Bodine BSL10T3 User manual

SAVE THESE INSTRUCTIONS
THIS PRODUCT CONTAINS A RECHARGEABLE LITHIUM-ION BATTERY.
THE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY.
Bodine © 2022 Signify Holding. All rights reserved.
Collierville, TN USA 38017 • Tech Support 888-263-4638 • www.bodine.com
442295716651
BSL10T3/BSL06T3
8/19/22
Li - ion
Self-Testing Emergency LED Driver
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
! IMPORTANT SAFEGUARDS ! WHEN USING ELECTRICAL EQUIPMENT, BASIC
SAFETY PRECAUTIONS SHOULD ALWAYS BE
FOLLOWED, INCLUDING THE FOLLOWING:
1. This product is for use with an emergency LED lighting load and supplies nominally 10.0 W/6.0 W
(depending on model) of power, with a voltage of 15-54 VDC in emergency mode for a minimum of 90
minutes, in compliance with NFPA 101 and NEC 700.12.
2. Make sure all connections are in accordance with the National Electrical Code or Canadian Electrical
Code and any local regulations.
3. To reduce the risk of electric shock, disconnect both normal and emergency power supplies before
servicing. Follow the instructions in the OPERATION section to disable the output of this LED driver.
4. This emergency driver is suitable for both factory or field installation.
5. This product is suitable for use in damp locations where the ambient temperature is 0ºC minimum,
+55ºC maximum. Product is also suitable for installation in sealed and gasketed fixtures. Product is
not suitable for heated air outlets and wet or hazardous locations. Maximum allowable case temp is
65ºC. See unit label for Tc measurement location.
6. An unswitched AC power source is required (120-277 VAC, 50/60 Hz).
7. Do not install near gas or electric heaters.
8. Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not field
replaceable. Contact the manufacturer for information on service.
9. The use of accessory equipment not recommended by the manufacturer may cause an unsafe
condition.
10. Do not use this product for other than intended use.
11. Servicing should be performed by qualified service personnel.
12. Equipment should be mounted in locations and at heights where it will not be subjected to tampering
by unauthorized personnel.
13. For Canadian application the output terminals should be in compliance with the accessibility
requirement of the Canadian Electric Code.
14. This device complies with part 15 of the FCC Rules. Operation is subject to the following two
conditions: (1) this device may not cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause undesired operation.
15. This product must be grounded. See the wiring diagrams for details.
Installation Instructions

INSTALL ATION
22
STEP 1 - DETERMINE SUITABILITY
> Disconnect AC power from the LED luminaire.
> Mount the emergency LED driver by the mounting tabs using the supplied screws. The
luminaire’s installation
instructions may provide guidance on the recommended mounting location.
>Mounting Height: Many factors influence emergency illumination levels, such as the lamp
load selected, luminaire design, and environmental factors therefore end use verification is
necessary. For field installations, when the attached luminaire is mounted at heights greater
than 7.17ft (2.2m), the level of illumination must be measured in the end application to ensure
the requirements of NFPA 101 and local codes are satisfied.
>Remote Mounting: The emergency LED driver may be remote mounted from the luminaire it
enclosed and installed in accordance with the NEC. If used in conjunction with an AC driver the
allowed distance is up to half the distance the AC driver manufacturer recommends remote
mounting the AC driver from the LED load. If used without an AC driver, and remote mounting
more than 5 feet from the luminaire, please consult the factory to determine the necessary
wire gauge. CAUTION: Remote mounting can result in reduced power output.
1. Ensure the LED load’s rated power is greater than or equal to the power output of this emergency LED
driver. This is to ensure that this emergency product will not produce more power than the LED load can
handle, thus ensuring that the LED load will not be damaged when the system is in the emergency mode.
2. Verify that the forward voltage of the luminaire’s LED array is within the limits of this emergency LED driver.
The forward voltage of the LED array is commonly designated as Vf and should be found on the luminaire
markings, in the luminaire specifications, or imprinted directly on the LED arrays. If multiple LED arrays are to
be driven, verify that the total forward voltage is within the limits of this product. Using a voltage meter, it
may be possible to directly measure the voltage across the LED arrays when operating from the AC driver.
3. Ensure the output current of the AC LED driver does not exceed 3.0 Amps. This is the current into the blue
wire connector.
4. Ensure there will be sufficient light output in the end application. Estimate the egress lighting illumination
levels by doing the following:
A. Find the efficacy of the LED load. This can be given by the luminaire manufacture. This number will be
given in lumens per watt (lm/w). It is the installer’s responsibility to validate the luminaire manufacturer’s
efficacy data.This can be accomplished by direct measurement, by review of independent 3rd party test
data (UL, ETL, etc.), accessing a public database of 3rd party data (such as Design Lights Consortium,
www.designlights.org), or other comparable means.
B. Lumens can be calculated by multiplying the output power of the emergency LED driver by the efficacy
of the LED load. In many cases the actual lumen output in emergency mode will be greater than this
calculation gives, however it will provide a good estimate for beginning the lighting design of the system.
Lumens In Emergency Mode = Lumens per Watt of Fixture * Output Power of Chosen Product
(Lumens) = (lm/W) * (W)
C. Using the results of this calculation and industry standard lighting design tools, calculate the
anticipated illumination levels in the path of egress.
This product is suitable for field installation with suitable LED loads including LED luminaires, DC voltage
driven LED replacements for fluorescent lamps and others. There are four (4) checks to determine if
your luminaire is eligible for field installation.
NOTE: This product has been designed to reliably interface with a wide selection of LED loads and is electrically
compatible with every simple LED array that meets criteria 1 and 2 above. However, compatibility cannot be
guaranteed with all current and future LED systems. Compatibility testing of the end-use system is suggested.
Please contact the factory with any questions.
NOTE: After installation, it will be necessary to measure the egress lighting illumination levels to ensure it
complies with national, state, and local code requirements.
Make sure the necessary branch circuit wiring is available. An unswitched source of power is
required. The emergency driver must be fed from the same branch circuit as the AC driver.
Installation of this emergency LED driver will vary based on the luminaire type, however,
generally follow these steps:
STEP 2 - INSTALLING THE EMERGENCY DRIVER

