  9. LEGRAND IME DELTA TDGA2 User manual

LEGRAND IME DELTA TDGA2 User manual

t=0)
0ff
h.f.filter
~
0n 0ff
h.f.filter
55
66
88
33
1111
99
10
22
1
44
77
2
13
L3N
PE
L1L2
L1L2
L3N
X
Y
Z
X = Y = Z
D1 D2 D3
TORE FERME / CLOSED CORE
CODE PASSAGE CÂBLE IΔn min
(1) In Imax(2)
CODE PASSING CABLE A A A
TDGA2 Ø 28 0,03 65 390
TDGB2 Ø 35 0,03 70 420
TDGH2 Ø 60 0,03 90 540
TDGC2 Ø 80 0,05 170 1020
TDGD2 Ø 110 0,1 250 1500
TDGE2 Ø 140 0,3 250 1500
TDGF2 Ø 210 0,3 400 2400
TORE OUVRANT / OPEN CORE
CODE PASSAGGIO CAVO IΔn min
(1) In Imax(2)
CODE PASSING CABLE A A A
TDAA2 Ø 110 0,5 250 1500
TDAB2 Ø 150 0,5 250 1500
TDAC2 Ø 300 1 630 3780
(1) Courant mini. IΔn valeur mini. de IΔn sélectionnable sur le relais de
protection raccordé au tore
IΔn lowest current IΔn lowest value that can be set on earth leakage relay
connected with toroid
(2) Courant de test correspondant à 6In: Imax (IEC/EN 60947-2 annexe M)
Test current corresponding to 6In: Imax (IEC/EN 60947-2 annex M)
0,3...3A
0,03...0,3A 3...30A
TAB.1
BTicino SpA
Viale Borri, 231
21100 Varese - ITALY
www.imeitaly.com
Guide d’utilisation
User’s Guide
RD2B2
LE12566AA 10/20 - 01 IM

Réglage du seuil d’intervention I
Δ
n

Sélection du calibre x1 / x10 / x100
Vérifier que la valeur d’intervention sélectionnée est compatible avec le seuil
de sensibilité mini. du tore associé.
ÕÕLED segnalazione LED éteint
LED allumé
LED clignotant
ŒTouche de test
Permet de vérifier le fonctionnement tore-relais, commutation LED Trip allumée et commutation relais.
œTouche de reset l’état du relais est actif jusqu’à ce que l’opérateur agisse sur la touche RESET. Le réarmement
ne pourra s’effectuer lorsque le courant de défaut mesuré >50% I
Δ
nsélectionné.
–Sélecteur Reset
MAN (manuel) = après avoir détecté le défaut, le compteur entre len alerte définitive via les deux relais
R1 (17-18-19) e R2 (60-61-62).
L’aler te est active jusqu’à ce que l’opérateur agisse sur la touche RESET.
AUT (automatique) = après avoir détecté le défaut, l’appareil se réinitialise automatiquement via le relais
R1 (17-18-19) qui contrôle le contacteur, faisant 3 tentatives avec un intervalle de 1 minute.
Après les 3 tentatives, si l'appareil n'est pas réinitialisé, le contacteur ouvre définitivement. Si le réarmement
s’est effectué avec succès, au bout de 30 secondes, l’appareil efface automatiquement le nombre de tentatives.
Si le défaut persiste après l'ouverture du contacteur (R1), l’appareil entre en alerte définitive en ouvrant
l'interrupteur principal contrôlé par le relais (R2) sans feffectuer d’essai.
—Sélecteur d’état du relais de sortie R1 (17-18-19)
Nd (norm. désexcité) sécurtié négative - Ne (norm. excité) sécurtié positive.
Le relais R2 (60- 61-62) est toujours normalement désexcité.
“Réglage de la temporisation de la sortie relais R1 (17-18-19)
En réglant le seuil d’inter vention sur la position 0,03 le délai d’intervention est automatiquement exclu, indépen-
damment de la position du sélecteur de calibre

