Field Calibration Instructions
Overview
Brasch Generation 2 sensor boards are calibrated at the factory and have an expected
calibration duration of approximately two years. Environmental conditions may shorten or
prolong this period of time, but once the sensor parameters drift outside of acceptable
tolerances, the sensor board must be either be recalibrated or replaced.
This document outlines the procedure for performing field calibration of all Brasch Generation
2 sensor boards including:
Carbon Monoxide Models Nitrogen Dioxide Models Combination Models
G E2-CM-24 G E2-ND-24 G E2-NCM-24
G E2-CM-120 G E2-ND-120 G E2-NCM-120
G E2-CM-Remote G E2-ND-Remote G E2-NCM-Remote
TRN 2-CM-Remote TRN 2-ND-Remote TRN 2-NCM-Remote
GDCP-CM-Remote GDCP-ND-Remote GDCP-NCM-Remote
Required:
•Voltmeter
•Potentiometer Adjustment Tool
•100 PPM Carbon Monoxide Test Gas (for CO sensors)
•5.0 PPM Nitrogen Dioxide Test Gas (for NO2 sensors)
•Gas Flow Regulator
•Tubing
•Calibration Hood
Note: All of the above required parts are included with Brasch CO and NO2 Test Gas Kits.
FG01
Rev 1.0 – November 30, 2021 1
Procedure:
1. Turn power OFF to the sensor board
2. Move the calibration jumpers (JP4) so that both pins are covered by the jumpers
3. Turn power ON to the sensor board
4. Connect the negative voltmeter lead to COM (TP3)
5. Connect the positive voltmeter lead to AN OUT (TP7)
6. et the voltmeter to measure DC voltage (VDC)
a) If possible, set the meter to display the average voltage to smooth out readings
7. Use the potentiometer adjustment tool on R2 until the meter reads approximately 5.0 V
a) This number will fluctuate but should remain stable at or near 5.0 V
b) If necessary, adjust potentiometer R1 to fine tune to 5.0 V
8. Remove the top calibration jumper on JP4
9. Apply test gas directly to the sensor
a) The voltage at TP7 will begin to drop
10.Once the voltage stabilizes, remove the bottom calibration jumper on JP4
a) tabilization requires approximately 5 minutes from the application of gas
11. Remove test gas from the sensor
12.Verify that the voltage at TP7 returns to approximately the same value as was set in
step 7
a) tabilization may take approximately 5 minutes from the removal of gas
13.Cycle power to the sensor board to verify that calibration data has been saved
14.Repeat this procedure for any remaining sensor boards
FG01
Rev 1.0 – November 30, 2021 2
Troubleshooting:
•If any of the following errors are present, calibration data was corrupted and this
procedure needs to be repeated.
◦tandalone Detectors: 9997
◦BM Transmitters: 0x0008
◦Control Panel Remotes: ensor # Calibration Invalid
•If achieving stable voltages is not possible, it may be necessary to replace the sensor
and/or the sensor board.
◦Once the useful lifespan of the sensor is exceeded, the sensor can no longer be
recalibrated. Both carbon monoxide and nitrogen dioxide sensors have an expected
lifespan of up to 10 years; however, this period can be reduced with increased
exposure to the target gas or sensor poisons. Replacing the sensor should yield
more stable voltages.
◦Over time, control electronics can degrade or suffer damage. If this is the case,
replacing the sensor board should yield more stable voltages.
FG01
Rev 1.0 – November 30, 2021 3
COM (TP3)
Calibration Jumpers
[ZERO]
[ PAN]
AN OUT (TP7)
R2 R1
FG01
Rev 1.0 – November 30, 2021 4
Revision: 1.0
Issue Date: November 30, 2021
Document Number: FG01
© Brasch Environmental Technologies, LLC
All Rights Reserved
Technical Support Contact Information
Phone: 314-291-0440 ext. 1006
Fax: 314-291-0646
Email: [email protected]
Website: www.braschenvtech.com/support-for-existing-systems
General Contact Information
Phone: 314-291-0440
Fax: 314-291-0646
Email: [email protected]
Website: www.braschenvtech.com

This manual suits for next models

14

Popular Accessories manuals by other brands

Quincy lab 140AE-1 operating manual

Quincy lab

Quincy lab 140AE-1 operating manual

HomePro ZIR000 user manual

HomePro

HomePro ZIR000 user manual

DOL 20SCR Technical user guide

DOL

DOL 20SCR Technical user guide

RAB Smart Task installation manual

RAB

RAB Smart Task installation manual

Kemppi KMS 300 quick guide

Kemppi

Kemppi KMS 300 quick guide

Stearns 57,500 Series Installation and service instructions

Stearns

Stearns 57,500 Series Installation and service instructions

iGuzzini TWILIGHT COPENAGHEN manual

iGuzzini

iGuzzini TWILIGHT COPENAGHEN manual

Adelaide Annexe & Canvas Avan Deluxe installation guide

Adelaide Annexe & Canvas

Adelaide Annexe & Canvas Avan Deluxe installation guide

OHAUS 5000 instruction manual

OHAUS

OHAUS 5000 instruction manual

HOME8 WLS1300 quick start guide

HOME8

HOME8 WLS1300 quick start guide

MAXBOTIX MaxSonar quick start guide

MAXBOTIX

MAXBOTIX MaxSonar quick start guide

ioSmart iSmart56 Installation and user guide

ioSmart

ioSmart iSmart56 Installation and user guide

Focusrite Scarlett 18i8 user guide

Focusrite

Focusrite Scarlett 18i8 user guide

Velleman ED38105 user manual

Velleman

Velleman ED38105 user manual

JumpSport SkyBounce user manual

JumpSport

JumpSport SkyBounce user manual

Prima-Temp PRIYA Instructions for use

Prima-Temp

Prima-Temp PRIYA Instructions for use

Tefcold BC85I-BC85I W user manual

Tefcold

Tefcold BC85I-BC85I W user manual

Vaisala WMS302 user guide

Vaisala

Vaisala WMS302 user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.