OPERATION
3
STEP 3 - INSTALLING THE ILLUMINATED TEST SWITCH
> See wiring diagram to connect the emergency driver to the AC driver and LED load. Make sure all
connections are in accordance with the National Electrical Code and any local regulations.
> After installation is complete, supply AC power to the emergency driver and the AC driver.
> At this point, the Charging Indicator Light should illuminate indicating the internal battery is charging.
> After the emergency driver has been charged for one-hour automatic commission test will be
performed. The emergency driver will switch to the emergency mode for 30 seconds and store in its
memory the current level of the connected load. If, during future self-test, this level deviates by more
than 25%, an error will be triggered.
> A short-term discharge test may be conducted after the emergency driver has been charged for one
hour. Charge for 24 hours before conducting a long-term discharge test. Refer to OPERATION.
> In a readily visible location, attach the label "CAUTION - This Unit Has More Than One Power
Connection Point. To Reduce The Risk Of Electric Shock, Disconnect Both The Branch Circuit-
Breakers Or Fuses And Emergency Power Supplies Before Servicing."
> Mount the supplied Illuminated test switch in a location that is visible
and accessible by maintenance personnel. The test switch mounts
through a ½” hole which may need to be made in the luminaire or
could come pre-punched by the luminaire supplier.
> Connect the test switch per wiring diagrams provided on these
instructions.
> If wired correctly, the indicator light should be ON when AC power
is supplied to the fixture indicating that the unit is charging. After
installing, mark with the "PUSH TO TEST" and "CHARGING INDICATOR
LIGHT" labels.
STEP 4 - WIRING THE EMERGENCY DRIVER
Fixture or
Test/Monitor Plate
2 Wire Illuminated
Test Switch
Hex Nut
Red
Black
When AC power fails, the emergency driver automatically switches to emergency mode, powering
the LED load per the rating of the emergency driver for a minimum of 90 minutes. When AC power is
restored, the emergency driver returns to charging mode.
ABConnect:
Applying AC power to the unit activates the charger circuit, and supplies power to the control/monitor
circuit and charging indicator light.
To deactivate the unit for storage or shipping, press and hold the test button while the unit is in
emergency mode until the LED load is turned off.
Self-Test:
This unit contains a control/monitor circuit that if enabled automatically performs a 30-second discharge
test once a month and a full 90-minute discharge test once a year. During routine testing, the self-testing
emergency driver simulates an AC power failure causing the unit to automatically switch to emergency
mode. The unit will monitor the operation of the LED load, battery voltage, and emergency duration. If the
emergency system functions properly, then the unit will return to normal mode. Should the unit detect any
problems, the indicator light will flash per failure condition (see Troubleshooting Guide) until the condition
has been corrected and the unit passes the next test.
Commissioning: After the emergency driver has been charged for one-hour an automatic
commissioning test will be performed. The emergency driver will switch to the emergency mode for 30
seconds and store in its memory the current level of the connected load. If, during future self-test, this
level deviates by more than 25%, an error will be triggered.
Caution:Once commissioned, connecting this equipment to higher voltage loads will result in reduce
current levels triggering the derangement signal indicating the equipment requires re-calibration to ensure
proper operation.

