Boutronic JGA2011 User manual

Manual Current relay print JGA2011 Boutronic B.V.
Boutronic B.V. Page - 1 - ’s-Gravenzande The Netherlands
Intro
The current relay JGA2011 is a universal control unit for
sensing 2 4 … 20 mA signals to 2 relay outputs.
.
Liability and warranty
Every JGA2011 is checked before sending for correct operation.
Therefore Boutronic has a warranty period of 1 year.
The warranty expires if:
-The defect is caused by gross negligence or by improper installation
-Repairs and/or modifications to the JGA2011 without permission from Boutronic.
Boutronic is in no way liable for damage caused as a direct or indirect consequence by the use of the
JGA2011.
Manual JGA2011
December 2020
www.boutronic.nl

Manual Current relay print JGA2011 Boutronic B.V.
Boutronic B.V. Page - 2 - ’s-Gravenzande The Netherlands
Menu
Intro ................................................................................................................................. 1
Liability and warranty....................................................................................................... 1
Menu................................................................................................................................ 2
Connections...................................................................................................................... 3
Connection example............................................................................................................................ 4
Operation............................................................................................................................................. 4
Current inputs...................................................................................................................................... 4
Potentiometer ..................................................................................................................................... 5
Relay .................................................................................................................................................... 5
Switching delay Relay .......................................................................................................................... 5
Change settings ................................................................................................................ 6
Potentiometer.................................................................................................................. 6
DIP-switches..................................................................................................................... 6
Setting with the serial menu ............................................................................................. 6
Relay 1.............................................................................................................................................. 7
Relay 2.............................................................................................................................................. 7
Debug level....................................................................................................................................... 7
Factory defaults................................................................................................................................ 7
Factory test ...................................................................................................................................... 7
Technical specifications..................................................................................................... 8
General ................................................................................................................................................ 8
Power................................................................................................................................................... 8
Inputs................................................................................................................................................... 8
Current input.................................................................................................................................... 8
Outputs................................................................................................................................................ 8
Relay................................................................................................................................................. 8
Measurements ................................................................................................................. 9

Manual Current relay print JGA2011 Boutronic B.V.
Boutronic B.V. Page - 3 - ’s-Gravenzande The Netherlands
Connections
The figure below shows schematically the JGA2011:
4: Firmware poort
2: LED
3: Potentionmeters
1
ON
2 3 4
L1 L2
P1
5: Dipswitches
6: Connections 1 to 6
1: Connections 7 to 12
35,0 mm
25,0 mm 7,5 mm
Top hat rail IEC/EN 60715
DIP 1...4
7
8
9
10
11
12
1
2
3
4
5
6
CON TRO L
Po wer sup pl y
w ww. bout roni c.nl
GN D
+24VDC IN
Type nummer JGA2011
+24VDC O UT
4-2 0m A in 2
GN D
Input s 4-20m A
RoHS compliant
T A : 0 . .. 70 C
Re lay 1
Re lay 2
4-2 0m A in 1
Re lay cont acts : 24 VAC/DC m ax 100 0mA
: 24VDC 5 0 mA
: R-loa d =500 Ohm
7 8 9 10 11 12
1 2 3 4 5 6
Ro HS compl ia ntT yp e J GA20 11
GND
4-2 0m A I N2
Relay2
GND
4-2 0m A I N1
Relay1
+ 24 VD C IN
+ 24 VD C OU T
www.boutronic.nl
Made in the N etherlands
Li ft f ron t here fo r ac ces s cont rol P2
Nr
Unit
Description
1
Connection 7 … 12
Connection 7 … 12, see front for type of connections
3
LED
These LEDs indicate whether the value of the corresponding input is above
or below the switching threshold. The burning time of the LED corresponds
to the set delay (default 1 sec). After this time, the relay switches.
2
Potentiometer
Potentiometer for setting the switching threshold of the relays
P1: Relay 1
P2: Relay 2
When DIP-switch 3 is ON, a software delay is used.
4
Firmware port
Connection to PCB (with a Boutronic dongle) for firmware update
or programming settings
5
DIP-switches
DIP-switch 1: reserved
DIP-switch 2: reserved
DIP-switch 3: Time with potentiometer or software
DIP-switch 4: reserved
See chapter change settings
6
Connection 1 … 6
Connection 1 … 6, see front for type of connections

