
humidity of max. 90%. If the storage period exceeds 12
months, you should contact the manufacturer.
The packaging material is recyclable. Dispose of the material in accordance with the
directives and provisions in force in the country of destination

Installation
14 DRYPOINT® RAX 600-5000 NA
8 Installation
8.1 Place of installation
Note!
Ambient conditions!
In the event that the dryer is not installed under suitable ambient conditions, the ability of the device to
condense refrigerant gas is impaired. This can result in a higher load of the refrigerating compressor, and
in a loss of efficiency and performance of the dryer.
This in turn leads to overheated condenser fan motors, to malfunction of electric components and to a
breakdown of the dryer. Failures of this type will affect warranty considerations.
Do not install the dryer in an environment in which chemicals with a corrosive effect, explosive gases,
toxic gases, evaporation heat, high ambient temperatures or extreme dust and dirt can be found.
Minimum installation requirements:
• Choose an area which is clean and dry, free from dust and protected against atmospheric disturbances.
• The load-bearing zone must be even, horizontal and able to bear the weight of the dryer.
• Minimum ambient temperature +34°F (+1°C).
• Maximum ambient temperature +122°F (+50°C).
• Ensure a proper cooling air replacement.
• Allow a sufficient clearance on each side of the dryer for proper ventilation and to facilitate maintenance operations.
The dryer does not require attachment to the floor surface.
Do not obstruct the ventilation grille (not even partially).
Prevent any recirculation of the outgoing cooling air.
Protect the dryer against draughts.

Installation
DRYPOINT® RAX 600-5000 NA 15
8.2 Installation plan
2
2
1
IN
OUT
7
- A -
- B -
1
7
6
IN
OUT
5
9
8
9
4
9
3
9
9 9
3 4
9
9
8
6
5
1 Air compressor
2 Aftercooler
3 Condensate separator
4 Prefilter
5 Bypass group
6 Dryer
7 Compressed-air tank
8 Final filter
9 BEKOMAT condensate drain
Installation type A is recommended when the compressor functions with reduced step switching and when the total
consumption corresponds to the throughput rate of the compressor.
Installation type B is recommended when the air consumption constantly varies, with peak values which considerably
exceed the throughput rate of the compressor. The storage capacity of the tank must be dimensioned in such a way
that a possible short-term high air demand (peak air consumption) can be compensated.
Do not obstruct the ventilation grille (not even partially).
Prevent any recirculation of the outgoing cooling air.
Protect the dryer against draughts.
Note!
Contaminated intake air!
In the event that the intake air is strongly contaminated (ISO 8573.1 class 3.-3 or poorer quality), we
recommend the additional installation of a prefilter (e.g. CLEARPOINT F040), to avoid clogging of the
heat exchanger.

Installation
16 DRYPOINT® RAX 600-5000 NA
8.3 Correction factors
Correction factor for operating pressure changes:
Inlet air pressure psig 60 80 100 120 140 160 180 203
barg 4 5.5 7 8 10 11 12 14
Factor (F1) 0.79 0.91 1.00 1.07 1.13 1.18 1.23 1.27
Correction factor for ambient temperature changes (Air-Cooled):
Ambient temperature ºF 80 90 95 100 105 110 115 122
ºC 27 32 35 38 40 43 45 50
Factor (F2) 1.11 1.09 1.06 1.00 0.94 0.87 0.78 0.69
Correction factor for inlet air temperature changes:
Air temperature ºF 90 100 110 122 130 140 150 158
ºC 32 38 43 50 55 60 65 70
Factor (F3) 1.16 1.00 0.82 0.68 0.61 0.52 0.45 0.40
Correction factor for DewPoint changes:
DewPoint ºF 38 41 45 50
ºC 3 5 7 10
Factor (F4) 1.00 1.08 1.20 1.36
Calculation of the actual air throughput:
Actual air throughput = air throughput acc. to planning x factor (F1) x factor (F2) x factor (F3) x factor (F4)
Example:
The RAX 600 has a planned nominal capacity of 600 scfm (1019 m³/h). The highest achievable air mass
under the followin
g
operatin
g
conditions is:
−Air inlet pressure = 120 psig (8 barg)
−Ambient temperature = 115°F (45°C)
−Air inlet temperature = 122°F (50°C
−Pressure dew point = 50°F (10°C)
DFactor (F1) = 1.07
DFactor (F2) = 0.78
DFactor (F3) = 0.68
DFactor (F4) = 1.36
Every function parameter corresponds to a numerical factor which, multiplied by the planned nominal capacity,
determines the following:
Actual air throughput = 600 x 1.07 x 0.78 x 0.68 x 1.36 = 463 scfm (787 m³/h)
463 scfm is the maximum air mass of the dryer under the aforementioned operating conditions.
Selection of the best suitable model in accordance with the operating conditions:
Air throughput acc. to planning = Required air throughput
factor (F1) x factor (F2) x factor (F3) x factor (F4)
Example:
The following operating parameters are known:
−Required air mass = 750 scfm (1274 m3/h)
−Air inlet pressure = 120 psig (8 barg)
−Ambient temperature = 115°F (45°C)
−Air inlet temperature = 122°F (50°C)
−Pressure dew point = 50°F (10°C)
DFactor (F1) = 1.07
DFactor (F2) = 0.78
DFactor (F3) = 0.68
DFactor (F4) = 1.36
To find out the correct dryer version, the required air mass must be divided by the correction factors of the
parameters indicated above:
Air throughput acc. to planning= 750 = 972 scfm (1652 m³/h)
1.07 x 0.78 x 0.68 x 1.36
The suitable model for these requirements is DRYPOINT RA
X
1000 (with a specif. nominal capacity of 1000 scfm
[1698 m³/h]).

