bioxX bx-ESG User manual

Installation and
Operating Manual of
Keep these installation instructions in safe place in the vicinity of the
control unit. When maintenance or repair work is required, it is very
important that these instructions are available.
with concealed power valve
bx-ESG

1. INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
1.2 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
1.3 Warranty and adhesion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2. ITEM CHECK LIST. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
3. TECHNICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.1 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
3.2 Cable Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.3 Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
3.4 Wiring for Power Supply (in-wall) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
4. INITIAL SETUP . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
4.1 Assembly instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
4.2 Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
5. OPPERATION MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
5.1 Adjustable Values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
6. KEYBOARD / DISPLAY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
6.1 Adjustmens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
7. OPTIONAL ACCESSORIES .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Notes / Contact data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
2
Warning!
Opening the internal equipment terminal box and
the connection to electricity mains, may only be
done by an authorized electrical specialist!

Airing of buildings are becoming ever more important due to the continued improvement of
airtight building envelopes. The consequence of this energy-saving building method is that the
air humidity, which is formed in the day to day use of a room can no longer escape suciently.
Dampness can thus form and cause damage, at worst resulting in mould and fungi growth,
which deteriorates air quality and can become a health hazard.
For the dehumidifying of buildings, ventilation systems of dierent types and performance
levels are used. Temperature and humidity sensors compare the internal and external
temperatures and humidity. A Controller compares these values.
At higher humidity in the building, using a load relay, a ventilation system is switched on.
The ventilation is only switched on if the humidity outside is less than inside, thus making the
drying process of the area possible.
The bioxX dehumidifying controller bx-ESG can be used in both home and the commercial
sector. Ensure that dampness due to defective construction parts, gutters, roofs etc.
is avoided; this can be achieved by routine repairs. The bx-ESG can also be used for
temperature control of cellars, restaurants, oces and dwellings (minimum and maximum
temperature).
Home/Oce
• Ventilating of rooms with high air humidity (e.g. Laundry rooms)
• Dehumidifying of dampness due to dense construction cover
• Dehumidifying of condensation on walls, oors and construction units that don’t t ush.
• Basic ventilation for humidity purposes (living spaces)
Commercial Sector
Additionally the dehumidifying controller can be used to operate industrial aerators and
ventilation systems up to an output of 1800 W humidity.
1.3 Warranty and Adhesion
bioxX system GmbH oers a two years warranty on factory defects and components of the
controller.
Repairs and maintenance should only be done by professionals.
• Inappropriate handling, maintenance or repair is done on it.
• After the installation changes are made to the system by a non-professional
3

• 1 x operating instructions
• 1 x dehumidifying controller
• 2 x temperature/dampness sensors
• 2 x sensor cables 10 m
• 4 x expansion anchors 6 mm (sensor)
• 4 x assembly screws (sensor)
• 4 x expansion anchors 6 mm (housings)
• 4 x assembly screws (housings)
• 1 x plug
• optional: 1 x interior sensor
• optional: 1 x sensor cable 10 m
• optional: 1 x coupler module
4
• 1 x operating instructions
• 1 x dehumidifying controller
• 2 x temperature/dampness sensors
• 2 x sensor cables 10 m
• 4 x expansion anchors 6 mm (sensor)
• 4 x assembly screws (sensor)
• 4 x expansion anchors 6 mm (housings)
• 4 x assembly screws (housings)
• 1 x power supply (in-wall)
• optional: 1 x interior sensor
• optional: 1 x sensor cable 10 mste
• optional: 1 x coupler module
Electrical connection 220 -240 ~ (power supply unit)
Power consumption (ESG + mains adaptor) <10 W
External connection (oating contact) Max. 1800 W
Protection class Protection class 2
Frost protection (adjustable) ON/OFF (standard ON)
Frost protection temperature (adjustable) 0 – 15 °C (standard 5 °C)
Active period (adjustable) 0 – 60 minutes (standard 10 minutes)
Inactive period (adjustable) 0 – 60 minutes (standard 10 minutes)
Switching dierence (indoors/outdoors) 0.5 g/m³
Operation hours from (adjustable) 0:00 - 23:30 hours
Operation hours to (adjustable) 0:00 - 23:30 hours
Minimum air humidity (adjustable) 0 – 100%
Maximum temperature (adjustable) 0 - 40°C
Temperature/Humidity Sensor bx-ESG-TF
Response time 8 seconds
Energy consumption 3.2µW (at 8 bit, 1 metering / s)
Measuring range: relative humidity 0 - 100%
Measuring range: temperature - 40 to 125 °C
Humidity tolerance 2%
Temperature tolerance 0.3 °C
Dimensions (H x L x W) 40 x 64 x 24 mm
Distance between drilled holes 18 mm