Manual Current relay print JGA2011 Boutronic B.V.
Boutronic B.V. Page - 4 - ’s-Gravenzande The Netherlands
Connection example
A connection example is given in the image below.
+24 VDC
GND
GND
Power in
Currentrelay
7 8 9 10 11 12
1 2 3 4 5 6
Ro HS co mpl ia nt
Type JGA2011
GND
4-2 0m A I N2
Relay 2
GND
4-2 0m A I N1
Relay 1
+24VD C IN
+24VD C OUT
www.boutronic.nl
Made in the N ethe rlands
Li ft front here for acces s control
Sensor or signal 1
Sensor or signal 2
Operation
The image below simply shows how the JGA2011 works.
Relais 1
4...20 mA Current in 1
4...20mA
GND
Level
0...100%
4mA = 0%
20mA = 100%
DIP 3 = OFF
DIP 3 = ON Software level
0...100%
Delay on = 1 sec
Delay off = 1 sec
Hystereis = 1%
Delay on = 1...600 sec
Delay off = 1...600 sec
Hystersis = 1...10%
Relais 2
4...20 mA Current in 2
4...20mA
GND
Level
0...100%
4mA = 0%
20mA = 100%
DIP 3 = OFF
DIP 3 = ON Software level
0...100%
Delay on = 1 sec
Delay off = 1 sec
Hystereis = 1%
Delay on = 1...600 sec
Delay off = 1...600 sec
Hystersis = 1...10%
GND
R = 500E
R = 500E
Current inputs
A signal of 4… 20 mA is applied to the current inputs. This signal is read in and converted to a 0% to
… 100% value.
If the current input is lower or equal than 4 mA, the JGA2011 will convert the value to 0%, if the
current input is higher or equal than 20 mA, the JGA2011 will convert the value to 100%.
Note: The maximum current that may be offered is: 30 mA.

Manual Current relay print JGA2011 Boutronic B.V.
Boutronic B.V. Page - 5 - ’s-Gravenzande The Netherlands
Potentiometer
The signal from the potentiometer is read in and converted to a 0 … 100% value.
If DIP-switch 3 is OFF, this value is compared with the value of the current input. If the current input
value is higher than the set value (switching threshold), the relay will be switched on. If the current
input value is lower than the set value, the Relay will be disabled.
Example: If the current input measures a signal of 12 mA, this current is converted to a value of 50%.
When the potentiometer is set to 40%, the relay will switch on. When the potentiometer is set to
60%, the relay remains switched off.
When DIP-switch 3 is ON, the set values are used as levels.
If the potentiometer is turned all the way to the left, the switching threshold is minimal. If the
potentiometer is turned all the way to the right, the switching threshold is maximum.
Relay
The relay switches when the corresponding input exceeds the switching threshold. Input 1 switches
relay 1 and input 2 switches relay 2.
Switching delay Relay
The switching delay with which the relay is switched with respect to the input is set to 1 second by
default. If DIP-switch 3 is ON, this time can be set for each relay separately. This time can only be set
through the USB port of the PC in combination with the Boutronic USB dongle
The operation of the switching threshold and the switching delay is schematically shown in the figure
Below:
ON
OFF
Relay 1
100%
75%
50%
25%
0%
Switching thresshold 1
20 mA
16 mA
12 mA
8 mA
4 mA
Current input 1
Time
Relay 1: Switchdelay ON/OFF = 1sec
Hysteresis = 1%
Switch threshold = 50%
ON
OFF
100%
75%
50%
25%
0%
20 mA
16 mA
12 mA
8 mA
4 mA
Relay 1: Switchdelay ON/OFF = 2 sec
Hysteresis = 1%
Switch threshold=25%
ON
OFF
100%
75%
50%
25%
0%
20 mA
16 mA
12 mA
8 mA
4 mA
Relais 1: Switchdelay ON/OFF =10 sec
Hysteresis = 1%
Switch threshold=75%
5sec 5sec 5sec
Relay 1
Switching thresshold 1
Current input 1
Relay 1
Switching thresshold 1
Current input 1
Time
Time
Time
Time
Time
Time
Time
Time