Installation
DRYPOINT® RAX 600-5000 NA 17
8.4 Connection to the compressed-air system
Danger!
Compressed air!
All works must only be carried out by qualified skilled personnel.
Never work on compressed-air systems which are under pressure.
The operator or the user must ensure that the dryer is never operated with a pressure exceeding the
maximum pressure value indicated on the name plate.
Exceeding the maximum operating pressure can be dangerous for the operator but also for the device.
The air temperature and the air flow at the inlet of the dryer must lie within the limit values indicated on the name plate.
The connecting lines must be free from dust, iron rust, shards and other contaminations and correspond to the flow
rate of the dryer. Should air with a very high temperature be treated, the installation of an aftercooler may be
necessary. For the implementation of maintenance works, the installation of a bypass system is recommended.
The dryer was designed in such a manner that vibrations that may occur during operation are limited. Therefore, it is
advisable to employ connecting lines (flexible hoses, vibration-inhibiting fittings etc.) which protect the dryer against
possible vibrations in the pipework.
Note!
Contaminated intake air!
In the event that the intake air is strongly contaminated (ISO 8573.1 class 3.-3) or poorer quality, we
recommend the additional installation of a prefilter (e.g. CLEARPOINT F040), to avoid clogging of the
heat exchanger.
===== Ende de r Stücklis te =====
8.5 Connection to the cooling-water network
Danger!
Compressed air and unqualified personnel!
All works must only be carried out by qualified skilled personnel.
Never work on compressed-air systems which are under pressure.
The user must ensure that the dryer is never operated with a pressure exceeding the nominal values.
Possible overpressure can be dangerous for the operator but also for the device.
The temperature and the amount of cooling water need to correspond to the limit values indicated on the name plate.
The cross-section of the connecting lines, which should preferably be flexible, must be free from dust, iron rust, shards
and other contaminations. We recommend employing connecting lines (flexible hoses, vibration-inhibiting fittings etc.)
which protect the dryer against possible vibrations in the pipework.
Note!
Contaminated intake wate
r
!
In the event that the intake water is strongly contaminated we recommend the additional installation of a
prefilter (500 micron), to avoid clogging of the heat exchanger.

Installation
18 DRYPOINT® RAX 600-5000 NA
8.6 Minimum cooling-water requirements:
Temperature 59…86°F (15…30°C) (1) HCO3 / SO4>1.0 mg/l or ppm
Pressure 44...145 psig (3…10 barg) (2) NH3 <2 mg/l or ppm
Delivery pressure > 44 psig (3 bar) (2) (3) Cl- 50 mg/l or ppm
Total hardness 6.0…15 dH° Cl2 0.5 mg/l or ppm
PH 7.5…9.0 H2S<0.05 mg/l or ppm
Conductivity 10…500 μS/cm CO2 <5 mg/l or ppm
Residual solids <30 mg/l or ppm NO3 <100 mg/l or ppm
Saturation mark SI -0.2 < 0 < 0.2 Fe <0.2 mg/l or ppm
HCO3 70…300 mg/l or ppm Al <0.2 mg/l or ppm
SO42- <70 mg/l or ppm Mn <0.1 mg/l or ppm
Note: (1) – Other temperatures upon request – check the data on the name plate.
(2) – Other pressures upon request – check the data on the name plate.
(3) – Pressure difference at the water connection of the dryer at maximum water flow.
Other delivery pressures upon request.
CAUTION!
During the piping of the dryer, the inlet and outlet connections need to be supported as is shown in the
illustration.
Non-observance will cause damage.