. Pour sélectionner le seuil d’intervention

I
Δ
n= 30mA avec
une intervention instantanée, sélectionner 0,03 et assurez vous que le sélecteur

est en position x1.
Le relais R2 (60-61-62) a un délai supplémentaire de 0,4 secondes par rapport à la valeur du délai
d'intervention sélectionné du relais R1 (17-18-19).
”Affichage instantané du courant différentiel (en % de la valeur I
Δ
n sélectionnée)

Insertion (on) - exclusion (off) filte pour les harmoniques.
ATTENTION
En raccordant le filtre pour les harmoniques, le différentiel ne doit pas être utilisé pour la protection des personnes.
INSTRUCTIONS POUR LE RACCORDEMENT
• La position de montage n’affecte en rien le bon fonctionnement du dispositif.
• Les opérations de réglage (seuil d’intervention, temporisation, etc.) doivent
être effectuées avec l’appareil hors tension.
• Suivre méthodiquement le schéma de raccordement : une erreur peut altérer le fonctionnement ou causer des dommages au
relais.
• Pour le fonctionnement optimal du système de protection différentielle, les recommandations d’installation
suivantes doivent être respectées :
+
Réduire autant que possible la distance entre le tore et le relais.
+
Utiliser les câbles de raccordement tore-relais blindés ou torsadés.
+
Eviter de placer les câbles de raccordement tore-relais parallèlement à des raccordements de puissance.
+
Eviter d’installer le tore et le relais près d’une souce de champ électomagnétique (gros transformateurs).
+
Passer dans le tore uniquement un conducteur actif (des.D1)
+
Si vous utilisez du câble blindé, l’armature doit être raccordée à la terre (des.D2)
+
Assurez vous que le conducteur soit positionné au centre du tore (des.D3).
n
•
Z
•Z•Z
SCHEMA DE RACCORDEMENT • WIRING DIAGRAMS
DIMENSIONS • OVERALL DIMENSIONS
70
89,5
65,6
45
44
TRANSFORMER
23
BA
INPUT
19 18 17
L1
L2
L3
N
46
RESET
60 61
R2
20
AUX.
SUPPLY
21
(+) (—)
62
R1
TRIP

Setting intervention threshold I
Δ
n

Range selector x1 / x10 / x100
Check that selected intervention value matches the lowest sensibility detectable by the connected ring current
transformer (see tab.1).
ÕÕSignaling LED LED off
LED on
LED blinking
ŒTest key
It allows to simulate alarm condition, LED Trip switching on and output relay switching.
œReset key the alarm stays until the operator doesn’t act on RESET key. Reset is not possible with persistent
residual current: >50% I
Δ
n.
–Reset selector
MAN (manual) = after having detected the failure, the meter enter the definitive alert through the two relays
R1 (17-18-19) and R2 (60-61-62).
The alert stays until the operator does not act on RESET key.
AUT (automatic) =after having detected the failure, the meter automatically resets through the R1 (17-18-19)
relay which controls the contactor, making 3 attempts with an interval of 1 minute.
After the 3 attempts, if the device is not reset, the contactor definitively opens.
In case of successful reset, after 30 seconds, the meter automatically clears the attempt count.
In case the failure persists after the contactor (R1) opening, the meter enter the definitive alert by opening
the master switch (R2) without making any attempt.
—Selector state of the R1 output relay (17-18-19)
Nd: (normally de-energized) negative security - Ne (normally energized) positive security
R2 relay (60-61-62) is always normally de-energized
“Setting intervention delay of the R1 output relay (17-18-19)
Selecting the intervenction threshold on position 0,03 the intervention delay is automaticall excluded, independently
of position of range selector,