Manual Current relay print JGA2011 Boutronic B.V.
Boutronic B.V. Page - 6 - ’s-Gravenzande The Netherlands
Change settings
The settings of the JGA2011 can be changed in two ways:
With the potentiometer, the DIP-switches and the programming button or with the USB port of the
PC in combination with the Boutronic USB dongle.
Potentiometer
The switching threshold of the relay is set with the potentiometer. Each relay has its own
potentiometer. When DIP-switch 3 is OFF, the setting through the potentiometer is active.
DIP-switches
A 4-fold DIP-switch is available on the JGA2011. The following functions can be enabled or disabled
by means of the DIP-switches:
DIP
Off
On
1
Reserved
Reserved
2
Reserved
Reserved
3
Use potentiometer for threshold level.
Delay is fixed 1 seconds and the
hysteresis is fixed 1%
Use software settings for threshold level,
Delay and hysteresis
4
Reserved
Reserved
Setting with the serial menu
You can change the settings with the USB port and the Boutronic Studio. The Boutronic Studio can be
downloaded from our website:
www.boutronic.nl/producten/boutronic_studio_instellen_via_windows
To connect the JGA2011 to the PC follow the next steps:
1. Connect the JGA2011 to your PC by a Boutronic USB dongle
2. Open the Boutronic Studio 2 with the tab ‘Terminal’, set the baud rate to 9600 and connect
3. Click on the black screen with the mouse and press three times the + (+++)
The following text is given on the screen:
--- MENU ---
1. Relay 1
2. Relay 2
D. Debuglevel
9. Factory defaults
T. Factory test
With the ‘1, 2, D, 9 and T’ the option will be selected
With the ‘+’ key the output level will be increased
With the ‘-’ key the output level will be decreased
With the ‘enter’key the value will be stored.
With the ‘esc’key the programming will be stopped.
With the ‘9’ key you will set all setting to factory levels

Manual Current relay print JGA2011 Boutronic B.V.
Boutronic B.V. Page - 7 - ’s-Gravenzande The Netherlands
Relay 1
Menu for changing setting relay 1
Value
Description
range
Factory
settings
Level: x %
Switching level when the relay is switching
0 ... 100 %
50 %
Hysteresis: x %
Hysteresis in %
1 ... 10 %
1 %
Delay on: x sec
Switching delay on
0 ... 600 sec
1 sec
Delay off: x sec
Switching delay off
0 ... 600 sec
1 sec
Relay 2
Menu for changing setting relay 2
Value
Description
range
Factory
settings
Level: x %
Switching level when the relay is switching
0 ... 100 %
50 %
Hysteresis: x %
Hysteresis in %
1 ... 10 %
1 %
Delay on: x sec
Switching delay on
0 ... 600 sec
1 sec
Delay off: x sec
Switching delay off
0 ... 600 sec
1 sec
Debug level
This option is for factory use only.
Factory defaults
This option can set all programming values to factory values.
Value
Description
N. No
No values will be set to factory values
Y. Yes
All values will be set to factory values
Factory test
This option is for factory test only.

Manual Current relay print JGA2011 Boutronic B.V.
Boutronic B.V. Page - 8 - ’s-Gravenzande The Netherlands
Technical specifications
General
Description
Value
Unit
Remarks
Measurement
90 x 36 x 57
mm
L x B x H
Mounting
DIN-rail (Top hat rail)
IEC/EN 60715
Material
Plastic ABS
Weight
80
gram
Max
Temperature storage
-20 … +60
C
Temperature operational
0 … +70
C
Relative humidity
10 ~ 95% RH @ 40 C,
non-condensing
Protecting range
IP20
Power
Description
Min
Typ.
Max
Unit
Remarks
Power in
20
24
30
VDC
20
24
24
VAC
1
-
35
-
mA
Power out
20
-
30
VDC
2
-
-
150
mA
3
1. Note: one of the phases is directly connected to the GND
2. This voltage is equal to the power supply in (single-sided rectified and with capacitor
buffered)
3. With a resettable fuse
Inputs
Current input
Description
Min
Typ.
Max
Unit
Remarks
Input voltage
-
-
30
VDC
Input current
4
-
20
mA
Max 30 mA
Input impedance
500
Ω
Outputs
Relay
Min
Typ.
Max
Eenheid
Opmerkingen
Switching voltage
-
-
30
VDC
Contact current
1
-
500
mA
Contact impedance
0,1
-
-
Ω
Separation
-
-
500
VDC
Galvanic

Manual Current relay print JGA2011 Boutronic B.V.
Boutronic B.V. Page - 9 - ’s-Gravenzande The Netherlands
Measurements
38,0 mm
25,0 mm 7,5 mm
Top hat rail IEC/EN 60715
90,0 mm
62,0 mm
44,0 mm
26,0mm
47,0mm
57,0mm
90,0mm
36,0 mm
7
8
9
10
11
12
1
2
3
4
5
6
CONTROL
Powersupply
www.boutronic.nl
GND
+24VDC IN
Type nummer JGA2011
+24VDC OUT
4-20mA in 2
GND
Inputs 4-20mA RoHS compliant
TA : 0 ... 70 C
Relay 1
Relay 2
4-20mA in 1
Relay contacts : 24VAC/DC max 1000mA
: 24VDC 50mA
: R-load = 500 Ohm
7 8 9 10 11 12
123456
RoHS compliantType JGA2011
GND
4-20mA IN2
Relay 2
GND
4-20mA IN1
Relay 1
+24VDC IN
+24VDC OUT
www.boutronic.nl
Made in the Netherlands
Lift front here for access control
Table of contents