3.1 Dimensions
Back View (Drilling Measurements) Right Side View
Front View
5

3.3 Diagrams
6
Unterputznetzteil
indoor sensor 1
indoor sensor 2 outdoor sensor
Network Power 9V DC
outdoor sensor
indoor sensor
outdoor sensor
indoor sensor
plug power supply (in-wall)

3.4 Wiring for Power Supply (in-wall)l
Warning!
When connecting the Power Supply to the controller, the polarity needs to be considered!
7

4. Initial Setup
Test the functionality by rst plugging the sensors into the power supply, before beginning the
complete assembly.
The controller is to be attached to a dry wall where it is well accessible and close to a wall
socket.
The external sensor must be rain-protected and above the splash-water range (50 cm),
preferably at the north side.
Direct sun exposure misrepresents the result of measurement due to heating.
The interior sensor must be attached in the area with the largest humidity load. This also
applies to the optional 2nd interior sensor.
When using the bx-ESG as temperature control the interior sensor must be in the area with
the largest thermal load (e.g. to attach within the upper part of the room).
4.2 Assembly
• Mark the wall where holes should be drilled
• Drill and insert expansion anchors
• Turn provided screws into the two upper holes and let the screws stand out 3 mm
• Hang the controller on the screws
• Loosen the two lower screws on the housings, which removes the lower cover to open
the housing
• Turn the bottom two screws in to x the housing to the wall
• Connect the potential-free contact (as a rule the live wire) to the lustre terminal
(see connection diagram)
• Pull the live wire from the lustre terminal to the air ventilation system
• Attach Sensor cables
• Raise the cover cap on the sensor to open it
• Fasten the sensors with the enclosed expansion anchors and screws
• Fasten the sensor cables
• Input the cables into the sensor and close the cap
• Plug in power supply
• Press the red button with the gears on it on the controller to get to the basic installation
• Exit the basic installation menu by pressing the red button with the gears on again
8

The controller can be used in two operation modes;
-
-
These modes of operation can be changed in the Installation Menu under “base adjustments “.
A seasonal change of the mode of operation is problem-free (e.g. Winter garden).
This can be done in the “Base Menu”, to get there you need to press the red button with the
gears symbol
• Date and Time
• Opperation Mode
• Running Time
• Pause Time
• Running Time (From on-time to o-time)
• Minimum Dampness Inside
• Freeze Protection Mode (on/o)
• Freeze Protection Temperature
• Switching Limit Inside/outside
• Upper Temperature Threshold (Temperature Control)
• Forced Ventilation
Die keypad consists of;
• Up, down, left and right arrow keys (blue)
• OK-Button (green)
• Basic-Settings-Button (red)
The 4-line LED display, shows all necessary data.
The displayed value is the actual current set value.
After you have changed/set the values to your requirement, you can continue scrolling through
the menu displays.
9
temperature
inside: 21,8 °C
outside: 14,3 °C
fan: active
parameter
frost protection
state: ON
Temp. min.: 5°C

settings
date/ time Set the current date and time
factory reset abort
reset
Sprache / language set your language
operating mode humidity control
temperature control
test run ventilation active / ventilation not active
Press the OK-button to start/ stop.
forced ventilation Set the timeframe for forced ventilation
absolute humidity inside
outside
fan state
temperature inside
outside
relative humidity inside
outside
date / time current date and time
parameter
frost protection ON/ OFF
minimum temperature
relative humidity minimum value
absolute humidity dierence
(inside to outside)
dierence value to start the vantilation
run/ pause time run time
pause time
ventilation active run time from ...
run time to ...
10
temperature inside
outside
relative humidity inside
outside
date / time current date and time
parameter
temperature minimum temperature
maximum tempareture
ventilation active run time from ...
run time to ...

Additional indoor sensor
Product No:
Sensor cable
Product No:
Coupling module
Product No:
In order to extend the sensor
wire by 10 m, a coupling module
for connection with the cable is
necessary.
11

QR Code
bx-ESG
bioxX systems GmbH
CEO: Karsten Butze
Dresdner Str. 172, 01705 Freital
Mobil: +49(0) 178 / 77 303 77
Tel.: +49(0) 351 / 212 936 52
Fax: +49(0) 351 / 418 867 549
www.bioxx-system.de
12
V 2.8.1
This manual suits for next models
3
Table of contents
Popular Control Unit manuals by other brands

Kontron
Kontron CU 5 -2 Series user guide

Knorr-Bremse
Knorr-Bremse BENDIX TIM G2 user manual

Lutz-Jesco
Lutz-Jesco ChlorStop operating instructions

M-system
M-system R7ML-DC16D instruction manual

Emerson
Emerson Varec 5010 Series Installation, operation and maintanance instructions

4qd
4qd SCC-001 instruction manual