. To set inter vention threshold

I
Δ
n= 30mA with instantaneous intervention,
select 0,03 and make sure that selector

is on position x1.
R2 relay (60-61-62) has a 0,4 second extra delay compared to the value of the selected inter vention delay of the
R1 relay (17-18-19).
”Instantaneous display of earth leakage current (in % of selected I
Δ
nvalue)

On-off harmonic filter
ATTENTION
By connecting the harmonic component filter, the differential must not be used to protect people.
WIRING INSTRUCTIONS
• Mounting position do not affect in any way the proper working.
• Setting operations (intervention threshold, delay time, etc.) must be carried out with non-fed meter.
• Please carefully follow the wiring diagram; an error in connecting the relay may give rise to irregular working or
damages.
• Four full functional of the earth relay the following installation recommendation should be adopted.
+
To reduce as much as possible the distance between ring current transformer and relay.
+
To use only shielded or twisted cables for their connection
+
To avoid in placing ring current transformer-relay connection cables parallelly to power wires
+
To avoid in mounting ring current transformer and relay near sources of intense electromagnetic fields
(big transformers).
+
Pass active conductor only through toroid (draw D1)
+
When using blind cable, ensure ground connection of armature (draw D2)
+
Ensure the central positioning of conductor through toroid (draw D3).
n
0,03 0,05 0,075 0,1 0,15 0,2 0,3
x1 30mA 50mA 75mA 100mA 150mA 200mA 300mA
x10 300mA 500mA 750mA 1A 1,5A 2A 3A
x100 3A 5A 7,5A 10A 15A 20A 30A
I
Δ
n
Ã
On
Õ
Trip / Fail
• • Manque de tension alimentation auxiliaire ou appareil défectueux
Z•Supervision • Supervision
Z Z Alarme • Alarm
Z• Z• ZInterruption du raccordement tore-relais • Connection breakdown between relay and ring current transformer
DESCRIPTION FACA AVANT • FRONT DESCRIPTION
ATTENTION
Schéma valable si sélecteur
—
en position Nd.
2-3: raccordement avec tore
4-6: réarmement déporté
20-21: dispositif alimentation auxiliaire
17-18-19: rrelais alarme R1
60-61-62: relais alarme R2
B1: 1° intervention bobine (intervention désexciation bobine contacteur)
B2: 2° intervention (intervention exciation bobine contacteur)
RESET: réarmement déporté (de série avec dispositif alim.aux.)
TRIP: signalisation visuelle de l’intervention de l’alarme éventuelle
ATTENTION
Wiring diagram valid with
—
selector in position Nd.
2-3: connection with ring transformer
4-6: remote rearmament
20-21: device extra supply voltage
17- 18-19: R1 alarm relay
60-61-62: R2 alarm relay
B1: 1° intervention coil (contactor coil dropout inter vention)
B2: 2° intervention coil (switch release coil dropout intervention)
RESET: remote rearmament (in series with device extra supply voltage)
TRIP: possible alarm inter vention visual signaling.
S 291/125
2
3
B
B1
LOAD
A
19 18
TRIP
17
L3
L2
L1
N
4
6
RESET
60 61
AUX.
R1
TRIP
R2
20 21
CT
B2
62
S 291/125x