Installation
DRYPOINT® RAX 600-5000 NA 19
8.7 Electrical connections
Danger!
Supply voltage!
The connection to the electric mains should only be carried out by qualified skilled personnel and must
correspond to the legal provisions in force in your region.
Prior to connecting the device, please check the name plate to avoid exceeding the indicated values. The voltage
tolerance is +/- 10%.
The installer is responsible for supplying and installing the power cable. Be sure to provide the proper fuses or
breakers based on the data information located on the nameplate.
LGT0027
LGT0025
RAX 600-1250 RAX 1500-5000
The mains socket must be provided with a magnetothermal
differential circuit breaker (IΔn=0.03A) which is adjusted on
the basis of the dryer's consumption (see nominal values
on the name plate of the dryer). The cross-section of the
power supply cables must correspond to the consumption
of the dryer. In this respect, the ambient temperature, the
cable laying conditions, the length of the cables and the
requirements of the local electricity supplier need to be
considered.
LGT0028
L1 L2 L3 PE
QS
CAUTION!
Please observe the direction of rotation of the compressor!
In this system, the direction of rotation of the compressor is supervised by a reverse-phase
protector (RPP).
When this guard is triggered, the DMC24 goes into alarm mode (the alarm LED flashes and the
display of the DMC24 shows and ). In the event that the compressor does not run, the
direction of rotation must be changed by interchanging two phases. These modifications must only be
carried out by a qualified electrician.
Do not by-pass the RPP protector: If the device is operated with the incorrect direction of
rotation, the compressor will fail immediately. This will void the guarantee.

Start-up
20 DRYPOINT® RAX 600-5000 NA
Danger!
Supply voltage and missing earth connection!
Important: ensure that the plant is connected to earth.
Do not use plug adapters at the power plug.
Possible replacement of the power plug must only be carried out by a qualified electrician.
8.8 Condensate drain
Danger!
Compressed air and condensate under pressure!
The condensate is discharged at system pressure.
The drain pipe needs to be secured.
Never direct the condensate drain pipe at persons.
The dryer is delivered with an already integrated electronically level-controlled BEKOMAT condensate drain. Connect
the condensate drain with a collection system or container by properly screwing it on.
Do not connect the drain with pressure plants.
Do not discharge the condensate into the environment.
The condensate accumulating in the dryer contains oil particles which were released into the air by the
compressor.
Dispose of the condensate in accordance with the local provisions.
It is advisable to install a water-oil separator, to which the total amount of condensate from the
compressors, dryers, tanks, filters etc. is supplied.
We recommend ÖWAMAT oil-water separators for dispersed compressor condensate and BEKOSPLIT
emulsion-splitting plants for emulsified condensate.
9 Start-up
9.1 Preliminary stages
Note!
Exceeding of the operating parameters!
Ensure that the operating parameters comply with the nominal values indicated on the name plate of the
dryer (voltage, frequency, air pressure, air temperature, ambient temperature etc.).
Prior to delivery, this dryer was thoroughly tested, packed and checked. Please verify the soundness of the dryer
during the initial start-up and check the perfect functioning during the first operating hours.
The initial start-up must be carried out by qualified personnel.
During the installation and operation of this device, all national regulations regarding electronics and
any other federal and state ordinances, as well as local provisions, need to be adhered to.
The operator and the user must ensure that the dryer is not operated without panels.
Table of contents
Other Beko Dryer manuals

Beko
Beko DE 8433 RXO User manual

Beko
Beko VH8735GA01 User manual

Beko
Beko DV 7120 User manual

Beko
Beko DRVT 61 W User manual

Beko
Beko DS7534RX3 User manual

Beko
Beko DRXS827A User manual

Beko
Beko DE 8433 GA0W User manual

Beko
Beko B3T4923D User manual

Beko
Beko DRYPOINT RS 700-3500 HP45 NA User guide

Beko
Beko DPU 7360 X User manual