
Page 16
LAARS Heating Systems
6. With the unit running, verify the supply gas pressure, manifold gas pressure, and CO2according to the
table below.
Supply Gas
Pressure
4” w.c. ≤ (supply pressure ) ≤ 13” w.c.
2
Table 4. Supply Gas Pressure
7. After placing the appliance in operation, the
Burner Safety Shuto Device must be tested.
To test:
(a) Close gas shuto valve with burner operating.
(b) The ame will go out and blower will continue
to run for the post purge cycle. One additional
attempt to light will follow. Ignition will not occur
as the gas is o. The ignition control will lockout,
and will have to be reset before the unit will
operate.
(c) Open gas shuto valve. Restart the appliance.
The ignition sequence will start again and the
burner will start. The appliance will return to its
previous mode of operation.
NOTE: Sizes 1000–2000 have two ignition controls
and two ignitors, which work independently of one
another. If the ignition control for stages 1 and 2
fails to properly light the main burners for those
stages, the second ignition control will still be
active, and will be able to energize stages 3 and
4. This, of course, will only occur if all other safety
devices conrm that the unit will run in a safe
condition.
4.B Set Up for High Altitude
( >2500 Feet )
Pennant appliances may be operated at high altitude
(7700 ft., 2347 m) with a reduction in output of approx-
imately 10%. At altitudes of less than or more than 7700
ft. (2347 m) the appliance will perform equally as well,
but with diering reductions in output. At elevations
higher than 7700 ft. (2347 m) the reduction in output
will exceed 10% and at elevations below 7700 ft. (2347
m) it will be less than 10%. High altitude adjustment
must not be made on appliances operating at elevations
below 2500 ft. (762 m).
No orice changes are required to adjust the
Pennant appliances for high altitude. High altitude
adjustment is accomplished by adjustment of the
gas valve manifold pressure and the air shutter(s).
The required instruments used to assist in these
adjust-ments are a CO2 or O2 Analyzer and a U-Tube
Manometer or other device capable of reading a
pressure of 2.5-3.0 inches w.c. (0.62-0.75 kPa).
Start the adjustment process by checking the
CO2 in the “as installed” condition. Adjust the air
shutter(s) so that the CO2 is about 8% or the O2is
about 6.8% for appliances operating on Natural Gas.
For appliances operating on LP Gas adjust the air
shutter(s) so that the CO2 is about 9.2% or the O2is
about 6.8%. Appliances with two blowers should be
adjusted so that the air shutters below each blower are
open the same amount.
Once the CO2 or O2 has been set, the manifold
pressure may be adjusted. Remove the 1/8 NPT plug
from the lower side of the gas valve that is to be
set and install a tting, hose and manometer. Start
the appliance and observe the manifold pressure.
Manifold pressure must be adjusted to 3.0 in. w.c.
(0.75 kPa) (for high altitude only, standard operating
pressure is 2.5 in. w.c. (0.62 kPa)). It is adjusted by
removing the slotted cap on the gas valve and turning
the adjustment screw (beneath the cap) clockwise to
increase pressure and replaced after the adjustments
have been completed and the tting, hose and
manometer have been removed and the 1/8" plug has
been replaced. Repeat this process until all gas valves
have been set. Note: The pressure can be set only
when the appliance is operating and only when the
particular gas valve being adjusted is energized by a
call for heat from the staging control.
After all of the gas valve manifold pressures have
been set, the CO2 or O2 must be reset. CO2 or O2
will have changed when the manifold pressure was
adjusted. Open the air shutter(s) to reduce the CO2or
O2 to the values achieved previously.
The procedure is complete when all gas valves are
adjusted to a manifold pressure of 3.0 in. w.c. (0.75
kPa) and the CO2 is adjusted to 8.0% for Natural Gas
appliances or 9.2% for LP appliances. When using an
O2 analyzer, the correct O2 is 6.8% for both Natural
Gas and LP appliances.
Caution
Should any odor of gas be detected, or if the
gas burner does not appear to be functioning
in a normal manner, close main shuto valve,
do not shut o switch, and contact your heating
contractor, gas company, or factory representative.
H2380000A
Customer Service and Product Support: 800.900.9276 • Fax 800.559.1583
Headquarters: 20 Industrial Way, Rochester, NH, USA 03867 • 603.335.6300 • Fax 603.335.3355
9 Brigden Gate, Halton Hills, Ontario, Canada L7G 0A3 (905) 203-0600 Fax: (905) 636-0666
www.Laars.com Printed in U.S.A. © Laars Heating Systems 1906 Document 1374A