INTRODUCTION
1.1BasicInformation
TheinstructionsinthismanualapplytoModelVRC‐3gas‐fired/fan‐assistedwarmairheaters.These
modelshaveanaxialfanforairdelivery.Theseheatersaredesignedforoverheadsuspensionandare
suitableforindoorinstallationonlyinstalledatanoperationambienttemperaturebetween‐15°Cand
45°C.WheninstalledasatypeC12/C32andwheretheheightabovefloorlevelisgreaterthan1,8metres
measuredtotheundersideoftheappliancetheymaybeusedasagarageairheater.Thisappliancemust
beinstalledinaccordancewiththerulesinforce.
Beforeinstallation,checkthatthelocaldistributionconditions,natureofgasandpressureand
adjustmentoftheappliancearecompatible.Apermanentelectricitysupplyof230volts,50Hz,single
phaseisrequired.
Heatersareapprovedfor: TypeC12‐horizontalventforbalanced‐flueheaters;
TypeC32‐verticalventforbalanced‐flueheaters;
TypeB22‐verticalvent;
CategoryII2H3+forGBandIE
Whentheexternalcontrolcallsforheat,anelectroniccontrolbeginstheignitionsequencetoprovideforasafe
start.About30secondsafterthecallforheat,thefanwillbegincirculatingwarmair.Theelectroniccontrolwill
supervisetheflameduringtheentireheatingcycletoensuresafeoperation.Whentherequiredroom
temperatureisreached,themainburnerwillshutdownleavingthefanrunningtocooldowntheheat
exchanger.Afterapproximately45seconds,thefandelayrelaywillturnoffthefan.
1.2Warranty
Warrantyisvoidif:
TECHNICALDATA
2.1Specifications
Table1
20 30 45 60 75 100
Gas category
Comb. Air & Flue Type B (1)
Comb. Air & Flue Type C (1)
Connection colars mm 100 100 130 130 130 130
Heat inputs Hs kW 26,42 31,63 54,38 73,25 87,85 114,87
Heat inputs Hi kW 23,80 28,50 49,00 66,00 79,15 103,50
Heat output kW 21,82 25,99 44,64 60,92 73,13 94,50
Thermal efficiency % 91,70 91,20 91,10 92,30 92,39 91,30
Gas consumption G20 m3/h 2,52 3,02 5,19 6,98 8,38 11,19
Gas consumption G31 kg/h 1,86 2,22 3,82 5,15 6,17 8,24
Gas pipe connection (2) inch
ESP MIN Press Pa 50 50 50 100 150 100
ESP MAX Press Pa 200 300 200 200 350 300
Air flow measured m3/h 2248 2741 4023 5573 7079 8068
Temperature rise (3) K 28 28 32 32 30 34
Electrical service (protection IP20) 400V 3P
50Hz
Blower electrical rating W 660 1250 1410 1700 3070 3200
Total electrical rating W 770 1370 1530 1810 3180 3320
Blower Weight kg 14,5 20,5 27 26 41 45
Unit Weight kg 54 55,8 87 99 109 155
Total Weight kg 68,5 76,3 114 125 150 200
230/240V 1N 50Hz 230/240V 1N 50Hz
VRC-3 II2H3+
B22P
C12, C32, C42, C82
½" ¾"
a) VRC-3 heaters are installed in atmospheres containing flammable vapors or
atmospheres containing chlorinated or halogenated hydrocarbons or atmospheres
containing any silicone, aluminum oxide, etc., that adheres to spark ignition flame
sensing probes.
b) The installation is not in accordance with these instructions.
1
2
(1) Gas appliance Classifications for approved venting methods based on CEN report CR 1749:2001.
(2) There is a difference between the gas connection diameter and the diameter of the supply line. Always use the most adequate diameter of the supply line
to minimize the pressure drop through the gas pipes – if necessary, reduce the diameter of the supply line at the inlet of the unit.
Figure for isothermal conditions.