This manual suits for next models

9

Other LEGRAND Relay manuals

LEGRAND 4 121 71 User manual

LEGRAND

LEGRAND 4 121 71 User manual

LEGRAND LEXIC 047 40 User manual

LEGRAND

LEGRAND LEXIC 047 40 User manual

LEGRAND 4 121 70 User manual

LEGRAND

LEGRAND 4 121 70 User manual

LEGRAND DPX3 160 User manual

LEGRAND

LEGRAND DPX3 160 User manual

LEGRAND LEXIC 047 43 User manual

LEGRAND

LEGRAND LEXIC 047 43 User manual

LEGRAND 0 405 14 User manual

LEGRAND

LEGRAND 0 405 14 User manual

LEGRAND IME DELTA D4-F User manual

LEGRAND

LEGRAND IME DELTA D4-F User manual

LEGRAND 6 037 72 User manual

LEGRAND

LEGRAND 6 037 72 User manual

LEGRAND 4 121 70 User manual

LEGRAND

LEGRAND 4 121 70 User manual

LEGRAND IME Delta D2-B User manual

LEGRAND

LEGRAND IME Delta D2-B User manual

LEGRAND Wattstopper LMCP-GE24 User manual

LEGRAND

LEGRAND Wattstopper LMCP-GE24 User manual

LEGRAND 0 038 11 User manual

LEGRAND

LEGRAND 0 038 11 User manual

LEGRAND KNX User manual

LEGRAND

LEGRAND KNX User manual

LEGRAND CX3 User manual

LEGRAND

LEGRAND CX3 User manual

LEGRAND Wattstopper LMRC-611-16M User manual

LEGRAND

LEGRAND Wattstopper LMRC-611-16M User manual

LEGRAND IME Delta 48-s User manual

LEGRAND

LEGRAND IME Delta 48-s User manual

LEGRAND LEXIC 26092 User manual

LEGRAND

LEGRAND LEXIC 26092 User manual

LEGRAND Wattstopper LMRC-611MCC User manual

LEGRAND

LEGRAND Wattstopper LMRC-611MCC User manual

LEGRAND LEXIC 0047 43 User manual

LEGRAND

LEGRAND LEXIC 0047 43 User manual

LEGRAND IME Delta D2-B User manual

LEGRAND

LEGRAND IME Delta D2-B User manual

LEGRAND Lexic 047 42 User manual

LEGRAND

LEGRAND Lexic 047 42 User manual

LEGRAND Celiane 673 91 User manual

LEGRAND

LEGRAND Celiane 673 91 User manual

LEGRAND 4 120 20 User manual

LEGRAND

LEGRAND 4 120 20 User manual

LEGRAND VANTAGE RadioLink EasyTouch II ScenePoint... User manual

LEGRAND

LEGRAND VANTAGE RadioLink EasyTouch II ScenePoint... User manual

Popular Relay manuals by other brands

Schrack LSZ6W Series Assembly

Schrack

Schrack LSZ6W Series Assembly

Notifier N-ANN-RLY product manual

Notifier

Notifier N-ANN-RLY product manual

Solcon TPR-6 instruction manual

Solcon

Solcon TPR-6 instruction manual

CD Automation Revo Sx user manual

CD Automation

CD Automation Revo Sx user manual

ABB REU 610 Technical reference manual

ABB

ABB REU 610 Technical reference manual

MICROENER IM30-SA Operation manual

MICROENER

MICROENER IM30-SA Operation manual

Pilz PNOZ XV2 operating instructions

Pilz

Pilz PNOZ XV2 operating instructions

GAE CMFD Product user manual

GAE

GAE CMFD Product user manual

Fike 55-048 Installation and maintenance instructions

Fike

Fike 55-048 Installation and maintenance instructions

SICK LGT 015 Technical description

SICK

SICK LGT 015 Technical description

NX NXP2-RL-SP installation instructions

NX

NX NXP2-RL-SP installation instructions

F&F BIS-410-LED quick start guide

F&F

F&F BIS-410-LED quick start guide

Comat Releco CMS-10F Short instruction manual

Comat Releco

Comat Releco CMS-10F Short instruction manual

Taco FuelMizer SR501-OR-4 instruction sheet

Taco

Taco FuelMizer SR501-OR-4 instruction sheet

Siemens 7PG17-XR151 manual

Siemens

Siemens 7PG17-XR151 manual

F&F 5908312595533 quick start guide

F&F

F&F 5908312595533 quick start guide

LOVATO ELECTRIC PMVF 10 quick start guide

LOVATO ELECTRIC

LOVATO ELECTRIC PMVF 10 quick start guide

GMI D1093S quick start guide

GMI

GMI D1093S quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.