4
MAINTENANCE
This self testing emergency driver automatically performs required routine testing. Results are
reported to maintenance personnel via the indicator light.
Note: Maintenance personnel should periodically check the indicator light. If the indicator light is
flashing, follow steps in the Troubleshooting Guide.
TROUBLESHOOTING GUIDE
Bi-Color indicator
(color/flashing) ERROR CORRECTIVE ACTION
Green/ No Flashes None The unit is operating correctly, and the internal battery is fully charged
Green/ Slow Flashes None
1. The Unit is charging. The main light is operating normal.
2. The Unit is running a self-diagnostic test. The LED Load is operating in
Emergency level.
OFF None In Emergency mode, or emergency run-time is ended and unit is de-activated.
Red / 2x Flashes Battery
Indicates that a self-test/self-diagnostic test did not meet full duration
1. Charge the unit for the rated recharge time and perform a manual self-
diagnostic test.
2. If error is still present, then the battery is past it's useful life and should be
replaced.
Red / 3x Flashes Charging
1. Check input AC mains wiring of Unswitched Hot, Neutral and Ground.
2. Verify Voltage and Frequency are stable and match the product's input rat-
ing on the label
Red / 4x Flashes LED Load,
Commissioning
During a self-test/self-diagnostic test, the unit detected the LED load has
changed more than 25% from the initial commissioned value.
1. Replace the LED Load and perform a manual self-diagnostic.
2. If error is still present, then recalibrate the commission value by deactivating
the unit. Apply AC mains to activate unit and it will recommission itself after
one h o ur.
3. Check for Open or Short circuit on the output connections.
Red / 5x Flashes Temperature
Product temperature is beyond its rated temperature range.
1. Ensure unit is within the rated temperature range stated on the product
label.
2. Confirm by measuring at the Tc point on the product label.
If the unit has encountered a problem after installation, then the Illuminated Test Switch will flash the error code
with the indicator light. Count the number of times the indicator is OFF to read the number of flashes. Then use
the troubleshooting steps to solve the issue.
To reset a failure indication, briefly push the Test Switch. If the condition has not been corrected by the
next scheduled test, the unit will once again detect the failure and signal the failure indicator.
To perform a manual self-diagnostic test, push and hold the Test Switch for minimum of 5 seconds. Once
test switch is released the emergency driver will perform a 30 second diagnostic test. During this test, unit
will monitor the operation of the LED load, and battery voltage. If the emergency system functions properly,
the unit will return to normal mode. Should the unit detect any problems, the indicator light will flash per
failure condition (see Troubleshooting Guide) until the condition has been corrected and the unit passes the
next test.
Self-test select feature:
Switch Position Function
ON Self-test feature Enabled
1 Self-test feature Disabled
A slide switch is used to enable and disable the self-test feature of the product.

AC Driver
Ground
Neutral
Line
LED -
LED +
Unswitched Line
Neutral
Ground
Wall Switch Bodine EM Driver
Line
Neutral
Ground
Driver In +
Driver In -
LED Load +
LED Load -
Test Switch +
Test Switch -
LED LOAD
ON
BLACK
RED
UL Class 2 Circuits
WIRING DIAGRAMS
NOTE: Emergency driver case and green connector must be grounded
EMERGENCY DRIVER AND AC DRIVER MUST BE FED FROM THE SAME BRANCH CIRCUIT
TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER DRIVERS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS.
NOTE 1: For short-term testing of the emergency function, the battery must be charged for at least one hour. The emergency driver must be
charged for at least 24 hours before conducting a long-term test.
This manual suits for next models
1
Table of contents
Other Bodine DC Drive manuals